HomeMy WebLinkAboutOWTS Design129 Cains Lane Carbondale, CO 81623 970.309.5259 carla.ostberg@gmail.com April 14, 2022 Kim Velasquez kimmer.velasquez@gmail.com Onsite Wastewater Treatment System (OWTS) Inspection and Proposed Sewer Line Design 3062 CR 113 Garfield County, Colorado Kim, As requested, CBO Inc. performed an Onsite Wastewater Treatment System (OWTS) inspection at 3062 CR 113, Carbondale, Colorado on April 7, 2022. The legal description of the 5.349-acre property is as follows: Quarter: SW Section: 10 Township: 7 Range: 88 Subdivision: VELASQUEZ MINOR Lot: 1 AS PER MINOR SUBDIVISION PLAT RECEPTION NUMBER 891027 5.35 ACRES The permit, installation observations, and record drawing are enclosed. The subject OWTS consists of a 1000-gallon, two-compartment Infiltrator® poly septic tank followed by a distribution box connecting two gravelless chamber beds, each consisting of 3 rows of 7 ‘ARC’ ADS chambers for a total of 42 chambers and 630 square feet of infiltrative area. Permit SEPT-04-17-4668 documents this system. The system was sized to accommodate 3 bedrooms. The permit was issued on May 5, 2017. A detached garage with plumbing is proposed. Use of the plumbing in the garage will be auxiliary use to the main residence. A new sewer line must be installed connecting the new garage with the existing sewer line between the residence and the septic tank. The sewer line must be minimum SDR-35 (and minimum Schedule 40 under any area subject to traffic) with a double sweep clean out and minimum 2% grade to the septic tank. If the sewer line exceeds 100-feet, an additional clean out must be installed. For the purposes of this OWTS design, Benchmark Elevation has been established as 6324.5’ (100’). CBO Inc. should be notified of any discrepancies or problems with grade elevations of proposed components during installation of the OWTS. OWTS Component Minimum Elevation Primary Tank Inlet Invert (approx. 6318’) Approximate horizontal distance 120’ / min. 2% fall / min. 30” fall *Elevations are based upon standard OWTS installation practices. Component elevations may change during installation due to site conditions. Minimum grade refers to piping between components. The septic tank is located to the south of the residence. A clean out is located under the deck. Both septic tank lids were accessible from grade. Both inlet and outlet tees were present. An effluent filter was installed on the outlet side of the septic tank. This filter must be cleaned annually, or as needed. The liquid level in the outlet pipe was slightly high. The septic tank was last pumped in the fall of 2021 by B&R Septic. The distribution box was accessible from grade. There was an accumulation of sludge in the distribution box and the concrete was showing signs of deterioration. We recommend the sewer line from the septic tank to the distribution box be jetted and the distribution box be cleaned, and flow equalizers re-installed on the two pipes existing the distribution box. Inspection ports observed were present at the beginning and end of each bed. We walked the STA and found no evidence of surface saturation or failure at the time of the inspection. This evaluation is not a guarantee of future system performance. Recommendations: • Clean effluent filter annually, or as needed. • Jet sewer line from septic tank to distribution box. • Clean sludge out of distribution box. • Re-install flow equalizers on pipes existing distribution box. Disclaimer: This inspection is intended only as an evaluation of the present condition of the OWTS based upon what was observed and the Licensed Inspector’s expertise in onsite wastewater technology. The Inspector has not been retained to warrant or guarantee the proper functioning of the system for any period of time in the future. Because of numerous factors which may affect the operation of an OWTS, as well as the inability of the Inspector to supervise or monitor the use or maintenance of this OWTS, this report shall not be construed as a warranty by the Inspector that the system will function properly for any particular prospective buyer, and the Inspector disclaims any warranty, either expressed or implied, arising from the inspection of the OWTS or this report. The evaluation does not ascertain the impact the system is having on groundwater. Please call with questions. Sincerely, Carla Ostberg, MPH, REHS NAWT Certified Inspector Certification # 11044ITC Exp. April 2024 View of septic tank lids Clean out under deck Inlet tee Outlet tee with effluent filter Liquid level in outlet tee slightly high Distribution box Distribution box / sludge accumulation / concrete showing signs of deterioration / flow equalizers have fallen off pipes exiting box STA with inspection ports December 9, 2017 Project No. C1222 Ross Velasquez keanod33@gmail.com Rob Velasquez rob@pinemtn.net Onsite Wastewater Treatment System (OWTS) Installation Observations TBD Cattle Creek Road Lot 1, Velasquez Subdivision Garfield County, Colorado Permit Number SEPT-04-17-4668 Ross and Rob, ALL SERVICE septic, LLC observed the installation of the onsite wastewater treatment system (OW TS) on November 18 and December 8, 2017 for the subject property. You, the property owners, installed the system. Distances to the well on the adjoining property to the east, ditch to the west, and fire suppression stank were verified as meeting the minimum setbacks required by county regulation. The installation included a sewer line exiting the residence with a minimum 2% fall and double sweep clean out. A 1000-gallon, two-compartment Infiltrator® poly septic tank with an effluent filter on the outlet tee was installed. This filter must be cleaned annually, or as needed. Effluent gravity flows to a distribution box, and then to two gravelless chamber beds. The distribution box is accessible from grade. Each chamber bed consists of 3 rows of 7 ‘ARC 36’ chambers connected with a level manifold, for a total area of 630 square feet of infiltrative area. Inspection ports were installed in each corner of each bed. Ports may be cut to grade and placed in sprinkler boxes for access. The OWTS was generally installed according to specifications. This observation is not a guarantee of workmanship and/or parts and materials. ALL SERVICE septic, LLC should be notified if changes are made to the OWTS in the future. Any additional OWTS construction must be according to the county regulations. LIMITS: Observations are limited to