March 15,2022 Project No. C1675
Matt and Julie Fadden
c/o Richard Stumpf
richard@ristumpf.com
Subsurface lnvestigation and Onsite Wastewater Treatment System Design
5-Bedroom Residence
TBD Weeping Willow Lane
Lot 9, Roaring Fork Preserve
Garfield County, Colorado
Matt and Julie,
CBO lnc. performed a subsurface investigation and completed an onsite wastewater treatment system
(OWTS) design for the subject residence. The 15.411-acre property is located outside of Carbondale, in
an area where OWTSs and wells are necessary.
Legal Description: Section: 36 Township: 7 Range: 88 Subdivision: ROARING FORK PRESERVE Lot: 9
AS PER FIRST AMENDED PLAT RECEPTION NO. 945740 15.412 ACERS
Parcel lD: 2393-363-19-009
SITE CONDITIONS
The property is currently undeveloped. A 5-bedroom residence and equipment barn are proposed. The
equipment barn will have plumbing but will be an auxiliary use to the residence.
The property will be served by a private well on the property. At the time of this design, the well had not
been drilled. The well must be at least S0-feet from the proposed septic tank and at least 1O0-feet from
the proposed soiltreatment area (STA).
The site is subject to high seasonal groundwater. Groundwater was monitored in the test pits throughout
the summer and fall of 2021. High seasonal groundwater was oþserved in June at an approximate
elevation of 6204' . For purposes of the OWTS design, we are estimating groundwater at 6205'.
The property has an approximate 2 to 3% slope to the northwest toward the Roaring Fork River. The
proposed soil treatment area (STA) will be located at approximate native grade of 6208' to 6209'. The
area is vegetated with native grasses.
There should be no traffic or staging of material over the future STA site to avoid compaction of soils
prior to construction of the STA.
Page2
SUBSURFACE
The subsurface was investigated on March 30,2021 by digging two soil profile test pit excavations (Test
Pits). A visual and tactile soil analysis was completed by Carla Ostberg at the time of excavation.l
The materials encountered in Test Pit #1 consisted of medium brown topsoil to 1.5-feet, underlain by light
brown sandy loam with cobbles to a maximum depth explored of 7.0-feet. No bedrock or groundwater
was encountered.
The materials encountered in Test Pit #2 consisted of medium brown topsoil to 1.S-feet, underlain by light
brown sandy loam with cobbles to a maximum depth explored of 6.0-feet. No bedrock or groundwater
was encountered.
Piezometers were placed in the test pits and monitored throughout the summer and early fall2021.
Results of this monitoring are documented in an enclosed documented titled Groundwater Monitoring
Results. We have estimated high seasonal groundwater at 6205'.
A sample of the soils was taken from Test Pit #1 at 3-feet below grade. The soil formed a ball and a
weak ribbon less than 1-inch in length before breaking. Soilstructure shape was single-grain. Soil
texture was gritty.
STA sizing is based on Soil Type 2, Sandy Loam with rock content exceeding 65%. The proposed STA
will be partially mounded with a minimum 3-feet of sand filter material (Secondary Sand). A long term
acceptance rate (LTAR) of 0.8 gallons per square foot will be used to design the OWTS.
Test Pit View of Test Pit #1
I Carla Ostberg holds a Certifìcate of Attendance and Examination from the CPOW Visual and Tactile
Evaluation of Soils Training.
Page 3
Sieved sample
View of Test Pit #2
Page 4
DESIGN SPECIFICATIONS
Desiqn Calculations:
Average Design Flow = 75 GPD x 2 people/bedroom x 3 Bedrooms + 150 GPD (4th and 5th Bedrooms) =
600 GPD
LTAR = 0.8 GPD/SF
600 GPD / 0.8 GPD/SF = 750 SF
The OWTS design is based on 5-bedrooms. An average daily wastewater flow of 600 GPD will be used
For the purposes of this OWTS design, Benchmark Elevation at grade 6209' has been established as
100' (Finished Floor of the Main Residence). CBO lnc. should be notified of any discrepancies or
problems with grade elevations of proposed components during installation of the OWTS.
*Elevations are based upon standard OWTS installation practices. Component elevations may change during
installation due to site conditions. Minimum grade refers to piping between components.
The 4-inch diameter SDR 35 sewer line exiting the residence must have a double-sweep clean out and a
minimum 2o/o grade to the septic tank.
