Please see attached. Letterfrom Kumar.
Blake Piland
RM Construction
5030 County Road 154
Glenwood Springs, CO 81601
Direct: 970-355-0351
Office: 970-300-2025
blake@buildwithrm. com
http ://www.buil dwithrm. com
Blake Piland < blake@buildwithrm.com >
Friday, January 7,2022 7:42 AM
Colleen Wifth
[External] Re: [External] basement conversion project
20220 1 07 A7 2859 455.p df
øRE-/A-2/-7Zf
From: Blake Piland <blake@buildwithrm.com>
Sent: Friday, January 7,20227:27 AM
To : Col leen Wirth <cwi rth @ga rfield-cou nty. com>
Subject: Re: IExternal] basement conversion project
Good Morning Colleen,
We've decided that we will stay wíth our original plan and not be asking to amend the application. You should
be seeing the letter requested from Kumar any day now, íf you haven't already. I had confirmation earlierthis
week that they were preparing it.
Thank you,
Blake Piland
RM Construction
5030 County Road 154
Glenwood Springs, CO 81601
Direct: 970-355-0351
Office: 970-300-2025
blake@buildwithrm. com
http ://www. buil dwithrm. com
From: Col leen Wirth <cwirth @ garfield-cou nty. com >
Sent: Wednesday, December 29,20214:03 PM
lake-Piland<blake@buildwithrm. com
Subject: RE: IExternal] basement conversion project
1
Hero Brake, 1fr, ¡ ¿pþlrva/,1dafe aúøúd q4
Yes, you will need a Colorado licensed engineers detail / cut sheet / menro expressing the on-site as-built structural
changes. You may consult an engineer of your choosing.
Before implementing design changes, look at 2015 IRC section R302.13 fire protection of floors. I understand the
desíre to expand unfinished space to make overhead duct work accessible, but you want to consider the floor system to
ensure R302.13 is met. While it's "unfinished", drywall or some other approved cover may pertain. You'll want to read
R302.13 and the exceptions.
Aside from that item, if you need to change the shape of your mechanical room you may do so provided all life safety
and building code provisions continue to be met ín the habitable portions of the basement living. From the red balloon
notations it does appear that changes will create an open walkway communicating between the family room and play
room so that the adjoining play room and bedroom bathroom areas - from use and function standpoint - still have
access to the existing stair off the family room.
FYI the CONDITIONS OF PERMIT and/or redlines from the original approved FIELD COPY still remain. Be careful to
ensure the required amount of (mechanical ventilation R303) is available to the "play room" space as no window or door
openings are provided.
Attached is a blank form for submitting AMENDED PLANS to us for addítional revíew. Complete the form includíng
your assigned permit number, contact information, check "revisions to approved plans" and provide explanation for the
change along with (2) hard cop¡es (full size, clearly legiblelof the AMENDED FLOOR PLANS.
f you have selected and consulted with an Engineer of Record - but scope of structural design changes is unknown untíl
observations are made after demolition -- we can treat the structural change as deferred submittal documents to be
presented to the building ínspector at time of framing inspection. Should that be your preference, you may supply the
AMENDED FLOOR PLAN and include a note regarding deferred structural plans. (example: "Services of Engineer XYZ
(contact information) have now been obtained, Engineer to consult during /following demolition and structural details
supplied at framing inspection")
Thanks for your careful project planning, reach out if you have more questions,
Have a safe & healthy New Year!
Best,
Colleen Wirth
Plans Examiner
Garfield County Building Division
LO8 8th Street, Suite 401-
Glenwood 5prings, CO 81601
cwi rth @ garf i el d-co u ntv. co m
office (970) 945-L377 ext. 161-o
From: Blake Píland <blake@buíldwithrm.com>
Sent: Wednesday, December 29,202L 9:06 AM
To: Sam lrmen <sirmen @garfield-county.com>
Cc: Colleen Wirth <cwirth@garfield-county.com>; Ted White <twhite@garfíeld-county.com>; Dave Argo
<dargo@ga rfiel d-cou nty. com >
Subject: IExternal] Re: IExternal] basement conversion project
2
Sam and Colleen,
As l've been waiting on the septic engineer and had time at home over Christmas, I've come up with a layout
change I would like to do. I've attached the original submitted layout and a ballooned revision area in red.
Rather than closing off the two current mechanical areas, I would prefer to expand this unfinished space,
especially considering the amount of overhead ductwork and inclusion of 2 dampers that I would have to
create accesses for. Thís does require me puttíng a doorway into a bearing wall. Can I make these changes and
will this require an engineer's direction or may I propose a plan for installing a header in this doorway?