components that are visible at the time of the inspection. The installer must have documented and demonstrated knowledge of the requirements and regulations of the county in which they are working. The quality of the installation is dependent of the expertise of the installer, soil type, and weather conditions. Please call with questions. Sincerely, ALL SERVICE septic, LLC Reviewed By: Carla Ostberg, MPH, REHS Richard H. Petz, P.E. View of chamber beds (note inspection ports installed in the second chamber) View of tank, distribution box, and chamber beds View looking north Septic tank View of OWTS after backfill Garfield County PERMIT CARD Community Development Department 108 8th Street, Suite 401 Glenwood Springs, CO 81601 Phone (970)945-8212 POST THTS IN A CONSPICIOUS PTACE WHEN CONSTRUCTION IS STARTED Project Address 3064 CR 113 Parcel No.2393ttJ30tJ047 Owner Name Tina & Robert Clay Velasquez & Robert Ross & Ke¿ Owne r phone 970-989-3008 Contractor(s)OWNER Contractor Phone Work Description New OWTS for s/f dwelling AGREEMENT ln consideration of the issuance of the permit, the applicant hereby agrees to comply with all laws and regulations related to the zoning, location, construction and erection of the proposed siructure for whichihis permit is granted. The applicant further agrees that if the above said regulations are not fully complied witn ¡n the zoning, location, erection and conètruction of the above described structure, the permit may then bó revoked by notice from the County Building division and immediately become null and void. Perc Test Final PLEASE SEE BACK OF PERMIT FOR OTHER COMMENTS ADDITIONAL INSPECTIONS MAY BE REQUIRED For Inspections Call (970) 945-1377 xl62l For Driveway Inspections Call (970) 625-8601 SHEET NO. SHEET TITLE COPYRIGHT ISSUED FOR GENERAL All designs ideas, arrangements and plans indicatedby these drawings and specifications are the propertyand copyright of the Architect and shall neither beused on any other work nor be used by any otherperson for any use whatsoever without writtenpermission Written dimensions shall take precedence over scaleddimensions and shall be verified at the job site. Anydimensional discrepancy shall be brought to theattention of the Architect prior to commencement ofthe work A G-1.0SCOT BROUGHTON Architects, LLCPO Box 4096 / 361 Southside Drive / Basalt, CO 81621[t] 970/927-0552 [f] 0554 / [e] sbarchitectsco@mac.comSBA1' = 1'-0", 1:0.50 COVER SHEETVELASQUEZ BARNLOT 1 VELASQUEZ SUBDIVISION3062 COUNTY ROAD 113CARBONDALE, CO 81623PERMIT SET 3/8/22, 1:54 PM V E L A SQUE Z B A R N PERMIT SET 3/8/22, 1:54 PM SHEET NO. SHEET TITLE COPYRIGHT ISSUED FOR GENERAL All designs ideas, arrangements and plans indicatedby these drawings and specifications are the propertyand copyright of the Architect and shall neither beused on any other work nor be used by any otherperson for any use whatsoever without writtenpermission Written dimensions shall take precedence over scaleddimensions and shall be verified at the job site. Anydimensional discrepancy shall be brought to theattention of the Architect prior to commencement ofthe work A G-1.1SCOT BROUGHTON Architects, LLCPO Box 4096 / 361 Southside Drive / Basalt, CO 81621[t] 970/927-0552 [f] 0554 / [e] sbarchitectsco@mac.comSBA1' = 1'-0" GENERAL INFORMATIONVELASQUEZ BARNLOT 1 VELASQUEZ SUBDIVISION3062 COUNTY ROAD 113CARBONDALE, CO 81623PERMIT SET 3/8/22, 1:54 PM AG-1.0 AG-1.1 AS-1.0 AS-1.1 A-1.0 A-1.1 A-2.0 A-3.0 S-1 S-2 S-3 S-4 COVER SHEET GENERAL INFORMATION SURVEY PARTIAL SITE PLAN FLOOR PLANS ROOF PLAN ELEVATIONS BUILDING SECTIONS FOUNDATION PLAN FLOOR FRAMING PLAN ROOF FRAMING PLAN DETAILS & GENERAL NOTES ANY DISCREPANCIES FOUND ON THESE PLANS AND WHERE THEY EXIST ON THESE CONSTRUCTION DOCUMENTS MUST BE BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO COMMENCEMENT OF WORK ALL WORK SHALL CONFORM TO THE BUILDING CODES & GUIDELINES OF THE REGULATING JURISDICTION. DO NOT DISTURB THE SITE BEYOND 5'-0" OF THE NEW BUILDING PERIMETER. DESIGNATE TREES AND SHRUBS FOR REMOVAL AND REPLANTING. ALL LANDSCAPING BEYOND THE AREA OF CONSTRUCTION TO BE PROTECTED. DISTURBANCE CREATED BY DEMOLITION IS TO BE RESTORED, FINAL GRADED AND RE-VEGETATED BUILDING FOOTPRINT IS TO BE STAKED FOR VERIFICATION OF CONFORMANCE WITHIN THE BUILDING SETBACKS AND VERIFICATION OF EXISTING GRADES. VERIFY SIZE AND LOCATION OF EXISTING UTILITY LINES WITH THE APPROPRIATE UTILITY COMPANY OR CONTRACTOR TO PERFORM WORK. ALL UTILITY LINES ARE TO BE BURIED. PROVIDE PROPER AND COMPLETE CONNECTION TO NEW CONSTRUCTION. SALVAGEABLE MATERIALS ARE TO BE STORED FOR POSSIBLE RE-USE. PROVIDE ENGINEERED SHORING AND BRACING AS NECESSARY. SURFACE & SUBSOIL DRAINAGE,AND SEDIMENT & EROSION CONTROL PLANS PER CIVIL ENGINEER'S RECOMMENDATIONS. DRAWING LIST GENERAL NOTES DIRECTORYABBREVIATIONS 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. L- LENGTH LAM- LAMINATE LAV- LAVATORY LBL- LABEL LH- LEFT HAND LIN- LINEAR LTL- LINTEL MAS- MASONRY MATL- MATERIAL MAX- MAXIMUM MECH- MECHANICAL MED- MEDIUM MEMB- MEMBRANE MET- METAL MFR- MANUFACTURER MIN- MINIMUM MISC- MISCELLANEOUS MLD- MOULDING MOV- MOVABLE MULL- MULLION N- NORTH NAT- NATURAL NIC- NOT IN CONTRACT NO- NUMBER NOM- NOMINAL NTS- NOT TO SCALE OA- OVERALL O/C- ON CENTER OD- OUTSIDE DIAMETER OH- OVER HANG OFF- OFFICE OPG- OPENING OPP- OPPOSITE PL- PLATE PL GL- PLATE GLASS PLMB- PLUMBING PLY- PLYWOOD PT- POINT PTD- PAINTED PVC- POLYVINYL CHLORIDE QT- QUARRY TILE R- RADIUS RA- RETURN AIR RECP- RECEPTACLE REF- REFERENCE REFR- REFRIGERATOR REG- REGISTER RET- RETURN REQ'D- REQUIRED REV- REVISED(ION) RD- ROOF DRAIN RH- RIGHT HAND RO- ROUGH OPENING ROW- RIGHT OF WAY RW HP- RANDOM WIDTH HEART PINE S- SOUTH SEC- SECTION SHT- SHEET SC- SOLID CORE SD- STORM DRAIN SHT- SHEET SIM- SIMILAR SP- SOUND PROOF SPEC- SPECIFICATION SPK- SPEAKER SQ- SQUARE SG FT- SQUARE FEET SS- STAINLESS STEEL STD- STANDARD STL- STEEL STRUCT- STRUCTURAL SYM- SYMMETRICAL SYS- SYSTEM T- TOP OF T- TREAD (@ STAIRS) T&G- TONGUE & GROOVE TEL- TELEPHONE TEMP- TEMPERED THK- THICK TYP- TYPICAL TV- TELEVISION UNF- UNFINISHED UON- UNLESS OTHERWISE NOTED VB- VAPOR BARRIER VERT- VERTICAL VG- VERTICAL GRAIN VIF- VERIFY IN FIELD VT- VINYL TILE W- WEST W/- WITH WC- WATER CLOSET WD- WOOD WDW- WINDOW WWF- WELDED WIRE FABRIC WP- WATERPROOFING WP HP- WIDE PLANK HEART PINE WS- WEATHER STRIPPING &- AND - ANGLE @- AT C.L.