The system installation will include a 2000-gallon, two-compartment Valley Precast concrete septic tank
with an Orenco@ Biotube Pump Vault and an Orenco@ PF3005 pump in the second compartment of the
septic tank. We recommend anchoring the septic tank with Deadmen because of the high seasonal
groundwater table. The floats should be set to dose approximately 65 gallons each pump cycle, allowing
approximately 10.5 gallons of drain back. The control panel for the pump must be located within line of sight
of the septic tank. We recommend Valley Precast out of Buena Vista be contracted for start-up of the
pumping system.
Pum Table
OWTS Component Minimum Elevation
Primary Tank lnlet lnvert (6205' 6") Approximate horizontal distance 15' /
min.2o/o fall to septic tank / min. 3.75" fall
Automatic Distributing Valve (ADV)(Approx. 6210') Approximate horizontal distance
99' / min. 1% rise to ADV / min. 12.375" rise
lnfiltrative Surface Approximate horizontal distance to furthest zone 7'
/ min. 1% fall I min. 0.875" fall
Min. 38.5 gal. (7 gal x 4) + 10.5
oal drain back
Dose Range Max = 160 gal. (600 GPD x25%
+ 10.5 oal drain back)
65 gallons/dose 10.5 gallons drain back (99' / 1 .5"
diameter pump line)
Dose Setting
2000 gallon 2-compartmet Valley
Precast concrete septic tank
4.5" onloff float separationFloat Separation
Pump Criteria 20.3 gallons per minute (GPM)20.0 feet total dynamic head
(TDH)
Page 5
Effluent will be pressure dosed through a 1.5-inch diameter pump line to a partially mounded, unlined sand
filter. The sand filter will be divided into two beds, each 12' x31.5' with some room between beds for
plumbing for a total approximate length of 65-feet. The excavation for the sand filter will begin 2.O-foot below
native grade (6206'). A minimum of 3-feet of sand filter material will be installed in the over-excavated
footprint, resulting in 1-foot of sand filter material extending above native grade. Sand filter material must be
clean, coarse sand, all passing a screen having four meshes to the inch. The sand must have an effective
size between 0.15 and 0.60 mm. The uniformity coefficient must be 7.0 or less. Material meeting ASTM 33,
for concrete sand, with three percent or less fines passing 200 mesh sieve may be used. A gradation of
the sand media must be provided.
Effluent will be pumped through a 1.5-inch diameter pump line from the pump chamber to an Orenco@
automatic distributing valve (ADV), model 6404. This pump line must have a minimum 1o/o grade for proper
drain back into the tank after each pump cycle. This pump line will cross a driveway. We recommend a
minimum Schedule 40 conduit. The ADV must be placed at a high point of each zone and be placed in an
insulated riser with access from grade. Screened rock must be placed below the ADV to support the ADV
and to assure the clear pipes exiting the ADV remain visible for future inspection and maintenance.
Level, 1.5-inch diameter manifolds will connect two laterals on each bed (see W3.0/1 Partially Mounded
Sand Filter Plan). Laterals must be 1.5-inches in diameter with 5/32-inch diameter orifices facing down,
spaced 2-feeton center, installed on the GeoMatrM with the filter fabric over the laterals. Laterals should
be placed 2-feet from the edges of the beds leaving 3-feet between laterals and 2-feet between each section
connected by the ADV. Four 39" wide GeoMatrM must be placed on the 12-footwide bed. Mats will overlap
the sides of the bed by 6-inches on each side. All material associated with the GeoMatrM installation must
be proprietary products associated with the GeoMatrM, including orifice shields and geotextile fabric.
Manufacturer instructions must be followed regarding installation of the GeoMatrM.
Each 1.S-inch diameter lateral must end in a sweeping ellfacing up with a ballvalve for flushing. Laterals
must be covered by the GeoMatrM separation fabric and at least 1-foot of topsoil or other suitable soil able to
support vegetative growth. There shall be no cobble-sized (2.5") or greater rock in final cover over the
GeoMatrM. lnspection ports must be placed into the sand filter materialon each corner of the beds.
The mound must have a minimum 3:1 slope (horizontal;vertical); therefore, the basal area will extend
approximately 9-feet beyond the sand filter on all sides (with a mound height of approximately 3.O-feet above
native grade). Soils in the sloped perimeter areas of the mound must be well draining and able to support
vegetative growth. This soil must be approved by this office prior to installation. The mound must be
crowned in a manner to promote drainage off the STA.
COMPONENT SPECIFICATIONS
The component manufacturers are typical of applications used by contractors and engineers in this area.
CBO Inc. must approve alternative components prior to installation of the OWTS. Requests must
be submitted, in writing, to our office for approval prior to installation. Component technical data
sheets are available upon request.
