HomeMy WebLinkAboutBuilding SpecsSTATE OF COLORADO Jan-2019
Name of Manufacturer:Plant I.D. Number:
Complete Address:
Contact Name:Contact Number:
Contact Email address:
Third Party Inspection Agency:
Model Name/No.
Sq. Footage Finished:
Sq. Footage Unfinished:
Approval Stamp
EXPIRES:
MANUFACTURER CERTIFIES that only approved equipment and materials will be used and the installations shall be made in accordance with approved plans
and applicable codes and provisions of the Colorado Division of Housing. Manufacturer agrees to in-plant inspection of units manufactured under the above plan
approval. Application shall be made for and insignia affixed to each factory built unit that is subject to Colorado statutes and which is manufactured or is to be
sold, offered for sale, or occupied in the State of Colorado.
DIV. OF HOUSING, 1313 SHERMAN STREET, RM 320, DENVER, CO. 80203 (303) 864-7836 Fax (303) 864-7857
Cover Sheet for Building Specifications & QA Manual
For more detailed information on this plan approval
please contact the Division of Housing
1313 Sherman St., Rm 320, Denver, CO 80203 | (303) 864-7810 | cdola.colorado.gov/housing
The following is based on information provided to the Division of Housing (DOH) and may
be modified based on the actual findings of the field inspection.
Site Address:_____________________________________________________________
DATE:
MANUFACTURER: ID NO.:
CONTACT: PHONE NO.:
MODEL NO.: DOH P/A NO.:
INSPECTION REQUIREMENTS:
Check on site:
“AC” Inspection
Local Inspection
Electrical connection to the building AC Breaker Panel provided by others.
REV Issued for. ..
0 Construction
ENGINEERING & CONSTRUCTION SERVICES, INC.
Structural Calculations
Wood Group USA
4057 Camelot Circle
Longmont, CO 80504
Wood Group Job No. 6655-DAD-22006
Xcel Energy 10'x14'
Control Building
Rifle, CO
ZAP Project Number: 22057-22006
·�oBt,9;.,
.VS20
', f' �
AUTHOR CHECK
ZJR
APPROVED DATE
07/11/22
Structural Calculations
22057-22006-SE-CAL-0 1
07/11/2022
Overview
Control Building
ZAP ECS Project Number 22057-22006
Scope: Perform a shuctural analysis and design to determine the structural members required for the I0'xl4'
Control Building. The shucture will be designed for two conditions : hoisted and foundation supported. When
hoisted, the building shall have no snow, wind, seismic or live loads present. The foundation supported
condition will be designed for snow, wind, seismic, floor live, and roof live loads. The design of the building
foundation and anchorage are not included in this calculation.
Data: Location - Rifle, CO
I.Roof:
a.Dead Load = Strnctural element self-weight
b.Snow Load = 47 psf
c.Live = 20 psf
2.Lateral Loads:
a.Wind = 120mph, Exposure C
b.Seismic: So s = 0.321g, Soi = 0.075g, I = 1.25, Site Class D, Design Category B
3.Floor:
a.Dead Load= Self weight
b.Live Load = 125 psf
4.AtHoist:
a.Dead Load = Self weight ofstrncture
References:
I.AISC 360-10
2.AISI Sl00-12
3.IBC 2018
4.ASCE 7-16
5.Wood Group USA Assembly Drawings
6.USGS Seismic Data
Computer Programs: RISA-3D Version 19.0.1
07/13/2022
Conclusion: All strnctural elements are adequate in strength and deflection. Refer to drawings in Attachment 1
for member sizes, orientation, and dimensions. Owner shall provide anchorage to foundation at (4) perimeter
locations of skid. Refer to maximum loads in the "Max Anchor Reactions" section for foundation and
anchorage design forces.
ZAP Engineering & Consh·uction Services, Inc.
U-Factor Calcs. 1/25 (R-Factor) = 0.040 U-Value
8/3/2022
MANUFACTURER:WOOD GROUP, USA
ID:4157
STREET ADDRESS:4057 CAMELOT CIRCLE
CITY, STATE, ZIP:LONGMONT, CO 80504
MODEL NO:.10'X 14' CONTROL BLDG.
SERIAL NO.:3741
NO. OF MODULES:1
INTERNATIONAL BUILDING CODE:2018
NATIONAL ELECTRIC CODE:2020
INTERNATIONAL MECHANICAL CODE:2018
INTERNATIONAL ENERGY CODE:2015
WIND - MPH:120
WIND EXP:C
ROOF (LIVE) PSF:20
ROOF (SNOW) PSF:43.4
FLOOR AREA - SQ. FT.:140
FLOOR (LIVE) PSI:125
GROUND SNOW LOAD - PSI:47
SEISMIC DESIGN CATEGORY:B
OCCUPANCY GROUP:S-2
CONSTRUCTION TYPE:V-B
FLOOR R-VALUE:25
WALL R-VALUE:25
ROOF R-VALUE:25
EXTERIOR FIRE RATING:N/A
BUILDING SEPARATION DISTANCE:10'
AMPS:100
VOLTS:120/240
PHASE:SINGLE
MODEL LABEL NO.
CODES
BUILDING DATA PLATE
DESIGN LOADS & CRITERIA
ELECTRIC PANEL