- CENTERLINE •, ', "- DEGREE, MINUTE, SECOND Ø- DIAMETER ', "- FOOT, INCH #- NUMBER - PERPENDICULAR AB- ANCHOR BOLT A/C- AIR CONDITIONING ADJ- ADJUSTABLE AFF- ABOVE FINISHED FLOOR ALT- ALTERNATE ALUM- ALUMINUM APPROX- APPROXIMATE ARCH- ARCHITECTS PLAN ASPH- ASPHALT AUTO- AUTOMATIC B- BOTTOM OF BD- BOARD BIT- BITUMINOUS BLDG- BUILDING BLK- BLOCK BLKG- BLOCKING BM- BEAM BOT- BOTTOM BS- BOTH SIDES BSMT- BASEMENT BRG- BEARING B PL- BEARING/BASE PLATE BVL- BEVELED CAB- CABINET C FL- COUNTER FLASHING C JT- CONTROL JOINT CL- CENTERLINE CLG- CEILING CLO- CLOSET CLR- CLEAR CMU- CONCRETE MASONRY UNIT COL- COLUMN CONC- CONCRETE CONST- CONSTRUCTION CONT- CONTINUOUS CORR- CORRIDOR CPT- CARPET CT- CERAMIC TILE CTR- CENTER DBL- DOUBLE DEG- DEGREE DIA- DIAMETER DIM- DIMENSION DR- DOOR DTL- DETAIL DWG- DRAWING E- EAST EA- EACH EB- EXPANSION BOLT EL- ELEVATION ELEC- ELECTRICAL ELEV- ELEVATOR EMER- EMERGENCY ENC- ENCLOSURE EQ- EQUAL EQUIP- EQUIPMENT EXH- EXHAUST EXIST- EXISTING EXT- EXTERIOR FD- FLOOR DRAIN FIN- FINISH FLR- FLOOR FND- FOUNDATION FP- FIREPLACE FT- FOOT FTG- FOOTING GA- GAUGE GALV- GALVANIZED GDO- GARAGE DOOR OPENER GL- GLASS GR- GRADE(ING) GYP- GYPSUM BOARD HB- HOSE BIBB HD- HEAD HD HT- HEAD HEIGHT HDW- HARDWARE HDWD- HARDWOOD HDR- HEADER HT- HEIGHT HTG- HEATING HORIZ- HORIZONTAL HVAC- HEATING/VENTILATION/AIR COND HW- HOT WATER ID- INSIDE DIAMETER IN- INCH INCL- INLUDE(D)(ING) INSUL- INSULATE INT- INTERIOR INV- INVERT JST- JOIST JT- JOINT KIT- KITCHEN KO- KNOCK OUT PROJECT INFORMATION OWNER Kim & Rob Velasquez 3062 County Road 113 Carbondale, CO 81623 ARCHITECT Scot Broughton Architects, L.L.C 361 Southside Drive Basalt, CO 81621 Phone: (970) 927-0552 sbarchitects@mac .com www.scotbarchitects.com CONTACT: Scot Broughton STRUCTURAL ENGINEER Silver Town Structures 307 AABC; Suite N Aspen, CO 81611 Phone: (970) 355-9169 CONTACT: Matt Monger GENERAL CONTRACTOR: To Be Determined SITE LEGAL DESCRIPTION: PARCEL #: 239310301001 SUBDIVISION: VELASQUEZ MINOR Lot: 1 AS PER MINOR SUBDIVISION PLAT RECEPTION NUMBER 891027 5.35 ACRES Quarter : SW Section: 10 Township: 7 Range: 88 Subdivision: GARFIELD COUNTY BUILDING CODES: IBC 2015 IRC 2015 MEP 2015 IECC 2015 CLIMATE ZONE: Zone 5B Vicinity Map SITE LOCATION SHEET NO. SHEET TITLE COPYRIGHT ISSUED FOR GENERAL All designs ideas, arrangements and plans indicatedby these drawings and specifications are the propertyand copyright of the Architect and shall neither beused on any other work nor be used by any otherperson for any use whatsoever without writtenpermission Written dimensions shall take precedence over scaleddimensions and shall be verified at the job site. Anydimensional discrepancy shall be brought to theattention of the Architect prior to commencement ofthe work A S -1.1SCOT BROUGHTON Architects, LLCPO Box 4096 / 361 Southside Drive / Basalt, CO 81621[t] 970/927-0552 [f] 0554 / [e] sbarchitectsco@mac.comSBA1" = 10' PARTIAL SITE PLANVELASQUEZ BARNLOT 1 VELASQUEZ SUBDIVISION3062 COUNTY ROAD 113CARBONDALE, CO 81623PERMIT SET 3/8/22, 1:54 PM 1 0 '-0 " 1 0 '-0 "25'-0"2 5 '-0 " 1 0 '-0 " 101'-1" 6325'-7" 1 0 0 '-1 0 " 6 3 2 5 '-4 " 100'-0"6324'-6" 100'-0"6324'-6" 6 3 3 0 6 3 3 1 6 3 3 2 6 3 3 3 6 3 2 5 6 3 2 2 6 3 2 1 6 3 2 0 6 3 1 9 6 3 1 8 6 3 1 7 6 3 2 4 6322 6321 6321 6321 6321 6318632163206321632063196 3 2 0 6 3 2 5 6 3 3 0 6 3 1 9 6 3 2 6 6 3 2 7 6 3 2 8 6 3 2 9 6 3 3 1 6 3 3 263336334 6 3 3 5 8" C.P.P. 15" C.M.P. 6" C.P.P. R.R.T. RET. WALL IRR. DITCH (TYP.) PROPOSED GARAGE FF: 6324.5' EXISTING DRIVEWAY TO REMAIN EXIST RESIDENCEFF: 6322.00 6340 6335 6 3 2 5 6 3 2 0 E X I S T I N G 8 " C U L V E R T E X I S T I N G 6 " C U L V E R T FUTUREPROPERTY LINEBOUNDARYLINE4 0 ' W I D E A C C E S S E A S E M E N T 1 0 'N 7 6 °1 0 '2 6 "E 3 0 .0 0 'S13°49'34"E2 0 .0 0 '1 0 .0 0 'N90°00'00"E 132.44'95.95'189.54' W A T E R T A N K E A S E M E N T 1 0 'S 23°54'42" E26.35'S 06°44'40" W131.82'Δ:30°39'23"R: 40.00'L: 21.40'1 4 ' 7 '7 ' 16' R : 5 '26'47' R : 1 5 'SWALESWALESWALE SWALE LOT 1 VELASQUES SUBDIVISION L O T 2 F U T U R E V E L A S Q U E S S U B D I V I S I O N BUILDING ENVELOPE 66'BUILDING ENVELOPEBUILDING ENVELOPE11' 11'1' 1 4 '4 '35' 4 :1 4:1 4 :1 4:1 10:110:110:110:110:110:1 10:1 10:1 10:1 10:1 10:110:1EXIST DRIVE PROPOSED DRIVE 6 3 2 4 CATTLE CREEK ROAD COUNTY ROAD 113 PLAN NORTH SITE ELEVATION 6324.5' EQUALS ARCHITECTURAL ELEVATION 100'-0" SHEET NO. SHEET TITLE COPYRIGHT ISSUED FOR GENERAL All designs ideas, arrangements and plans indicatedby these drawings and specifications are the propertyand copyright of the Architect and shall neither beused on any other work nor be used by any otherperson for any use whatsoever without writtenpermission Written dimensions shall take precedence over scaleddimensions and shall be verified at the job site. Anydimensional discrepancy shall be brought to theattention of the Architect prior to commencement ofthe work A -1.0SCOT BROUGHTON Architects, LLCPO Box 4096 / 361 Southside Drive / Basalt, CO 81621[t] 970/927-0552 [f] 0554 / [e] sbarchitectsco@mac.comSBA1/4" = 1'-0" FLOOR PLANSVELASQUEZ BARNLOT 1 VELASQUEZ SUBDIVISION3062 COUNTY ROAD 113CARBONDALE, CO 81623PERMIT SET 3/8/22, 1:54 PM15'-0" 9'-0"Sill 3'-0"100d 25'-0" 9'-0"Sill 3'-0"UP13T(11")14R(73/4")100a8'-0"9'-0"100b10'-0"10'-0"100c8'-0"9'-0"101a 102a 102b 2 2 A A B B C C 1 1 1/4:1213'-101/2"11'-11/2"15'-0"11'-31/4" 51/2" 11'-61/2" 51/2" 7'-01/4" 51/2" 3'-4"51/2"40'-0"27'-1"12'-11"40'-0"27'-1"12'-11"13'-101/2"13'-21/2"12'-11"17'-6"17'-6" 11'-6"12'-0"11'-6" 6'-1"11'-5"11'-5"6'-1"27'-1"51/2"8'-21/2"51/2"3'-91/2"1'-10" 9'-51/4"2'-31/2"11'-61/2"2'-31/2"5'-73/4"3'-91/2" 35'-0" T.O. SLAB @ PERIM. 100'-0" T.O. SLAB 100'-0" = 6324'-6" T.O. SLAB 100'-0" = 6324'-6" T.O. APRON 99'-111/4" 1 A-3.0 1 A-3.0 2 A-3.0 2 A-3.0 3 A-3.0 3 A-3.0 1 A-2.0 2 A-2.0 3 A-2.0 4 A-2.0 CONC. APRON 3-CAR GARAGE 100 STORAGE #1 101 STORAGE #2 102 MECH. 103 UP13T(11")14R(73/4")5 5'-0"9'-0"Sill 5'-2" 7 7'-0"9'-0"Sill 3'-2"43'-0" 9'-0"Sill 4'-53/4"UP 5T(0'-11")6R(0'-8")102a 2 2 A A B B C C 1 163'-0" 9'-0"Sill 4'-53/4"10:1210:1210:1210:1210:12 1 A-3.0 1 A-3.0 2 A-3.0 2 A-3.0 3 A-3.0 3 A-3.0 1 A-2.0 2 A-2.0 3 A-2.0 4 A-2.0 3'-0"40'-0"27'-1"12'-11"6'-51/2"6'-51/2"40'-0"27'-1"12'-11"6'-51/2"6'-51/2"35'-0" 17'-6"17'-6" 35'-0" 17'-6"17'-6" 22'-31/2"3'-0" 51/2" 5'-0" 51/2" 3'-91/2"51/2"8'-21/2"51/2"3'-91/2"4'-83/4"43/4" 11'-41/2"11'-41/2" 43/4" 12'-111/2" 7'-71/4" 51/2" 18'-101/4" 51/2" 7'-71/4" T.O. PLWD. 109'-03/4" T.O. PLWD. 113'-03/4" OFFICE 200 PWDR 201 STORAGE 202 SCALE: 1/4" = 1'-0"1MAIN LEVEL FLOOR PLAN SCALE: 1/4" = 1'-0"2LOFT LEVEL FLOOR PLAN SHEET NO. SHEET TITLE COPYRIGHT ISSUED