COMPONENT MANUFACTURER MODEL NO COMMENTS
Septic Tank Valley Precast Item # 2000T-2CP-HH 2-compartment concrete
septic tank with high
read pump
Tank Deadmen Valley Precast Item # DM Anti-Buoyancy
Pump Orenco@ PF300511y2HP
120 Volt
Biotube ProPak Pump
Packaoe
Orenco@ BPP3ODD Vault, Filter, Control Panel
(demand dose)
Page 6
Construction must be according to Garfield County On-Site Wastewater Treatment System Regulations, the
OWTS Permit provided by Garfield County Building Department, and this design.
INSTALLATION CONTRACTOR
CBO lnc. expects that the installer be experienced and qualified to perform the scope of work outlined in this
design. The installer must review this design thoroughly and coordinate with our office in advance of
installation. Any additional conditions in this design or county permit must be completed and documented
prior to final approval of the OWTS installation. Communication between the installer and this office is
expected throughout the installation.
I NSTALLATION OBSERVATIONS
CBO lnc. must view the OWTS during construction. The OWTS observation should be performed before
backfill, after placement of OWTS components. Septic tanks, distribution devices, pumps, dosing
siphons, and other plumbing, as applicable, must also be observed. CBO lnc. should be notified 48 hours
in advance to observe the installation.
ln an effort to improve the accuracy of the record drawing, we request that the installer provide a
sketch of the installation, including path of the sewer lines, water line installation (if applicable),
septic tank location, STA location, and measurements from building corners or another fixed
objects on the property. This sketch is most easily provided on Sheet W2.0 of the OWTS Design
Packet. Photographs of the installation and final cover are also requested to supplement our installation
documentation.
REVEG ETATION REQUIREMENTS
An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire
disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing
characteristics (but without taproots), provides a maximum transpiration rate, and competes well with
successional species. No trees or shrubs, or any vegetation requiring regular irrigation shall be placed over
the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented
and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation
cover.
OPERATION INFORMATION AND MAINTENANCE
The property owner shall be responsible for the operation and maintenance of each OWTS servicing the
property. The property owner is responsible for maintaining service contracts for manufactured units,
alternating STAs, and any other components needing maintenance.
Tank Risers and Lids Orenco@ Double-walled PVC Risers and
Lids (24" diameteQ
ADV Orenco@ v64044 1.5" lnlet and Outlets
ADV Riser and Lid Orenco@ Double-walled PVC Risers
and Lids (30" diameter)
GeoMatrM GeoMatrix Systems,
LLC
252,GeoMa1rn,t (39,,)
Orifice Shields 112 total
Flushing Assembly Orenco@ 1.5" dtameter two 45" or 90" long sweep
only (8 total)
Page 7
Geo-fabrics or plastics should not be used over the STA. No heavy equipment, machinery, or materials
should be placed on the backfilled STA. Machines with tracks (not wheels) should be used during
construction of the STA for better weight distribution. Livestock should not graze on the STA. Plumbing
fixtures should be checked to ensure that no additionalwater is being discharged to OWTS. For example, a
running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA.
lf an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned
annually, or as needed. lf the OWTS consists of a pressurized pump system, we recommend the laterals be
flushed annually, or as needed.
The homeowner should pump the septic tank every two years, or as needed gauged by measurement of
solids in the tank. Garbage disposal use should be minimized, and non-biodegradable materials should not
be placed into the OWTS. Grease should not be placed in household drains. Loading from a water softener
should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS.
Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste
only.
ADDITIONAL CONSTRUCTION NOTES
lf design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of
freezing. The pump shall have an audible and visual alarm notification in the event of excessively high-
water conditions and shall be connected to a control breaker separate from the high-water alarm breaker
and from any other control system circuits. The pump system shall have a switch so the pump can be
manually operated.
Excavation equipment must not drive in the excavation of the STA due to the potential to compact soil.
Extensions should be placed on all septic tank components to allow access to them from existing grade.
Backfill over the STA must be uniform and granular with no material greater than minus 3-inch.
LIMITS:
The design is based on information submitted. lf soil conditions encountered are different from conditions
described in report, CBO lnc. should be notified. All OWTS construction must be according to the county
regulations. Requirements not specified in this report must follow applicable county regulations. The
contractor should have documented and demonstrated knowledge of the requirements and regulations of
the county in which they are working. Licensing of Systems Contractors may be required by county
regulation.
Please call with questions.
