HomeMy WebLinkAboutObservation of Installation 8.19.2022CBO Inc.
129 Cains Lane
Carbondale, CO 81623
970.309.5259
carla.ostberg@gmail.com
August 19, 2022 Project No. C1631
Mike Thompson
Mjthompson1980@gmail.com
Onsite Wastewater Treatment System (OWTS) Installation Observations
477 CR 112
Garfield County, Colorado
Permit Number SEPT-7045
Mike,
CBO Inc. observed the installation of the onsite wastewater treatment system (OWTS) on April 14 and
28, 2022 for the subject property. Tonka Excavation installed the system.
The OWTS design is based on 5-bedrooms. An average daily wastewater flow of 600 GPD was
used.
The existing septic tank was pumped and will be removed when construction on the cabin addition
commences.
The sewer line exiting the cabin was re-routed and ties into the sewer line existing the garage with a wye
fitting and minimum 2% grade to the septic tank.
The system installation included a 1500-gallon, two-compartment Infiltrator® poly septic tank with an
effluent filter on the outlet tee. This filter must be cleaned annually, or as needed. Risers must bring
the manhole lids to grade for access.
An irrigation ditch in a culvert bisects the property from northeast to southwest. The sewer line from the
septic tank to the distribution box crosses under the irrigation ditch culvert. The sewer line was encased
10-feet on each side of the crossing with 6-inch, Schedule 40 sewer pipe.
Effluent gravity flows to the distribution box, and then to four gravelless chamber trenches. The
distribution box was accessible from grade and flow equalizers were installed on each outlet pipe in the
distribution box to assure equal flow to each trench.
Each trench consists of 15 ‘Quick 4’ Standard Plus Infiltrator® chambers, with the exception of one
trench that has 14 chambers for a total of 59 chambers and 708 square feet of infiltrative area. There
was at least 4-feet of undisturbed soil between each trench. Inspection ports were installed at the
beginning and end of each trench. Ports may be cut to grade and placed in sprinkler boxes for access.
The OWTS was generally installed according to specifications. This observation is not a guarantee of
workmanship and/or parts and materials. CBO Inc. should be notified if changes are made to the OWTS
in the future. Any additional OWTS construction must be according to the county regulations.
LIMITS: Observations are limited to components that are visible at the time of the inspection. The installer must
have documented and demonstrated knowledge of the requirements and regulations of the county in
which they are working. The quality of the installation is dependent on the expertise of the installer, soil
type, and weather conditions.
Please call with questions.
Sincerely,
CBO Inc.
Carla Ostberg, MPH, REHS
Trenches One less chamber in trench to save tree
Distribution box Septic tank
Garfield County
Public Health
Garfield County Public Health
2014 Blake Ave.
Glenwood Springs, CO 81601
Phone: (970) 945-6614 ext. 8150
Permit Number SEPT-7045
OWTS PERMIT
KEEP AVAILABLE AT PROJECT SITE
Permit Type X New X Repair X Remodel/addition X Tank only
Issue Date 08 27 2021 Expiration Date 08/2712022
For inspections, call: 970-945-6614 ext. 8150 and call the Design Engineer, if applicable
Project Address: 477 CR 112, Carbondale, CO 81623 Parcel No.: 239323400361
Owner Name: Thompson Family Trust Owner Phone: (925) 399-2258
Designed By: CBO Septic Consulting, Inc. Designer Phone: (970) 309-5259
Number of Bedrooms: 5 Minimum Tank Capacity: 1,500-gallon Minimum Absorption: 700 ftz
Permit Conditions:
This OWTS Permit is approved on the condition of compliance with the report and design as
submitted by CBO Septic Consulting, Inc. dated July 12, 2021. Changes to the design and permit must
be approved by Garfield County Public Health and the designer prior to construction.
The new OWTS will serve an existing one -bedroom residence that will be expanded to 5-bedrooms.