FOR GENERAL All designs ideas, arrangements and plans indicatedby these drawings and specifications are the propertyand copyright of the Architect and shall neither beused on any other work nor be used by any otherperson for any use whatsoever without writtenpermission Written dimensions shall take precedence over scaleddimensions and shall be verified at the job site. Anydimensional discrepancy shall be brought to theattention of the Architect prior to commencement ofthe work A -1.1SCOT BROUGHTON Architects, LLCPO Box 4096 / 361 Southside Drive / Basalt, CO 81621[t] 970/927-0552 [f] 0554 / [e] sbarchitectsco@mac.comSBA1/4" = 1'-0" ROOF PLANVELASQUEZ BARNLOT 1 VELASQUEZ SUBDIVISION3062 COUNTY ROAD 113CARBONDALE, CO 81623PERMIT SET 3/8/22, 1:54 PM 2 2 A A B B C C 1 1 10:12 4:12 10:12 4:12 1 A-3.0 1 A-3.0 2 A-3.0 2 A-3.0 3 A-3.0 3 A-3.0 1 A-2.0 2 A-2.0 3 A-2.0 4 A-2.0 2'-0"20'-113/4"8'-01/2"10'-113/4"1'-71/2"2'-0"1'-0"1'-0"2'-0"1'-0" 1'-6"1'-6" 5'-0" SCALE: 1/4" = 1'-0"1ROOF PLAN SHEET NO. SHEET TITLE COPYRIGHT ISSUED FOR GENERAL All designs ideas, arrangements and plans indicatedby these drawings and specifications are the propertyand copyright of the Architect and shall neither beused on any other work nor be used by any otherperson for any use whatsoever without writtenpermission Written dimensions shall take precedence over scaleddimensions and shall be verified at the job site. Anydimensional discrepancy shall be brought to theattention of the Architect prior to commencement ofthe work A -2.0SCOT BROUGHTON Architects, LLCPO Box 4096 / 361 Southside Drive / Basalt, CO 81621[t] 970/927-0552 [f] 0554 / [e] sbarchitectsco@mac.comSBA1/4" = 1'-0" ELEVATIONSVELASQUEZ BARNLOT 1 VELASQUEZ SUBDIVISION3062 COUNTY ROAD 113CARBONDALE, CO 81623PERMIT SET 3/8/22, 1:54 PM 2 1 T.O. FTG. 96'-6" T.O. SLAB @ MAIN L. 100'-0" T.O. PLWD @ LOFT 109'-0" T.O. PLATE 117'-6 1/4" T.O. PLATE 112'-0"4'-93/4"2'-33/4"R.O.1'-103/4"3'-2"7'-03/4"R.O.4 12 10 12 4x4 KNEE BRACE 4x6 RAFTER TAIL 7 3 C B A T.O. FTG. 96'-6" T.O. SLAB @ MAIN L. 100'-0" T.O. PLWD @ LOFT 109'-0" T.O. PLATE 117'-0"3'-0"5'-03/4"R.O.4'-53/4"3'-03/4"R.O.8'-11/2"R.O.10 12 10 12 4x4 KNEE BRACE4x4 KNEE BRACE4x6 RAFTER ASPHALT SHINGLES TO MATCH HOUSE 1 4 100d 1 2 T.O. FTG. 96'-6" T.O. SLAB @ MAIN L. 100'-0" T.O. PLWD @ LOFT 109'-0" T.O. PLATE 117'-0"14'-2"5'-03/4"R.O.4 12 10 12 4x4 KNEE BRACE 4x4 KNEE BRACE 4x6 RAFTER 5 100c100b100a A B C T.O. FTG. 96'-6" T.O. SLAB @ MAIN L. 100'-0" T.O. PLWD @ LOFT 109'-0" T.O. PLATE 117'-0"4'-53/4"3'-03/4"R.O.3'-0"5'-03/4"R.O.111/4"ASPHALT SHINGLES TO MATCH HOUSE CHANNEL SIDINGTO MATCH HOUSE 2 6 SCALE: 1/4" = 1'-0"1NORTH ELEVATION SCALE: 1/4" = 1'-0"2EAST ELEVATION SCALE: 1/4" = 1'-0"3SOUTH ELEVATION SCALE: 1/4" = 1'-0"4WEST ELEVATION SHEET NO. SHEET TITLE COPYRIGHT ISSUED FOR GENERAL All designs ideas, arrangements and plans indicatedby these drawings and specifications are the propertyand copyright of the Architect and shall neither beused on any other work nor be used by any otherperson for any use whatsoever without writtenpermission Written dimensions shall take precedence over scaleddimensions and shall be verified at the job site. Anydimensional discrepancy shall be brought to theattention of the Architect prior to commencement ofthe work A -3.0SCOT BROUGHTON Architects, LLCPO Box 4096 / 361 Southside Drive / Basalt, CO 81621[t] 970/927-0552 [f] 0554 / [e] sbarchitectsco@mac.comSBA1/4" = 1'-0" BUILDING SECTIONSVELASQUEZ BARNLOT 1 VELASQUEZ SUBDIVISION3062 COUNTY ROAD 113CARBONDALE, CO 81623PERMIT SET 3/8/22, 1:54 PM 21 T.O. FTG. 96'-6" T.O. SLAB @ MAIN L. 100'-0" T.O. PLWD @ LOFT 109'-0" T.O. PLWD. 113'-0 3/4" 1'-43/4"5'-0"6'-7"5'-6"T.O. PLATE 117'-0" 1'-43/4" 6'-8"40° 10 12 4 12 4x6 RAFTER TAIL STORAGE 202 3-CAR GARAGE 12'-0"1'-03/4"1 2 T.O. FTG. 96'-6" T.O. SLAB @ MAIN L. 100'-0" T.O. PLWD @ LOFT 109'-0" T.O. PLATE 117'-0" 1'-0" 1'-6" 10 12 412 10 12 OFFICE 200 PWDR 201 3-CAR GARAGE 100 STORAGE #1 101 STORAGE #2 102 A B C T.O. FTG. 96'-6" T.O. SLAB @ MAIN L. 100'-0" T.O. PLWD @ LOFT 109'-0" 3'-0" 2'-0"2'-0" T.O. PLWD. 113'-0 3/4"12'-0"8'-0"1'-0"4'-03/4"10 12 3-CAR GARAGE 100 STORAGE 202 OFFICE 200 SCALE: 1/4" = 1'-0"1CROSS SECTION THRU GARAGE SCALE: 1/4" = 1'-0"2CROSS SECTION THRU STORAGE #1+STORAGE #2 SCALE: 1/4" = 1'-0"3LONGITUDINAL SECTION THRU GARAGE DRAWING NUMBER CHECKED BY DRAWN BY DATE JOB NUMBERVELASQUEZ BARN3062 County Road 113Garfield County, COMAM REVISIONS 307N AABC(970) 300-1003Aspen, CO 8161103/07/22 21-518 StructureSSilver Town HLB PERMIT SET S1 1 2 AA C B 21 B C T.O. CONC. SLAB @ PERIM. 100'-0" T.O.W. = 102'-6" T.O.F. = 97'-8" S4 1 S4 1 Footing Pad Schedule Mark Size Thick.Reinforcing A B C D E 2'-0" x 2'-0" 2'-6" x 2'-6" 3'-0" x 3'-0" 3'-6" x 3'-6" 4'-0" x 4'-0" 10" 10" 10" 10" 10" 3-#4 EA. WAY 4-#4 EA. WAY 3-#5 EA. WAY 4-#5 EA. WAY 4-#5 EA. WAY F G 4'-6" x 4'-6" 5'-0" x 5'-0" 10" 10" 5-#5 EA. WAY 5-#5 EA. WAY 1'-5 1/4"9'-3 1/2"1'-7 1/2"10'-3 1/2"1'-7 1/2"9'-3 1/2"1'-5 1/4" 35'-0"12'-11"3'-9 1/4"23'-3 3/4"40'-0"35'-0"27'-1"12'-11"40'-0"T.O.W. = 100'-6" T.O.F. = 97'-8" T.O.W. = 99'-4"T.O.W. = 99'-4"T.O.W. = 99'-4" T.O.W. = 100'-6" T.O.W. = 100'-6" T.O.F. = 97'-8" S4 1 4" CONCRETE SLAB W/ #4 @ 1' - 6" O.C. OVER 4" COMPACTED SOIL OR GRAVEL PROVIDE CONTROL JOINT @ 12' - 0" O.C. MAX. S1 1 S1 1 S1 1 S1 1 S4 3 S4 3 S4 3 S4 2 S4 2 10'-7 1/4"1'-4"11'-1 1/2"1'-4"2'-10 1/2"1'-4"2'-0 1/2"1'-4"3'-0 1/4"11'-4 1/4"1'-4"8 S6 2 S1 8 S6 2 S1 B B C C S1 3 S1 3 D D 10'-7 1/4"12'-5 1/2"10'-7 1/4"12'-0 1/4"13'-6 1/2"13'-1 1/4"T.O.W. = 100'-6"16" CONC. FOOTINGTYP. U.N.O.8" CONC. WALLTYP. U.N.O.Abv.A Abv.A Abv.A Abv.A Abv.A Abv.A Abv.A Abv.A Abv.A Abv.A Abv.C Abv.A Abv.A Abv.A Abv.A Abv.C Abv.A Abv.A Abv.A Abv.A Abv.C Abv.C Abv.T Abv.T Abv.B Abv.B Abv.A Abv.A D.T. D.T.D.T. D.T.D.T.D.T. 3 4 2HT BMS @ CORNER HT COLUMNTYP. POST & BM. @ CONC. PAD4" 10"45° T.O. SLAB SEE PLAN 2-#5 CONT. SEE PLAN 3" CLR.2X6 @ 16" O.C. BEARING WALL 2x6 BASE PLATE W/ 1/2"ØX10" EXP. ANCHOR @ 4' O.C. CONC. SLAB PER PLAN MONO FTG. @ CONC. SLABDBL. HT BEAM @ CONC. COLUMN2X6 LEDGER @ VAIULTED TRUSS1 BOT. OF KICKER @ GARAGE DOORSSTEEL COLUMN PER PLAN 1/4 3/4"Ø X 10" EXPANSION ANCHORS1/2" X 10" X 10" BASE PL. W/ 1 1/2" NON-SHRINK GROUT PAD & REINF. PER PLAN SEE PLAN 3"CLR.SLAB PER STR. GEN. NOTESS COLD JOINT BOND BREAK STEEL COLUMN 1'-0"3"1 1/2"1 1/2"6 3/4"WOOD BEAM PER PLAN PL 1/2 X SEE PLAN T.O. BM.MAN DOOR KICKER 25/8"Ø GR50 THREADED ROD WOOD PACKOUT PER PLAN 8" CONC. WALL PER 2/S4 3/4" X 8 X 1' 7 1/2" ST. PL. W/ (4) 12" #6 BARS L 2.5 X 3.5 X .25 W/ 2 1/2" #9 SCREW EVERY OTHER STUD 2 1/4"5"5"5"2 1/4"(2) #3 TIES IN TOP 6"8 3/8"LVL BEAM PER PLAN DBL. 5 1/2" LVL EA. SIDE OF KICKER; (4) TOTAL 5/8"Ø BOLT6 X 6 DF #16 X 6 D F # 1 4 3/4" 4" 1 1/2" X 1 1/2" X 1 1/2" MORTISE & TENON W/ 1/2"Ø X 10 LAG 5/8"Ø BOLT TY P . S O L I D B L O C K I N G TY P . S O L I D B L O C K I N G A35 CLIP EA. SIDE TOP & BOT (4) TOTALTOPBOTTOM 1 2 AA C B 21 B C UP 3-CAR GARAGE STORAGE #1 STORAGE #2 D.T. D.T.D.T. D.T.D.T.D.T. DESIGN NOTES 1.Submit Prefabricated Truss Package to Engineer of Record - See Structural General Notes on S5. 