Sincerely,
CBO lnc.Reviewed By
38823 'u',i.
3-28-2022 :
L I
foo
(læ',ü* Ltstfu"t
Carla Ostberg, MPH, REHS Romeo A. Baylosis, PE
Pump Selection for a Pressurized System - Single Family Residence Project
Fadden / Lot 9, Roaring Fork Preserve
Parameters
300Discharge Assembly Size
Transport Length Before Valve
Transport Pipe Class
Transport Line S¡ze
Distributing Valve Model
Transport Length After Valve
Transport Pipe Class
Transport Pipe Size
Max Elevation Lift
Manifold Length
Manifold Pipe Class
Manifold Pipe Size
Number of Laterals per Cell
Lateral Length
Lateral Pipe Class
Lateral P¡pe Size
Orifice Size
Orif¡ce Spacing
Residual Head
Flow Meter
'Add-on' Friction Losses
Galculations
1.25
99
40
1.50
6404
7
40
1,50
5
ù
40
1.50
I
29.25
40
1.50
5t32
2
None
feet
inches
inches
feet
inches
feet
feet
inches
feet
ìnches
inches
feet
feet
inches
feet
ooll
Io
d
a!oT
.9
Êt!E
o
Ë
P
250
200
150
100
50
PumpData
5 10 15 20 25
Net Discharge (Spm)
30 35 40
Minimum Fiow Rate per Orif¡ce
Number of Orifices per Zone
Total Flow Rate per Zone
Number of Laterals per Zone
% Flow D¡fferential l svlast Orifice
Transport Velocrty Before Valve
ïransport Velocity After Valve
Frictional Head Losses
0.68
30
20.3
2
0.7
o.¿
ea
gpm
gpm
o/o
fps
fps
00
feet
feet
feet
feet
feet
feet
feet
feet
gals
gals
gals
gals
gals
gals
Loss through D¡scharge
Loss in Transport Before Valve
Loss through Valve
Loss in Transport after Valve
Loss in Manifold
Loss in Laterals
Loss through Flowmeter
Add-on' Friction Losses
Pipe Volumes
2.9
2.5
4.3
0.2
0.0
0.1
U.U
U.U
Vol of Transport Line Before Valve
Vol of Transport L¡ne After Valve
Vol of Manifold
Vol of Laterals per Zone
Total Vol Before Valve
Total VolAfter Valve
'qu¡rements
20.3
20.0
10.5
0.7
U.J
6.2
10.5
7.2
PF3005 High Head Effluent Pump
30 GPM, 1/2HP
1151230V 1Ø 6OHz,200V 3Ø 6OHz
PF3007 High Head Effluent Pump
30 GPM, 3/4HP
23OV 1Ø 60H2, 200/460V 3Ø 60Hz
PF3010 High Head Effluent Pump
30 GPM, IHP
23OV 1Ø 60H2, 200/460V 3Ø 6OHz
PF3015 High Head Effluent Pump
30 GPM, 1-1l2HP
230V 1Ø 60Hz,2OOl230l460V 3Ø 60Hz
gpm
sY$lrMs@
System Curve: -
Pump Curve: ' '
Pump Optimal Range:-
Operating Point:
Design Point:
G
o
feet
G)qPublb.net* Garfield County, Co
O WEEPING WILLOW LN
CARBONDALE
FADDEN, MATTHEW SCOTT & J ULIE
ANNE
2815 W 115TH DRIVE
DENVER CO 80234
81623
2019Total Actual
Value
Overview
Legend
f, Parcels
Roads
Parcel/Account
Numbers
Highways
=* Limited Access
- Highway
Major Road
' Local Road
Minor Road
Other Road
RamP
-- Ferry
Pedestrian Way
Owner Name
i,.:l takes c Rivers
* County Boundary
Line
$11,840 Last25ales
Date Price
7t/r9/202} $O
e/ts/2020 $o
Account
Number
Parcel
Number
Acres
Land SqFt
Tax Area
20t9MiI
Levy
R0085ó1
239336319009
15
0
011
79.7760
Physical
Address
Owner
Address
Date created:3/I7/2O22
Last Data Uploaded: 3/I7 /2O22 2:24:37 AM
Deve rone d bv¡$:) *t.gFidçt
3117122, 12:26 PM
Account
Parcel
Property
Address
legal
Description
Acres
Land SqFt
TexArea
M¡llt€vy
Subdivislon
qPublic.net - Garfield County, CO - Property Record Card: R008561
G)qPublic.net'" Garfi eld County, co
Summary
R0085ó1
23933ó319009
OWEEPING WILLOW LN, CARBONDALE, CO 81ó23
Section: 3ó Township: 7 Range:88 Subdivision: ROARING FORK
PRESERVE Lot: 9 AS PER FIRSTAMENDED PLAT RECEPTION NO.