Blake Piland
RM Construction
5030 County Road 154
Glenwood Springs, CO 81601
Direct: 970-355-0351
Office: 970-300-2A25
blake@buildwithrm. com
http : //www. buil dwithrm. som
From: Sam lrmen <sirmen@garfield-c >
Sent: Wednesday, December L5,2021- 10:51 AM
To: Blake Piland <blake@buildwithr >
Cc: Colleen Wirth <cwirth@sarfield-co >; Ted White @>; Dave Argo
<dargo@garfield-co >
Subject: RE: IExternal] basement conversíon project
Good Morning Blake,
Thankyou forthe submittalof and paymentof feesforthe OWTS alteration at LL3 Fox Run Rd. Attached isthe receipt
for this payment. I have sent the application over to Ted. Once we receive the letter from Kumar, we will contact you
regarding the issuance of the main building permít. Please let us know if there is anything else you need. Hope you have
a great day out there and be safe if you are out on the roads!
Thanks,
Sam lrmen
{íurJieltï Crr.unty
Permit Technicían
Community Development Department
sirmen(ôsarfi eld-countv.com
Direct 970-945-1377 Exl. !625
T:970-945-8212 | Fi 97A-384-3470
108 8th St, Suite 401- | Glenwood Springs, CO 81601
From: Blake Piland <blake@buildwÍthr >
Sent: Wednesday, December t5,2A2L 7:54 AM
To: Colleen W¡rth <cw¡rth@garfíeld-co >
5
Cc: Ted Whíte @>; Sam lrmen <sirmen@garfield-countv.com>; Dave Argo <dareo@sarf¡eld-
countv.com>
Subject: IExternal] Re: IExternal] basement conversion project
Good Morning Sam,
Here is the application forthe septic alteration as requested. I've also included an ILC and the septic inspection
that we had performed at purchase. Would it be possible to make a payment by credit card as before? lf not, I
ean stop in and drop physieal eopies along with a ehee k off, just let me know. lf so, please call at your
convenience. I'll have Kumarfollow with an email as requested.
Thank you,
Blake Piland
RNI Co¡rstruction
5030 County Road 154
Glenwood Springs, CO 81601
Direct: 970-355-0351
Office: 970-300-2025
bl ake@buildwithrm. com
http : /lwww. buil dwithrm. com
From : Col leen Wirth <cwirth @earf ield-cou ntv.com>
Sent: Friday, December IO,2O2L 1:48 PM
To: Blake Piland <blake@buildwithrm.com>
Cc: Ted Whíte @>; Sam lrmen <sirmen@garfield-countv.com>; Dave Argo <dargo@sarfield-
countv.com>
Subject: RE: IExternal] basement conversion project
RE: BLRE-10-21-72L9 | Blake Piland basement conversion pro¡ect
Blake,
I spoke with Ted and below is the best approach moving forward:
Fill out an OWTS Permit Application form and submit to our Community Development Department front desk
Fee due is 575.00, make check payable to GARFIELD COUNTY TREASURER (with OWTS permit in note section)
Have Kumar & Associates prepare and send email ATTN: Ted White, twhite@garfield-countv.com -
OWTS Engineerto convey they are providing OWTS design services for Blake Piland at 113 Fox Run, Rifle.
OWTS Engineer correspondence to include an explanation of circumstances and timeframe for submitting
forthcomíng design / plan drawings to Garfield County staff.
Once that is done, I will go ahead and approve your building permit for issuance.
For project planning, your issued FIELD COPY will include CONDITIONS OF PERMIT #6-7.
ól stP t lC SYSI EM RË\rlLW/ APPHüVALS: PRIOR I ü IINAL tsUlLl-]iNG INSPECT ION &
CERTIFICATE OF OCCUPANCY PRÛVIDE FINALAPPftOVAL / SIGN-OFF FROM
GARFIELD COUNTY'S PUBLIC HEALTH DEPARTMENT.
7} NO ÛCCUPANCY OF THE BASEMENT SPACE SH,ALLÛCCUR UNTII- SUCH TIME
FINAL APPROVAL FüR îHE ALTERED SEPT¡C SYSTEM AND FINAL BUiLDiNG
TNSPECTTON t5 APPROVED, I
4
Here's the link to your OWTS application form and checklist
Onsite wastewater treatment svstems - Environmental Health (garfield-countv.coml
My contact information is provided below, if you need to reach me,
Colleen Wirth
Plans Examiner
Garfield County Community Development
108 8th Street, Suite 401-
Glenwood Springs, CO 8160L
cwirth @ garf ield-cou ntv.com
offíce (970) 945-1377 ext. 1610
From: Blake Píland <blake@buildwithr >
Sent: Monday, December 6,2O2L 3:17 PM
To: Ted White @>; Colleen Wirth <cwirth@sarfield-co >
Cc: Alissa Piland <alissa.piland@sm >; Joshua Wílliams <iUlilliams@sarf¡el >
Subject: Re: IExternal] basement conversion project
HiAII,
I've been in contact with Kumar & Associates on a septic plan. Unfortunately, they aren't available to begin
work on design for another 2 months. ls it possible to move forward with the interior review and work while
we waít on a septic plan?
