HomeMy WebLinkAboutSteel Plans2 | P a g e " ™Fire/Smoke Rated Assembly Details (If applicable) o Walls o Ceiling o Floors o Other assemblies required to be rated o If section 722 of the IBC is opted for use, a Colorado Register Design Professional is required to stamp details Structural Framing Plans " ™Components o Floor Assemblies o Wall Assemblies o Roof Assemblies o Ceiling Assemblies o Headers, Beams and Columns o Proposed Foundation o Braced Wall line details, and tie down equipment with locations that are not specifically addressed in approved installation manual. MEP Plan Sheets " ™Mechanical plans o Show the mechanical system. Include all units, their sizes, mounting details as required, all ductwork and duct sizes, fire dampers where required, equipment schedules. Show dimensions, exhaust, supply, return/transfer air register locations " ™Electrical plans o Show all electrical fixtures, wiring sizes and circuiting, grounding, panel schedules, single line diagrams, load calculation, fixture schedules, and dimensions. " ™Plumbing plans o Show all fixtures, piping, slopes, materials, sizes, and dimensions. o Show plumbing fixture calculations " ™Gas System Plans o Gas Isometric with distances and BTU ratings of appliances it serves o Piping material and sizes, service pressure ratings Spec Set Package "™Spec Cover Sheet "™Copy of the “AC” Inspection letter denoting the “AC” inspection items listed on the submitted plans. Information from the date to site address on the first page must be filled in by the factory, except for the CDOH P/A NO (DOH assigned). " ™Truss Details o Engineered and stamped details by a State of Colorado professional designed per TPI 1 - 2014 per IBC 2018 o Include correct loading and wind speed/exposure, etc. 3 | P a g e " ™Energy Compliance o COMCHECK (signed) "Use appropriate version 2015 or(2012, 2009 based on local adoption) "Use the Colorado city where the building will be installed (If site location is not a selection on ComCheck, list exact location on Construction Site information box) "Energy compliance software is available through the Department of Energy. http://www.energycodes.gov/ o If a ComCheck is omitted and the prescriptive method is opted for use, please clearly denote on plans a table showing the information depicted in the IECC, Section C103 and applicable information per 8 CCR 1302-14, Rule 2.7 " ™Structural Calculations- Gravity and Lateral. Only the cover page of the submitted calc set is required to be engineer stamped. The pages of the calcs are to be numbered. " ™Manufacturer’s Specifications if requested and other information deemed necessary. The Colorado Division of Housing plan review does not begin until the entire plan submission is received. Applicant must sign and date below acknowledging submittal checklist has been read and all applicable documents have been submitted for review and any changes to plans require plans to be resubmitted for review, and approved by DOH before construction. All DOH plans are subject to field inspection. Additional information not included in this general list may be requested by DOH plan reviewers to complete review. X_________________________________________________________ Date:_________________ For additional plan review requirements, questions, or concerns, please reach out to our staff at manufactured.plans@state.co.us . 8/15/2022Rick.Schlitt Digitally signed by Rick.Schlitt Date: 2022.08.15 16:06:00 -06'00' DRAWING NO. DESCRIPTION 6655-DAD-22005-1 COVER SHEET 6655-DAD-22005-2 BOM 6655-DAD-22005-3 ELEVATION VIEWS 6655-DAD-22005-4 FRAME ASSEMBLY 6655-DAD-22005-5 ROOF ASSEMBLY 6655-DAD-22005-6 DETAILS 6655-DAD-22005-7 ROOF & FASTENER DETAILS El ELECTRICAL LAYOUT PLAN E2 PP01 GENERAL PURPOSE PANEL SCHEDULE E3 ONE LINE DIAGRAM E4 BILL OF MATERIAL IFOR CONSTRUCTION July 08, 2022 REVISION • DESCRIPTION REVIEWED BY· DATE DRAWN BY· DATE REFERENCES "'" i Eru,>N k''.