Subject: OWTS Design
1650 County Road 237
Silt, Colorado
Reference: Geotechnical Investigation, 1650 County Road 237, Silt, Colorado by
Huddleston-Berry Engineering & Testing, LLC for Shane Wade, December 22,
2021.
Dear Mr. Wade,
At your request, Huddleston-Berry Engineering & Testing, LLC completed design of an Onsite
Wastewater Treatment System (OWTS) for a single-family residence at 1650 County Road 237
in Silt, Colorado. The site location is shown on Figure 1 – Site Location Map. A site plan is
included as Figure 2.
Site Description
At the time of the investigation, the site was open and gradually sloping down towards the east.
Site topography is shown on Figure 2. Vegetation consisted of weeds, grasses, and small to large
bushes and trees. The site was bordered to the north and east by residential/agricultural
properties, to the south by 250 Road, and to the west by Harvey Gap Road.
Subsurface Investigation
As indicated in the referenced report, three test pits were excavated in the vicinity of the
proposed Soil Treatment Area (STA). Test Pits TP-8 and TP-9 encountered 1.0 foot of topsoil
above loamy sand with gravel and cobbles. Test Pit TP-10 encountered 1.0 foot of topsoil above
silt loam. Groundwater was not encountered in the subsurface at the time of the investigation.
In general, HBET believes that the seasonal high groundwater in the vicinity of the proposed
STA is deeper than 6.0 feet.
The locations of the test pits are shown on Figure 2. Copies of the test pit logs are included in
Appendix A.
1650 County Road 237
#2388-0001
03/29/22
C:\HBET\Project Files\2022\02388-0001 1650 County Road 237\200 - Geo\02388-0001 LR032922.doc 2
Onsite Wastewater Treatment System
Seepage Bed Design
The design of the absorption system generally follows the requirements of the Garfield County
Board of Health as outlined in the Garfield County On-Site Wastewater Treatment System
(OWTS) Regulations, adopted June 2018. The proposed construction at the site is anticipated to
include a four-bedroom home.
Based upon visual-tactile classification of the site soils, a Long-Term Acceptance Rate (LTAR)
of 0.6 will be utilized for the absorption field design. Infiltrator Systems Quick4 Standard
Chambers are proposed. The daily flow of the sewage disposal system is calculated below, and a
plan and profile of the absorption system are shown on Figure 3.
Average Daily Flow = (7 persons)(75 GPD/person)
= 525 GPD
Soil Treatment Area = (525 GPD / 0.6) = 875 Square Feet
Adjusted Soil Treatment Area = (875 SF)(1.2)(0.7) = 735 Square Feet
# of Quick4 Chambers = (735 / 12) = 62 Chambers; Use 64 Chambers
System Installation
The installation of the septic tank, plumbing lines, Infiltrators, etc. should be completed in
accordance with the Garfield County On-Site Wastewater Treatment System (OWTS) Regulations
and Infiltrator Systems, Inc. specifications. In addition, the following construction procedures
are recommended:
The septic tank and distribution box should be placed level over native soils that have
been scarified to a depth of 8 to 12 inches, moisture conditioned, and recompacted to
a minimum of 95% of the standard Proctor maximum dry density, within ±2% of
optimum moisture content. However, up to 3-inches of washed rock or pipe bedding
passing the 1-inch sieve may be used as a leveling course under the septic tank and/or
distribution box.
The bottoms of trenches and backfill around the septic tank and distribution box
which will support sewer or effluent lines should be compacted to at least 90 percent
of the standard Proctor maximum dry density, within ±2% of optimum moisture
content. Pipe bedding should have a maximum particle size of 1-inch.
Vehicular or heavy equipment traffic and placement of structures should not encroach
within 10 feet of the septic tank or distribution box.
Inspection Schedule
Huddleston-Berry Engineering & Testing LLC should be retained to monitor the construction of
the OWTS. The following schedule of observation and/or testing should be followed:
Observe the absorption bed excavation prior to placement of Infiltrator chambers.