2.Floor framing does not account for any gypcrete or concrete topping. 3.2x6 ledger w/ (1) 3 5/8" HEADLOK screws @ 16" O.C. (ea. vert. stud). 4.Attach 2x6 rafter framing to wood beams or ledgers w/ (3) 10d toe-nails. 5.Various structural elements like beams and hangers may be custom order. In order to insure that the structure is built according to the designer’s intent the contractor shall fully review drawings prior to construction. COLUMN LEGEND DENOTES COLUMN BELOW. DENOTES COLUMN ABOVE OR TRANSFERED THIS LEVEL. DENOTES CONTINUOUS COLUMN. K.P. = KING POST D.T. = DOUBLE TRIMMERS PROVIDE ENOUGH STUDS TO MATCH WIDTH OF BEAM ABOVE. ALL COLUMNS SHOWN ARE 2-2x6's UNLESS NOTED AS FOLLOWS: WOOD PARALLAM, PSL STEEL A 3 - 2 x 6 J 3 1/2 x 3 1/2 S HSS 3 1/2 x 3 1/2 x 1/4 B 4 - 2 x 6 K 3 1/2 x 5 1/4 T HSS 4 x 4 x 1/4 C 5 - 2 x 6 L 5 1/4 x 5 1/4 U HSS 4 x 4 x 3/8 D 3 - 2 x 4 M 5 1/4 x 7 V HSS 4 x 4 x 1/2 E 4 - 2 x 4 W HSS 5 x 5 x 1/4 F 5 - 2 x 4 OTHER Y HSS 5 x 5 x 1/2 G 6 x 6 POST ST Existing Steel Z HSS 5 x 5 x 5/16 H 8 x 8 POST EX Existing Wood P HSS 7 x 3 x 5/16 WALL LEGEND Designation Construction Exterior wall Typical 2x framing. Provide cont. studs at 16" O.C. from botom plate to dbl. top plate. See General Notes typ. exterior wall in section C3. 355 Bearing Wall Typical 2x6 framing. Provide a double top plate with studs at 16" O.C. Sheathing varies. MULTIPLY BEAM FASTENING SCHEDULE # PLY FASTENERS 2 (2) - Rows 16d Common Nails @ 12" O.C.470 3 (3) - Rows 16d Common Nails @ 12" O.C 530 4 (2) - Rows 1/2"Ø bolts @ 24" O.C.340 HANGER SUMMARY HANGER FASTENER Beam Hangers LSSR210-2Z F: 22 - .162 X 2 1/2" J: 18 - .162 X 2 1/2" BA3.56/11.88 F: 16 - .162 X 3 1/2" J: 8 - .162 X 1 1/2" 10:1210:12 10:12 STR. KICKER STR. KICKER STR. KICKERSTR. KICKERSTR. KICKERSTR. KICKERSTR. KICKERSTR. KICKER11 7/8" TJI / 210 @ 16" O.C. 3 - 9 1/2" LVL 052 Beam 3 - 9 1/2" LVL 053 Beam 3 - 2 x 8 054 Beam 2 - 9 1/2" LVL055 Beam3 - 2 x 10 056 Beam 3 - 20" LVL 057 Beam 3 - 2 x 10 058 Beam 2 - 9 1/2" LVL059 Beam3 - 2 x 8060 BeamT.O. 3/4 PLY WD. 109'-0"3 - 2 x 8061 BeamOPEN 3 - 5 1/2" LVL 063 Beam 2 - 5 1/2" LVL2 - 5 1/2" LVL 2 x 6@ 24" O.C.2 x 6@ 24" O.C.LEDGER LEDGER LEDGER NOTE #3 NOTE #3NOTE #3 NOTE #3 S4 5 S4 3 S4 7 S4 3 S4 7 S4 6 S4 7 S4 7 S4 6 S1 4 NOTE #42 - 11 7/8" LVL088 Beam2 - 11 7/8" LVL089 Beam2 - 11 7/8" LVL090 Beam2 - 11 7/8" LVL091 Beam11 7/8" TJI / 210 @ 16" O.C. ITS2.06/11.88 11 7/8" TJI / 210 @ 16" O.C. ITS2.06/11.88 11 7/8" TJI / 210 @ 16" O.C. A35 1 - 11 7/8" LVL Joist Hangers LRU212Z F: 6 - .148 X 3" J: 7 - .148 X 3" ITS2.06/11.88 F: 6 - .148 X 3" J: 0 T.O. 3/4 PLY WD. 113'-0 3/4" 3 - 18" LVL 096 Beam [113'-0"][112'-0 1/8"][113'-0"][113'-0"][113'-0"]2 - 11 7/8" LVL [108'-11 1/4"] A35 1 - 11 7/8" LVL LVL BLOCKING [113'-0"] Abv.A Abv.A Abv.AAbv.A Abv.A Abv.A Abv.A Abv.A Abv.A Abv.M Abv.A Abv.A Abv.AAbv.M S2 DRAWING NUMBER CHECKED BY DRAWN BY DATE JOB NUMBERVELASQUEZ BARN3062 County Road 113Garfield County, COMAM REVISIONS 307N AABC(970) 300-1003Aspen, CO 8161103/07/22 21-518 StructureSSilver Town HLB PERMIT SET DRAWING NUMBER CHECKED BY DRAWN BY DATE JOB NUMBERVELASQUEZ BARN3062 County Road 113Garfield County, COMAM REVISIONS 307N AABC(970) 300-1003Aspen, CO 8161103/07/22 21-518 StructureSSilver Town HLB PERMIT SET 1 2 AA C B 21 B C COLUMN LEGEND DENOTES COLUMN BELOW. DENOTES COLUMN ABOVE OR TRANSFERED THIS LEVEL. DENOTES CONTINUOUS COLUMN. K.P. = KING POST D.T. = DOUBLE TRIMMERS PROVIDE ENOUGH STUDS TO MATCH WIDTH OF BEAM ABOVE. ALL COLUMNS SHOWN ARE 2-2x6's UNLESS NOTED AS FOLLOWS: WOOD PARALLAM, PSL STEEL A 3 - 2 x 6 J 3 1/2 x 3 1/2 S HSS 3 1/2 x 3 1/2 x 1/4 B 4 - 2 x 6 K 3 1/2 x 5 1/4 T HSS 4 x 4 x 1/4 C 5 - 2 x 6 L 5 1/4 x 5 1/4 U HSS 4 x 4 x 3/8 D 3 - 2 x 4 M 5 1/4 x 7 V HSS 4 x 4 x 1/2 E 4 - 2 x 4 W HSS 5 x 5 x 1/4 F 5 - 2 x 4 OTHER Y HSS 5 x 5 x 1/2 G 6 x 6 POST ST Existing Steel Z HSS 5 x 5 x 5/16 H 8 x 8 POST EX Existing Wood P HSS 7 x 3 x 5/16 WALL LEGEND Designation Construction Exterior wall Typical 2x framing. Provide cont. studs at 16" O.C. from botom plate to dbl. top plate. See General Notes typ. exterior wall in section C3. 355 Bearing Wall Typical 2x6 framing. Provide a double top plate with studs at 16" O.C. Sheathing varies. MULTIPLY BEAM FASTENING SCHEDULE # PLY FASTENERS 2 (2) - Rows 16d Common Nails @ 12" O.C.470 3 (3) - Rows 16d Common Nails @ 12" O.C 530 4 (2) - Rows 1/2"Ø bolts @ 24" O.C.340 DESIGN NOTES 1.Submit Prefabricated Truss Package to Engineer of Record - See Structural General Notes on S5. 2.Attach 2x6 @ 24" .O.C. ladder framing to 2X6 truss top chord w/ (3) 10d toe-nails. 3.2x6 ledger w/ (1) 3 5/8" HEADLOK screws @ 16" O.C. (ea. vert. stud). 4.DBL. 5 1/2" LVL ledger w/ (2) 6" HEADLOK screws @ 16" O.C. (ea. vert. stud). 5.Attach 2x6 rafter framing to 2x framing w/ (3) 10d toe-nails. 6.Various structural elements like beams and hangers may be custom order. In order to insure that the structure is built according to the designer’s intent the contractor shall fully review drawings prior to construction.10:1210:124:124:12NOTE #2 2 - 9 1/2" LVL048 Beam2 - 9 1/2" LVL 049 Beam 2 - 9 1/2" LVL050 BeamSTR. KICKERSTR. KICKERSTR. KICKERSTR. KICKER2 - 5 1/2" LVL067 Beam2 - 5 1/2" LVL 068 Beam 2 - 5 1/2" LVL 069 Beam 2 - 5 1/2" LVL070 Beam2 - 5 1/2" LVL 074 Beam STR. KICKER STR. KICKERLEDGERLEDGERLEDGERLEDGER2 x 6 @ 24" O.C.2 x 6@ 24" O.C.2 x 6@ 24" O.C.2 x 6 @ 24" O.C.2 x 6@ 24" O.C.PER 4/S4PER 4/S4PER 4/S4PER 4/S4A35A35A35NOTE #4NOTE #3NOTE #3NOTE #3NOTE #3 NOTE #5NOTE #5 NOTE #5NOTE #5NOTE #56 3/4 x 22 1/2 GL083 BeamLRU212Z 2 x 12 @ 16" O.C. 2 x 12 @ 16" O.C. LRU212Z 2 x 12 @ 16" O.C. 2 x 12 @ 16" O.C.2 - 11 7/8" LVL085 Beam2 - 11 7/8" LVL086 BeamBA3.56/11.882 - 11 7/8" LVL087 BeamLRU212Z 2 x 12 @ 24" O.C. LRU212Z 2 x 12 @ 24" O.C. LSSR210-2Z 2 - 2 x 12 092 Beam 2 - 2 x 12 093 Beam Btwn.A NOTE #2 NOTE #2 3 - 2 x 10 095 Beam S3ROOF SHEATHINGIS CONTINUOUSTO LOWER KICKERROOF