Blake Piland
RI\'l Constmction
5030 County Road 154
Glenwood Springs, CO 81601
Direct. 970-355-0351
Office. 970-300-2025
blake@buildwithrm. com
http : //www. buil dwithrm. com
From:TedWhite@>
Sent: Wednesday, December L,2O2I4:16 PM
To: Blake Piland <blake@buildwithr >; Colleen Wirth <cwirth@sarfield-co >
Cc: Alissa Piland <alissa.piland@sm >; Joshua Williams <jwilliams@sarf¡el >
Subject: RE: IExternal] basement conversion project
Blake,
l'm glad that you had the system inspected prior to your purchase of the property. A lot of people don't
know that they should have that done, but your experience in the industry paid dividends for you in that regard.
As far as alterations go, we require a system inspection (already completed), then a design to address the
proposed expansion that will indicate if the existing system is sized appropriately to handle the expansion, and
if not, what improvements need to be made. lf the existing STA needs to be expanded, then we would want a
soils analysis done to provide the parameters for how much of an expansion would be needed. lf only a tank is
required, we only reqúire that we be provided with the tank size and manufacturer, and where the new tank will
be located in relation to the other OWTS components. I hope this addresses the quest¡ons that you have. lf
you have additional questions or if we can be of further assistance, please contact us.
5
e üarþld (bun{¡,
i Ìriri," ii¡.,¡J¡f¡
Edward R. "Ted" White, P.E.
Environmental Health Specialist I I I
Garfield County Public Health
2014 Blake Ave. Glenwood Springs, 81601
www. O arf i e ld -cou ntv. com
twh ite@ oarfield-countv. com
970-945-6614 x 8106 (main otfice)
970-230-2442 (mobile)
Ga¡field County Public Health Department- working to promote health and prevenf drsease
From: Blake Piland <blake@buildwithrm.com>
Sent: Tuesday, November 3O, 202t 8:L0 PM
To: Ted White @>; Colleen Wirth <cwirth@earfield-countv.com>
Cc: Alissa Piland <alissa.piland@em >; Joshua Williams <iwilliams@garfield-countv.com>
Subject: Re: IExternal] basement conversíon project
I figured as much. With that said, then I do have several questions
I've got some experience installing new septic systems in new construction, but have never been part of a
project where one needed to be modified. I guess my first question would be, where do we begin? We had
Down Valley Septic and Drain inspect the system prior to purchasing the home this summer. We've reached
out to them and they have implied that their expectations would be that we could upgrade the system by
simply adding a 500 gallon dosing tank between the current tank and the cleanout located outsíde of our
home? Does this sounds practical? I've looked at the two links that you have provided and there doesn't seem
to be any differentíating between the application for modifying an existing system or installing a new system.
Are we looking at needing to get a soils engineer involved, do a perc test and/or have an engineer design a
new system for us? How much of the requirements in the application are pertinent to what we will need to
do, and could you even answer that without inspecting the current system? Speaking of, do we need to have
you send someone out to inspect our current system?
Thank you,
Blake Piland
RNI Constructiorr
5030 County Road 154
Glenwood Springs. CO 81601
Direct: 970-355-0351
Office: 970-300-2025
blake@buildwithrm. com
hup ://www. buil dwithrm. com
6
From:Tedwhite@>
Sent: Tuesday, November 3O,20214:32 PM
To: Blake Piland <blake@buildw¡thr >; ColIeen Wirth <cwirth@sarfield-countv.com>
Cc: Alissa Piland <alissa.p¡land@sm >; Joshua Williams <iwilliams@qarfíeld-countv.com>
Subject: RE: IExternal] basement conversion project
Blake,
Unfortunately, we have to go with the original project description. The two extra rooms in the þasement
could be finished as bedrooms by someone else that may purchase the house. As you sa¡d, the world can
throw us curve balls, and unfortunately, the system needs to be sized for 5 bedrooms.
'{inrþhl (uantÍ
,
Edward R. "Ted" White, P.E.