Observe placement of the septic tank, distribution box, and all connecting sewer and
effluent lines prior to backfill. Verify proper fall between inverts.
Observe and verify installation of the absorption bed prior to placement of cover and
backfill.
1650 County Road 237
#2388-0001
03/29/22
C:\HBET\Project Files\2022\02388-0001 1650 County Road 237\200 - Geo\02388-0001 LR032922.doc 3
In conformance with Garfield County regulations, HBET will be required to provide the Garfield
County Board of Health with documentation certifying that the OWTS was placed in
conformance to the plan and profile and Garfield County regulations.
General Notes
The OWTS design was based upon the results of the subsurface investigation and on our local
experience. The design is valid only for the proposed construction.
We are pleased to be of service to your project. Please contact us if you have any questions or
comments regarding the contents of this report.
Respectfully Submitted:
Huddleston-Berry Engineering and Testing, LLC
Michael A. Berry, P.E.
Vice President of Engineering
03/29/22
FIGURES
2789 Riverside ParkwayGrand Junction, CO 81501Project No.: 02388-0001Date: 03/29/22By: MAB1650 COUNTY ROAD 237PART OF PARCEL 212725400042FIGURE 2 - SITE PLANAPPROX. TEST PIT LOCATIONC.I. = 2 FTSCALE: 1" = 60'03/29/22
GENERALIZED BED PROFILECOVER SOIL; NATIVE SOILS OR OTHER SUITABLETOPSOIL. GRADE TO CARRY SURFACE WATERAWAY FROM BED.NONWOVEN, NEEDLE PUNCHED, GEOTEXTILEFABRIC IMMEDIATELY ABOVE CHAMBERSGENERALIZED SYSTEM PROFILE2789 Riverside ParkwayGrand Junction, CO 81501MINIMUM SETBACKS(UNITS = FT)**OTHER SETBACKS NOT LISTED HERE SHOULD BE IN ACCORDANCE WITH GARFIELD COUNTY OWTS REGULATIONSINFILTRATOR SYSTEMS QUICK4STANDARD CHAMBERS**USE SWEEP 90'S ORTWO 45'S AT 90DEGREE BENDS**DETAIL AREASCALE: 1" = 30'Project No.: 02388-0001Date: 03/29/22By: MAB4-INCH DIAMETER SEWER ANDEFFLUENT PIPE MEETING ASTMD1785, SCHEDULE 40 OR SDR 35SEPTIC TANK WITHMINIMUM 1,250GALLON CAPACITYDISTRIBUTION BOXTHAT ENSURES EVENDISTRIBUTION OFEFFLUENTINSPECTION PORTSINFILTRATOR SYSTEMSQUICK4 STANDARD CHAMBERSINSPECTION PORTSNEW RESIDENCE1650 COUNTY ROAD 237PART OF PARCEL 212725400042FIGURE 3 - SEPTIC SYSTEMDETAILSWELLWATER LINE03/29/22
APPENDIX A
Typed Test Pit / Perc Testing Logs
Silt LOAM with Organics (TOPSOIL)
Loamy SAND with Gravels and Cobbles (<35% rock), tan, moist,
structureless
Bottom of test pit at 6.0 feet.