FRAMINGSHOWN ON S2 DRAWING NUMBER CHECKED BY DRAWN BY DATE JOB NUMBERVELASQUEZ BARN3062 County Road 113Garfield County, COMAM REVISIONS 307N AABC(970) 300-1003Aspen, CO 8161103/07/22 21-518 StructureSSilver Town HLB PERMIT SET A. The foundation design was based on the following assumed parameters: Maximum allowable bearing pressure - 2,000 psf Minimum required dead load pressure - 0 psf Lateral soil pressure - Active 55 pcf - Passive 350 pcf The actual soil condition shall be investigated and the above parameters shall be verified by a Soils Engineer, registered in the State of Colorado, prior to construction of the foundation. If there are any discrepancies with the above assumptions, then the foundation shall be re-designed. CONCRETE: A. CONCRETE REQUIREMENTS Concrete has been designed and shall be constructed in accordance with the latest editions of the American Concrete Institute Building Code, ACI 318 and Specifications for Structural Concrete for Buildings, ACI 301. Provide hot or cold weather protection per ACI 305 & 306. 1. Concrete shall have a minimum compressive strength at 28 days of: Walls & footings 3000 psi Slabs 3000 psi 2. Provide Type II cement throughout with 4% air entrainment. 3. Mechanically vibrate concrete. 4. No admixtures shall be used without approval by the engineer. 5. Addition of water to the batch material for insufficient slump is not permitted. 6. Do not place pipes, ducts or chases in the structural concrete without the approval of the engineer. 7. Thoroughly clean all case and construction joints prior to placing concrete in adjacent pour. 8. Concrete shall not be in contact with aluminum. B. REINFORCING Detailing, fabrication, and erection of reinforcing steel bars shall comply with the ACI Manual of Standard Practice for Detailing Reinforced Concrete Structures ACI 315. 1. Reinforcing bars shall be ASTM A615-Grade 60. 2. Welded wire fabric shall conform to ASTM A185. Furnish in flat sheets only. 3. Concrete protection for reinforcement: Cast against and permanently exposed to earth ....... 3 in. Exposed to earth or weather............. #6-#18 bar........ 2 in. #3-#5 bar......1 1/2 in. Not exposed to earth or weather...... slabs & walls.....3/4 in. beams & cols....1 1/2 in. 4. Reinforcing lap splices shall be a minimum of 36 bar diameters unless noted otherwise. Lap wire fabric reinforcement one full mesh plus 2" at sides and ends and wire together. 5. Splices in horizontal beams and walls shall occur at midspan for top bars and over supports for bottom bars. 6. Discontinue one-half of horizontal steel across construction/control joints. 7. Provide corner bars of equal size and spacing around all corners. 8. Provide 2-#5 bars with a minimum of 2'-0" projection beyond the sides of all openings in walls, beams and slabs. Provide 1-#5 x 4'-0" diagonally at all re-entrant corners of slabs. 9. Provide accessories necessary to properly support reinforcing at the positions shown on the plans. 10. Reinforcing spacings are maximum on center and all reinforcing is continuous, unless noted otherwise. C. SLABS 1. Provide control joints at 12'-0" max. spacing or as shown on the plans. 2. Provide minimum 4" compacted gravel under floor slab on grade. The material shall consist of minus 2-inch aggregate w/ less than 50% passing the No. 4 sieve and less than 2% passing the No. 200 sieve. STRUCTURAL GENERAL NOTES & SPECIFICATIONS STRUCTURAL STEEL: A. STRUCTURAL STEEL Structural steel shall be detailed, fabricated and erected in accordance with latest provisions of the AISC Manual of Steel Construction and AISC Code of Standard Practice. Use welders meeting the requirements of the AWS Standard Qualification Procedure. Comply with AWS D1.1 Structural Welding Code. 1. All steel shall conform to ASTM A36 except beams shall be ASTM A992 Grade 50 and tube columns which shall conform to ASTM A500 (GR. B) and pipe shapes which shall conform to ASTM A53 (Gr. B). 2. Bolts shall conform to ASTM A325N. Anchor bolts shall conform to ASTM A307. Bolt size shall be 3/4" diameter unless noted otherwise. Installation shall be in accordance with AISC Specifications for Structural Joints Using ASTM A325 or A490 Bolts, 1978. 3. All welds shall be made with E70XX electrodes. 4. Prime all steel with approved primer paint to exposed bolts, welds, and abraded shop paint areas. 5. All column base plates shall have 1" minimum grout to provide continuous bearing. B. GROUT AND ANCHOR BOLTS 1. Dry pack or grout shall be shrink resistant Embeco 153 or equivalent. 2. Expansion bolts shall be Simpson "Wedge-All" or approved wedge type, installed in accordance with the manufacturer's requirements. 3. Headed anchor studs (H.D.A.S.) shall be attached to structural steel with equipment approved by the stud manufacturer according to the stud manufacturer's recommendations. 4. Anchor bolts embedded in concrete shall be placed with setting templates. 5. Location and coordination of anchor bolt placement shall be the responsibility of the steel fabricator. Steel fabricator shall supply anchor bolt setting plan. C. STEEL CONNECTIONS 1. Provide bolted connections for steel beams per Part 4 and Part 5 of the AISC Manual of Steel Construction. Except where otherwise shown, provide connections to support loads equal to one-half the total uniform load capacity of the member. 2. A minimum of two bolts shall be used for all connections. Size and grade shall be determined by the fabricator. STRUCTURAL WOOD FRAMING: A. DIMENSIONAL LUMBER All wood members shall be as described in the 2001 edition of the "National design Specifications for Wood Construction" by the National Forest Products Association and the WWPAW. 1. Unless otherwise noted on the drawings, wood framing members shall be Douglas Fir/Larch, Grade #2 or better. Redwood members shall be construction grade. 2. Sizes shown are nominal, except when noted as RC (Rough Cut) they are full dimensions. 3. All wood members attached to concrete or masonry shall be redwood or strandguard engineered lumber. 4. Block all joists and rafters per the I.R.C. B. FASTENERS AND CONNECTORS Alternate fasteners and connectors to those listed below, which have I.C.B.O. approval, may be used with approval by the Engineer. 1. Connectors shown on the plans are manufactured by the Simpson Strong-Tie Company, Inc. Connectors by other manufactures shall be deemed as equivalent if their rated capacity is equal to or greater than that of the connector specified. Follow manufacturer's recommendations for installation of connectors. 