945740 15.412 ACERS
t5.4tt
0
t1-
79.7760
ROARING FORK PRESERVE
View MaB
Owner
FADDEN, MATTHEW SCOTT & JULIE ANNE
2815 W 115TH DRIVE
DENVER CO 80234
Land
Unit Type IRRIGATED LAND-AGRICLTRL. - 4117 (AGRICULTURAL PROPERTY)
SquareFeet 0
Actual Values
Assessed Year
Land Actual
I mprovementActual
Total Actual
AssessedValues
Assessed Year
Land Assessed
I mprovement Assessed
Total Assessed
Tax History
TexYear
Taxes Billed
2020
$263.64
2079
s26s.96
202L
$11,840.00
$11,840.00
202!
$3,430.0O
$o.oo
$3,430.(x)
20LA
$363.76
2O:2O
$12,040.00
$o.oo
$12,040.00
2020
$3,490.00
$o.oo
$3,490.00
2017
$347.72
Sale Price
$o.oo
2027
$273.64
Click here to view the tax information for th¡s p
Transfers
Sale Dete
77/19/2]020
9/75/2020
9/75/2020
9/LO/2020
8/20/2020
2/26/2015
72/75/2014
70/6/2013
3/9/2006
3/A/2006
77/8/2004
5/29/2002
5/23/2002
5/20/2002
Reception Number
945740
94t985
94198?
94L994
94tO.7t
859785
e?7ote
941696
694032
494031
663586
604723
ó03998
603997
Book - Page
1780-62
7780-67
1640-292
1360-465
1357-225
7357-213
Deed Type
Plat
BARGAIN AND SALE DEED
STATEMENTOFAUTHORITY
SPECIALWARRANTY DEED
CoRRECTTON QUITCLAIM
LIS PENDENS
QUITCLAIM DEED
NOTICE OF LIS PENDENS
WARRANTY DEED
STATEMENTOFAUTHORITY
QUITCLAIM DEED
WARRANTY DEED
DECLARATION
AGREEMENT
$o
$o
$o
$780,000
$5ó5,000
$o
$o
$o
$o
$o
$o
$o
$o
$o
https://qpublic.schneidêrcorp.com/Application.aspx?ApplD='t038&LayerlD=22381&PageTypelD=4&PagelD=9447&Q=126012332&KeyValue=R008561 112
3117122, 12t26 PM qPublic.net - Garfield County, CO - Property Record Card: R008561
s/8/2002
9/L4/200I
8/20/2Wt
8/15/2001
5/3u2æt
4/20/2000
5/27/t999
r2/3O/t:998
12/3O/1e?8
4tgotL987
4t20/1987
4/6/7962
ó03999
ó03P95
586745
@e
69y 6
sç?3?1
546792
fiq!2q
138724
18\2e7
398e8?
2177r2
7357-269
7357-209
7279-57
7357--2L7
1359-I28
IL83-436-439
!L3t-757
7LO7-Ot70
7to7-01"66
0710-05ó8
0709-o947
0340-0327
$7,776,000
QUITCLAIM DEED
EASEMENT
RESOLUTION
QUIJclÁtM DFED
DECLARATION
GENERALWARRANTY DEED
AFFIDAVIT
QUITCTAIM DEED
QUITCLAIM DEED
coRRECTTON QUtTCLAtM
QUITCTAIM DEED
WARRANW DEED
$o
$o
$o
$o
$o
$o
$o
$o
$o
$o
$o
Propefi Related Public Documents
Click here to view Prop4yjg!3!9d.gCþ!¡C_DocumeDlg
Photos
No dåta eva¡lable forthefollowlng modules: Buildings, Sketches.
::;:iriili- blr gr:at;:l'iÈi:e,ì.
llserfriy"asy-!.ql¡çY
-9PPÂf-riv"ævJe!¡ss
La9!84þ_Uplqa43¿!ZZW&:24¿31-.M Y<:r:;k:r;!."j:i7't
l -:er.¡ci¡¡¡lii i:t).
l-)Fsþr',"rdçr
https://qpublic.schneidercorp.com/Application.aspx?ApplD=1038&LayerlD=22381&PageTypelD=4&PagelD=9447&Q='126012332&KeyValue=R008561 212