NOTES
GROUND ELEVATION
LOGGED BY SD
EXCAVATION METHOD Trackh/Backhoe AT TIME OF EXCAVATION 5.5 ft
AT END OF EXCAVATION 5.5 ft
AFTER EXCAVATION ---
TEST PIT SIZE
EXCAVATION CONTRACTOR Client GROUND WATER LEVELS:
CHECKED BY MAB
DATE STARTED 11/10/21 COMPLETED 11/10/21
DEPTH(ft)0.0
2.5
5.0 GRAPHICLOGATTERBERG
LIMITS
MATERIAL DESCRIPTION
SAMPLE TYPENUMBERFINES CONTENT(%)RECOVERY %(RQD)BLOWCOUNTS(N VALUE)POCKET PEN.(tsf)DRY UNIT WT.(pcf)MOISTURECONTENT (%)LIQUIDLIMITPLASTICLIMITPLASTICITYINDEXPLASTICITYINDEXPAGE 1 OF 1
TEST PIT NUMBER TP-8
CLIENT Shane Wade
PROJECT NUMBER 02388-0001
PROJECT NAME 1650 County Road 237
PROJECT LOCATION Silt, CO
GEOTECH BH COLUMNS 02388-0001 1650 CR 237 USDA.GPJ GINT US LAB.GDT 3/24/22Huddleston-Berry Engineering & Testing, LLC
2789 Riverside Parkway
Grand Junction, CO 81501
970-255-8005
Silt LOAM with Organics (TOPSOIL)
Loamy SAND with Gravels and Cobbles (<35% rock), tan, moist,
structureless
Bottom of test pit at 3.0 feet.
NOTES
GROUND ELEVATION
LOGGED BY SD
EXCAVATION METHOD Trackh/Backhoe AT TIME OF EXCAVATION dry
AT END OF EXCAVATION dry
AFTER EXCAVATION ---
TEST PIT SIZE
EXCAVATION CONTRACTOR Client GROUND WATER LEVELS:
CHECKED BY MAB
DATE STARTED 11/10/21 COMPLETED 11/10/21
DEPTH(ft)0
1
2
3 GRAPHICLOGATTERBERG
LIMITS
MATERIAL DESCRIPTION
SAMPLE TYPENUMBERFINES CONTENT(%)RECOVERY %(RQD)BLOWCOUNTS(N VALUE)POCKET PEN.(tsf)DRY UNIT WT.(pcf)MOISTURECONTENT (%)LIQUIDLIMITPLASTICLIMITPLASTICITYINDEXPLASTICITYINDEXPAGE 1 OF 1
TEST PIT NUMBER TP-9
CLIENT Shane Wade
PROJECT NUMBER 02388-0001
PROJECT NAME 1650 County Road 237
PROJECT LOCATION Silt, CO
GEOTECH BH COLUMNS 02388-0001 1650 CR 237 USDA.GPJ GINT US LAB.GDT 3/24/22Huddleston-Berry Engineering & Testing, LLC
2789 Riverside Parkway
Grand Junction, CO 81501
970-255-8005
Silt LOAM with Organics (TOPSOIL)
Silt LOAM, brown, moist, blocky, moderate structure
Bottom of test pit at 3.0 feet.
NOTES
GROUND ELEVATION
LOGGED BY SD
EXCAVATION METHOD Trackh/Backhoe AT TIME OF EXCAVATION dry
AT END OF EXCAVATION dry
AFTER EXCAVATION ---
TEST PIT SIZE
EXCAVATION CONTRACTOR Client GROUND WATER LEVELS:
CHECKED BY MAB
DATE STARTED 11/10/21 COMPLETED 11/10/21
DEPTH(ft)0
1
2
3 GRAPHICLOGATTERBERG
LIMITS
MATERIAL DESCRIPTION
SAMPLE TYPENUMBERFINES CONTENT(%)RECOVERY %(RQD)BLOWCOUNTS(N VALUE)POCKET PEN.(tsf)DRY UNIT WT.(pcf)MOISTURECONTENT (%)LIQUIDLIMITPLASTICLIMITPLASTICITYINDEXPLASTICITYINDEXPAGE 1 OF 1
TEST PIT NUMBER TP-10
CLIENT Shane Wade
PROJECT NUMBER 02388-0001
PROJECT NAME 1650 County Road 237
PROJECT LOCATION Silt, CO
GEOTECH BH COLUMNS 02388-0001 1650 CR 237 USDA.GPJ GINT US LAB.GDT 3/24/22Huddleston-Berry Engineering & Testing, LLC
2789 Riverside Parkway
Grand Junction, CO 81501
970-255-8005