2. All timber nailing and connections shall conform to the IRC and AITC. 3. Bolts for wood member connections shall be 3/4" diameter, ASTM A307 with a minimum 1 1/2" washer at each end (unless noted otherwise). 4. Self-drilling fasteners for the attachment to structural steel shall be "Teks" fasteners as manufactured by Buildex. C. PLYWOOD SHEATHING Plywood sheathing for roofs, floors and exterior shear walls shall be APA Grade-Trademarked C-D, Exposure 1, unless otherwise noted. 1. Roof Diaphragms (240 plf) shall be 5/8", APA rated sheathing, 40/20 place with 8'-0" dimension perpendicular to the joist, rafter or truss span. End joists shall be staggered. Attach plywood at edges with 8d nails at 6" O.C. and at intermediate supports with 8d nails at 12" O.C. 2. Floor Diaphragms (250 plf) shall be 3/4", APA rated Sturdi-I-Floor, 24 O.C. place with 8'-0" dimension perpendicular to the joist span. End joints shall be staggered. Attach plywood with APA glue and at edges nail with 8d nails at 6" O.C. and at intermediate supports with 8d nails at 10" O.C. Sheathing shall be T&G. 3. Typical Exterior Wall Diaphragms (180 plf, 252 plf wind) shall be 1/2", APA rated sheathing, 24/0 with end joins staggered. Studs shall be 16" O.C. and sheathed full height. Attach plywood at edges with 8d nails at 6" O.C. and at intermediate supports with 8d nails at 8" O.C. D. GLUE LAMINATED BEAMS Laminated member shall be designed and fabricated in accordance with "The Standard Specifications for the Design and Fabrication of Structural Glue Laminated Lumber" published by the AITC and the appropriate Lumber Producers' Association. 1. Use exterior glue for all exposed laminated members. 2. All members exposed to weather shall receive one coat of end sealer at trimmed ends. Seal all exposed surfaces with sealer coat as soon as practical after erection. 3. Appearance grade shall be in accordance with the architectural drawings. 4. If beam is cantilevered and the cantilever is greater than one-third of the back span, install beam "TOP" down. 5. Allowable unit stresses for dry conditions of use required shall be as follows: Members stressed principally in bending such as beams & girders (AITC 24F-V4) unless otherwise noted on drawings. Fb=2400 psi Fv=165 psi Fc(perp)=650 psi E=1.8E6 psi Members stressed principally in compression or tension such as columns & truss members (AITC 24F-V8) Unless otherwise noted on drawings. Fc(parallel)=1650 psi E=1.6E6 psi E. MICRO-LAM BEAMS Micro-laminated members shall be designed and fabricated in accordance with the "National Research Board" and the "National Design Specifications for Wood". 1. Allowable unit stresses for dry conditions of use required shall be as follows: Fb=2600 psi Fv=285 psi Fc(perp)= 750 psi E=1.8E6 psi 2. Install micro-laminated members in accordance with the manufacturer's recommendation. 3. Holes, cuts, or notches not previously approved by the engineer or the manufacturer shall not be made. 4. Micro-laminated lumber is marked on the drawings as "ML" and shall be 1 3/4" wide, unless noted otherwise. F. FABRICATED WOOD JOISTS (I-Series) I-series fabricated joists with structural wood flanges and plywood webs called for on the drawings (TJI/210, TJI/360, TJI/560) are as manufactured by the Trus-Joist Corp.. Joists by other manufacturers may be used if the depth and deflection is equal to or less than that of the joist specified for the particular span and spacing and when authorized by the Architect/Engineer. 1. Fabricated wood joists shall be in accordance with the manufacturer's recommendations. 2. Supply all plates, blocking, bridging, bracing, stiffeners and other related items as recommended by the manufacturer. G. PRE-FABRICATED TRUSSES Provide engineered open web roof trusses as profiled by drawings and designed to handle live and dead loads with deflection limits of l/360 as indicated on the structural drawings. Submit design calculations, bearing the seal of the manufacturer's Engineer, with the shop drawings. Calculations shall indicate species and grade of lumber, design loadings and allowable stresses, force analysis of each member and design of each connection. 1. Truss manufacturer shall be a member of the Truss Plate Institute (TPI) and the Component Manufacturer's Council. 2. Shop drawings shall be supplied to detail each truss type, truss layout, bracing and any applicable connections with hangers related to truss to truss connections. 3. Supply all plates, blocking, bridging, bracing, stiffeners and other related items as recommended by the manufacturer. GENERAL: 1. Any changes to the contract drawings shall be submitted to the structural engineer for approval. 2. All dimensions and details on structural drawings shall be verified against the architectural drawings and any discrepancies shall be brought to the attention of the architect prior to fabrication or construction. Details on the structural drawings are typical. DO NOT SCALE DRAWINGS. 3. All openings through the structural system shall be approved by the Engineer. 4. Contractor shall provide all necessary temporary bracing, shoring, guying or other means to prevent excessive stresses and to hold the structural elements in place during construction. 5. The contract structural drawings and specifications represent the finished structure. They do not indicate the method of construction. The contractor shall provide all measures necessary to protect the structure during construction. Such measures shall include, but are not limited to bracing, shoring for loads due to construction equipment and protection of existing structures. Observation visits to the site by the structural engineer shall not include inspection of the above items nor will the structural engineer be responsible for the contractor's means, methods, techniques, sequences for procedure of construction, or the safety precautions and programs incident there to. 6. Options are for the convenience of the contractor. He shall be responsible for all changes necessary if he chooses an option and shall coordinate all details. The cost of additional engineering work necessitated by selection of an option shall be borne by the contractor. 7. Any engineering design provided by others and submitted for review shall bear the seal and signature of an engineer registered in Colorado. 