Environmental Health Specialist lll
Garfield County Public Health
2014 Blake Ave. Glenwood Springs, 81601
www. qarfield-cou nty. com
twh ite@sarfie ld-cou nty. com
970-945-6614 x 8106 (main office)
970-230-2442 (mobile)
Garfield County Public Health Department- working to promote health and prevenf drsease
From: Blake Piland <blake@buíldwithr >
Sent: Tuesday, November 30,20217:54 AM
To: Colleen Wirth <çu¿írth@earfield-cou >
Cc: Ted White @>; Alissa Píland <alissa.piland@emaíl.com>
Subject: Re: IExternal] basement conversion project
HiColleen,
I would be remiss if I don't at least ask the question. lf we were to relabel the 2 additional basement bedrooms
for different use (craft room, bonus), would we be able to finish as drawn without upsizing the septic? We are
a family of 5 and I don't have any concern about capacíty for our use. I know the world can throw curveballs,
but it is our full intention to raise our family here, my youngest is 2, and occupy this home for the next 20
years or better. I understand that records would then indicate thís home to be a 3 bedroom but that doesn't
matter to me.
Blake Piland
RN'l Constmcfion
5030 County Road 154
Glenwood Springs, CO 81601
Direct: 970-355-0351
Office: 970-300-2025
G
7
blake@buildwithrm. com
http : //www.buildwithrm. com
From : Col leen Wirth <cwirth @sa rfield-cou ntv. com>
Sent: Tuesday, November L6, 202L 2:44 PM
To: Blake Piland <blake@buildwithrm.com>
Cc: Ted Whíte <twhite@sarfield-cou ntv.com>
Subject: RE: basement conversion project
Hello Blake,
Thanks for sharing updated info RE: the property's existing septic tank and leach field
I will state this less eloquently than my colleagues in Environmental Health - but I believe it is the structure's overall
total bedroom count that impacts how sizing / capacity of an on-site wastewater treatment system gets calculated (as it
implies level of use by number of building occupants). As you are increasing from 3 existing bedrooms to 5 bedrooms
and have an existíng L,000 gallon tank - I will advise you to consult Garfield County Environment Health at earliest
convenience to discuss permit requírements to alter / upgrade the existing system. Environmental Health is reached by
calling {970) 945-6614 extension 8L50.
CC: Ted White, Environmental Health, please share correspondence as needed with fellow teammates in EH. Blake is
pursuing a basement finish to create and finish 2 additional bedrooms in a habitable basement, application review is
PENDING BIRE-10-21-72L9, parcel number 217905300010, t 13 Fox Run Rd, Rifle Colorado
Colleen Wirth
Plans Examíner
Garfield County Buildíng Division
108 8th Street, Suite 40L
Glenwood Springs, CO 81601
cwirth @qa rf iel d-cou ntv. com
office (970) 945-t377 ext. 1610
From: Blake Piland <blake@buildwithrm.com>
Sent: Monday, November 15,202L 4:02 PM
To: Col leen Wirth <cwirth @sa rfield-cou ntv. com>
Subject: IExternal] Re: basement conversíon project
Sce halnr,v'
Blake Piland
RM Construction
5030 County Road 154
Glenwood Springs, CO 81601
Direct: 970-355-0351
Office; 970-300-2025
blake@,buildwithrm. com
http ://www. buildwithrm. com
I
From: Colleen Wirth <cwirth@earfield-co >
Sent: Monday, November 1-5,20213:45 PM
To: Blake Piland <blake@buildwithr >
Subject: RE: basement conversíon project
RE: BLRE-10-2L-72L9 / Blake Piland basement conversion proiect
Hi Blake,
This afternoon I started reviewing your basement plans at 113 Fox Run Rd, Rifle, and have questions about the existing
on-site wastewater treatment system.... and the anticipated impact finish work will have on existing tank or tanks:
'J,. Please re-confirm the property is currently served by an existíng on-site wastewater treatment system, and not
a communíty or other metro service district? (your application form has check box next to OWTS but l'm not
readily able to cross reference through GarCo Land Explorer an historic OWTS- permit number). Yes, onsite
septic. We had this inspected prior to purchase this summer and then pumped, hydrojetted and made a minor
repair at the outlet where the tank had settled. I can do some research and see if we can come up with a permit
number, otherwise let me know if there is any other info I can provide. lnspection Attached
2. How old is the exísting septíc tank and leach field? I assume same age as the house. Home was built in 1981"
3. Do you know the existing septic tanks gallon capacity? L,000 Gallon
4. How may bedrooms does the home have now? 3 Bedrooms
5. Andy how many total bedrooms will the home have after the basement conversion project is completed? 5
Bedrooms
Basement Level bathroom as indícated on plans was in place prior to our purchase of the home.
Clarífication to above questions, will enable me to appropriately mark up plans (and determine if a referral call to
Environmental Health staff and Public Health team is appropriate before I release the building permít).
Thanks for working through this, your answers will be very helpful!
Colleen Wirth
Plans Examiner
Garfield County Building Division
108 8th Street, Suite 401
Glenwood Springs, CO 8L601"