An existing OWTS on the property will be abandoned and replaced with a new OWTS. The new
system will consist of a new, two -compartment 1,500-gallon septic tank set level with access to
grade and an effluent filter in the outlet tee of the tank. Effluent will gravity flow to a distribution
box set level with access to grade that will distribute effluent to 720 ftZ of STA. The new STA will
consist of four gravelless chamber trenches, each trench consisting of 15 Infiltrator Quick4 chambers
per trench (60 chambers total). Inspection ports are to be installed at each end of each trench.
Maintain all setbacks and elevations as designed.
Contact the designer and Garfield County Public Health at least 48 Fours prior to requesting final
inspection of the installed system prior to backfill.
Agreement
All installations must comply with all requirements of the Garfield County OWTS regulations
including but not limited to the conditions specified above.
In consideration of the issuance of the permit, the applicant hereby agrees to comply with all
laws and regulations related to the zoning, location, construction, and erection of the proposed
OWTS and associated structures for which this permit is granted. The applicant further agrees
that if the above said regulations are not fully complied with in the zoning, location, erection,
and construction of the above described OWTS and structure, the permit may then be revoked
by notice from the Health Department and immediately become null and void.
The issuance of a permit and specifications of terms and conditions therein will not constitute
assumption of liability, nor create presumption that the local public health agency or its
employees may be liable for the failure or malfunctioning of any system. Permit issuance will
not constitute a certification that the system, the equipment used in the system, or any
component used for system operation will ensure continuous compliance with the provision of
the OWTS Act, the regulations adopted thereunder, or any terms and conditions of a permit.
Permit Approval
Plans and specifications for the proposed OWTS have been reviewed and are considered
satisfactory. Permission is hereby given to the property owner(s) to perform the work indicated
in accordance with the Garfield County OWTS Regulation. This Permit will expire 1 year from
the date of issuance unless construction on the system has commenced. An "as -built" drawing
must be submitted and inspection of the system must be completed by GCPH before final
approval of the system will be issued.
r
08/27/2021
Issued By: Garfield County Environmen al Health Date
Department
Garfield County Public Health Department – working to promote health and prevent disease
Public Health
Michael J. and Susan Thompson
477 County Road 112
Carbondale, CO 81623
Via email: mjthompson1980@gmail.com
Subject: Final Acceptance Letter
477 County Road 112
Carbondale, CO 81623
OWTS Permit #: SEPT-7045
May 3, 2022
Michael,
On April 25, 2022, we visited the site at 477 County Road 112 near Carbondale in
Garfield County, Colorado to observe the OWTS installation pursuant to OWTS Permit # SEPT-
7045. At the time of our site visit, the contractor had installed the new sewer line, the new
cleanout adjacent to the building, a new 1,500-gallon two-compartment septic tank, the new
effluent line, the distribution box, and the four gravelless chamber trenches. The septic tank and
distribution box were installed level with access brought to grade. An effluent filter was present
in the outlet tee of the septic tank. The chamber trenches were level. Two of the trenches
consisted of 15 Quick4 chambers per trench, one consisted of 14 Quick4 chambers, and the
last trench consisted of 16 Quick4 chambers for 60 total chambers (720 ft2). The difference in
number of chambers per trench was due to the presence of a tree in one of the trench
alignments. Additionally, inspection ports were present at each end of each trench. In our
opinion, this system was installed in general conformance with Garfield County OWTS
Regulations. No further action or review from Garfield County Environmental Health is required
regarding this permit. Please provide an As-Built drawing of the system, when available, for our
files.
Thank you,
Edward R. “Ted” White, P.E.
Environmental Health Specialist III
Garfield County Public Health
2014 Blake Avenue
Glenwood Springs, CO 81601
(970) 945-6614 ext. 8106
twhite@garfield-county.com
195 W. 14th Street
Rifle, CO 81650
(970) 625-5200
2014 Blake Avenue
Glenwood Springs, CO 81601
(970) 945-6614
832‐R‐13‐002