8. Dimensions on the structural drawings are exact with the exception of masonry and sawn lumber dimensions which are nominal. Verify all dimensions with the architectural drawings. 9. Where required construction details are not shown or noted on these plans the contractor shall notify the engineer and the engineer shall provide sufficient details for the work to proceed. 10. Construction materials shall be spread out if placed on framed construction. Load shall not exceed the design live load per square foot. 11. Shop drawings shall be submitted to the architect for all structural items. The Engineers review is intended only as an aid to the contractor for obtaining correct shop drawings. Responsibility for correctness shall rest with the contractor. The contractor shall review all shop drawings prior to submittal. Items not in accordance with the contract documents shall be flagged upon his review. The shop drawings do not replace the original contract drawings. It is the contractors responsibility to make sure items are constructed to the original drawings. The adequacy of engineering designs and layout performed by others rests with the designing or submitting authority. A. DESIGN LIVE LOADS 1. Basic Roof Snow 40 PSF 4. Garage 40 PSF 2. Residential Floors 40 PSF 5. Wind 115 mph, Exposure B 3. Decks 40 PSF 6. Seismic Zone C B. DESIGN CODES International Residential Code, (IRC), 2015 with the International Building Code, (IBC), 2015 for Special Inspection American Concrete Institute Building Code (ACI 318-14) American Institute of Steel Construction, Manual of Steel Construction (AISC 9th Edition) American Institute of Timber Construction, Timber Construction Manual (AITC 5th Edition) National Design Specifications for Wood Construction (NDS2014) DESIGN DATA: FOUNDATION: B. EXCAVATION 1. Contractor shall provide all necessary sheeting, shoring and bracing where required to properly and safely complete the work. 2. Avoid excessive wetting or drying of the foundation excavation during construction. Keep excavations reasonably free of water at all time and completely free of water during placement of concrete. C. BEARING REQUIREMENTS 1. Footings shall bear on natural undisturbed soil below the frost depth required by the applicable building code. Any discrepancies with the footing elevations shown on the plans shall be brought to the attention of the engineer. 2. Building shall be founded on continuous concrete spread footings placed on undisturbed natural soil. D. GENERAL REQUIREMENTS 1. Center foundations under columns and walls unless noted otherwise. 2. Provide foundation ventilation in crawl space areas as required by the I.R.C. . 3. Backfill on walls with fill on both sides shall be compacted in equal lifts each side of wall. Walls backfilled on one side only shall have all supporting slabs, permanent framing or temporary bracing in place prior to placement of the backfill (unless noted otherwise on plans). 2 1 3 4 Abv. Cont. 3 - 2 x 8 3 - 2 x 6 3 - 2 x 8 3 - 2 x 8 HNGR A11 7/8" TJI / 210@ 16" O.C.3 - 11 7/8" LVL LSSUI2.1 T.O. PLY 100'-0"[99'-9 3/4"]Joist size and spacing Joist/beam bearing location Building elevation Joist/beam hanger designation (see schedule) Column from above with solid packout to below Column from above continuous to below Bearing wall below Header or beam size designation Column from above and to below Top of beam elevation Extents of joist or rafter Roof slope indication Column between beams Column from above terminating on beam Optional beam description B A B Column designation (See Schedule) Column to below T Joist/beam hanger designationFRAMING LEGEND Abv. Abv. A Btwn. A Btwn. 2 - 11 7/8" LVL Ridge 4:12 4:12 2-#5 CONT. #4 HORIZ. @ 1'-6" MAX. #4x @ 1'-4" VERT. 4" CONC. SLAB SEE PLAN 2-#5 CONT. TOP & BOTT. T.O. FTNG. SEE PLAN SEE PLAN T.O. WALL T.O. SLAB SEE PLAN 1/4" EXP. JOINT MAT'L 2X6 TREATED PLATE W/ 1/2"ØX10" EXP. ANCHOR @ 4' O.C. SEE PLAN 10"3"CLR.SOIL DRAIN #5 VERT. @ 1'-4" O.C. CENTER IN WALL 8" CONC. WALL @ CONC. SLAB32"6"MIN.3'-0"MIN. FROST2'-0"MAX.TYP. 8" CONC. WALL @ EXTERIOR2-#5 CONT. @ BOTT. 8" CONC. WALL SEE PLAN 3" CLR.10"T.O. FTNG. SEE PLAN 2-#5 CONT. #4 VERT. @ 1'-4" O.C. CENTER IN WALL #4 DOWELS @ 1'-6" O.C. 22"6"3'-0"MIN. FROSTSOIL DRAIN 2-#5 CONT. @ TOP BOND BREAK TREATED 2X6 SILL W/ 1/2"ØX10 EXP. ANCHOR @ 4' O.C. #4 HORIZ. @ 1'-4" O.C. MAX.6"MIN.T.O. WALL SEE PLAN FOR REINF. SEE 1/S5 8" CONCRETE WALL 8"#4x @ 18" O.C. SEE PLAN CONC. SLAB SEE PLAN T.O. SLAB3'-0"3'-0"TYP. TURNED DOWN CONC. SLAB7 5 6 GABLE END KICKERLOW GARAGE DOOR KICKERHIGH GARAGE DOOR KICKERMAN DOOR KICKER 1S4 A35 CLIP EA. SIDE TOP & BOT (4) TOTAL DBL. 5 1/2" LVL EA. SIDE OF KICKER; (4) TOTAL 3/4"Ø BOLT6 X 6 DF #16 X 6 D F # 1 2 3/4" 1 1/2" X 1 1/2" X 1 1/2" MORTISE & TENON W/ 1/2"Ø X 10 LAG 3/4"Ø BOLT DBL. 5 1/2" LVL EA. SIDE OF KICKER; (4) TOTAL 3 5 / 8 " A35 CLIP EA. SIDE TOP & BOT (4) TOTAL TY P . S O L I D B L O C K I N G TY P . S O L I D B L O C K I N G LVL BEAM PER PLAN WOOD FRAMING PER PLAN 6 X 6 D F # 1 DTT2Z 1/2"Ø BOLT W/ 2" SQ. WASHER A35 CLIP TOP & BOT. (4) A35 CLIPS @ 2X COLUMN PACKOUT; (2) INSIDE & (2) OUTSIDE 6 X 6 DF #11" LET IN 2 1/2" X 2 1/2" X 1 1/2" MORTISE & TENON W/ 1/2"Ø X 10 LAG FLOOR SYSTEM PER PLAN 11 7/8" LVL BLOCKING EA. SIDE 11 7/8" LVL BLOCKING EA. SIDE WOOD COLUMN PER PLAN WOOD FRAMING PER PLAN6 X 6 DF #11" LET IN (4) A35 CLIPS @ 2X COLUMN PACKOUT; (2) INSIDE & (2) OUTSIDE 6 X 6 D F # 1 5/8"Ø BOLT 2 1/2" X 2 1/2" X 1 1/2" MORTISE & TENON W/ 1/2"Ø X 10 LAG 2 1/2" X 2 1/2" X 1 1/2" MORTISE & TENON W/ 1/2"Ø X 10 LAG FLOOR SYSTEM PER PLAN 11 7/8" LVL BLOCKING EA. SIDE 11 7/8" LVL BLOCKING EA. SIDE (2) MSTA 30 STRAP 4" WOOD FRAMING PER PLAN WOOD FRAMING PER PLAN LS50 CLIP @ TOP A35 CLIP @ BOT. H7Z TIE (6) 6" HEADLOK SCREWS 4X4 DF #14X6 DF #1 WOOD COLUMN PER PLAN 3X4 DF #1 (2) TIMBERLOK SCREWS TOP & BOT. WOOD FRAMING PER PLAN Garfield County, CO Developed by Account Number R083984 Par cel Number 239310301001 Acr es 5 Land SqFt 0 T ax Ar ea 011 2019 Mill Levy 79.7760 Physical Addr ess 3062 113 C OUNTY RD C ARBONDALE 81623 Owner Addr ess VELASQ UEZ, ROBERT C LAY & TINA KIM 3062 C OUNTY ROAD 113 C ARBONDALE C O 81623 2019 T otal Actual V alue $767,790 Last 2 Sa les Date Pr ice 4/3/2021 $0 7/7/2017 $0 Date created: 4/14/2022 Last Data Uploa ded: 4/14/2022 2:14:11 AM 921 ft Overvi ew Legend Parcels Roa ds Parcel/Account Number s Highw ays Limited Access Highwa y Major Road Loca l Roa d Minor Road Other Road Ra mp Ferry Pedestria n Way Owner Na me Lakes & River s County Boundar y Line 832‐R‐13‐002