\ -0//( P- O]/ClY "'" "'. r,7 ,UL W-7 ru, R,;;:. l.'i/'X r?7 REV DATE 0 07/08/22 0 07/08/22 0 07/08/22 0 07/08/22 0 07/08/22 0 07/08/22 0 07/08/22 0 07/12/22 0 07/12/22 0 07/12/22 0 07/12/22 WOOD GROUP USA WOOD GROUP USA FABRICATION 4057 CAMELOT CIRCLE, LONGMONT CO 80504 [fl Z,.,uu & Z,.,q14 6o1H/J<lltf/ ,ao,tlfTY AHO CONflDfHflAl THE IUFORMATIOU CONIAHtEO Ill THI! ORAWIUG IS THE SOlE PROPRiflY Of WOOD ANY PRODUCTIOU Ill PA�T OR A5 A WHOLE \VllHOUI THE WRntEU PER'f,'JSSIOU Of WOOD IS PROHl61TEO GENERAL NOTES I. WIND LOAD: 120 MPH. EXPOSURE C 2.GROUND SNOW LOAD: 40 PSF 3.ROOF SNOW LOAD: 37 PSF. 11: 1.20 4.FLOOR LIVE LOAD: 125 PSF 5.ROOF LIVE LOAD: 20 PSF 6.ROOF INSULATION: R-25. WALL INSULATION: R-25 SKID INSULATION: N/A Conc. Floor7.INTERIOR WALL AND CEILING LINER: 14 GA GALVANNEALED SHEET METAL. PAINTED WHITE 8.EXTERIOR SHEET METAL: PBR PANEL 26 GA. DESERT SAND COLOR 9.FASTENERS: HILTI HWH 12- 14XI" SELF-TAPPING HEX HEAD 5/8" OD WASHER@ IZ' ONCENTER. APPLIES TO EXTERIOR, INTERIOR, ROOF AND CEILING PANELS10.FIRE RATING: NONE. BUILIDNG MUST BE A MINIMUM OF 120" FROM ANY OTHER STRUCTUREII.I EA. 3' X 7' DOOR. PANIC HARDWARE, DOOR CLOSER. 24"X24" WINDOW, 18"X24" LOUVER 12. 1 EA. 6' x 7' DOUBLE INSULATED DOORS WITH PANIC RATED EXIT HARDWARE AND DOOR CLOSER 13. TYPE OF CONSTRUCTION: V-B 14. OCCUPANCY CLASSIFICATION: S-2 15. SEISMIC CATEGORY: B. Ss: 0.321g, Sl: 0.075g, SITE CLASS: D, Sds: 0.331g, SDl: 0.12G, le=l.25 16. RISK CATEGORY: Ill 17. All WELDING SHALL BE IN CONFORMANCE WITH AWS DI.I. 01.3 AND PERFORMED BY CERTIFIED WELDERS, WELD ELECTRODES TO 8E USED SHALL BE E70XX18.ONLY W-SHAPES CONFORM TO A992 GR.SO. ANGLES, PLATES. CHANNELS CONFORM TOASTMA36 19. BUILDING ESTIMATED WEIGHT: 8.800 POUNDS 20. BUILDING Will BE CERTIFIED PER CDOH 8 CCR 1302-14 ADMINISTRATIVE RULES. 21. BUILDING Will BE MOUNTED& BOLTED DOWN AT LOCATION BY XCEL ENERGY ON THEIR EXISTING CONCRETE PAD. Structural Only �x�. �����. -�ff�4'. �.-� �OBt,9,. ... � � .'<;) �-o ·co . Ii *t 1�__, ,: . f . � ,, ··.. ti",,,-y �l!oNir· � All APPLICABLE CODES: 08/02/2022 I. 2018 INTERNATIONAL BUILDING CODE 2.2020 NATIONAL ELECTRIC CODE (NFPA 70)3. 2015 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) 4. 2018 INTERNATIONAL MECHANICAL CODE (IMC) FINISH NOTES: I. All SKID SURFACES TO BE COATED SHALL BE SSPC SP-3 2.ALL INTERIOR SURFACES TO BE COATED SHALL BE PRIMED WITH 3-5 OFT MILS OF AMERON AMERLOCK 2/400, WHITE COLOR 3. All EXTERIOR SURFACES TO BE COATED SHALL BE PRIMED WITH 3-5 OFT MILS OF AMERON AMERLOCK 2/400, WHITE COLOR � 4.All EXTERIOR SURFACES TO BE COATED SHALL BE TOP COATED WITH 4-6 OFT MILS OF AMERO� AMERSHIELD COATING. DESERT SAND COLOR XCEL ENERGY RIFLE CS QUESTAR FEED 12' O" X 20' O" INSTRUMENT BUILDING COVER SHEET ""'66SS-OAD-2200512536771 I 05120122 I'"· 0 1=•AS NOTEDI,_ 6655-DAD-22005-1 l'"'�lof 7 : VULT=120 MPH: Vsad=93 MPH 22. BUILDING ELECTRICAL CLASSIFICATION IS GENERAL PURPOSE. THERE IS NO HAZARDOUSMATERIALS STORED OR CONTAINED IN THIS BUILDING.23. 2 EA. - 16" 115 VOLT AC SHUTTER MOUNTED EXHAUST FANS ARE MOUNTED FOR AIR REQUIRED. REVISION DESCRIPTION XCEL ENERGY E110/10/18 REVIEWED BY/DATE DRAWN BY/DATE ELECTRICAL LAYOUT PLAN REV 0JOB# 6655-DAD-18066 PRELIMINARY FOR REVIEWJDH 10/10/18 12' X 20' AIR COMPRESSOR BUILDING FOR FABRICATION REVISION DESCRIPTION 5/20/2022 REVIEWED BY/DATE JDH 7/12/2022 DRAWN BY/DATE JOB# 6655-DAD-22005/253677 PRELIMINARY FOR REVIEWJDH 5/20/2022 RIFLE CS QUESTAR FEED WOOD GROUP USA FABRICATION 4057 CAMELOT CIRCLE LONGMONT, CO 80504 PP-01:2 INTERIOR LIGHTS PP-01:2 PP-01:4 1 ½C PP-01:2 EXTERIOR LIGHTS PP-01:2 EXHAUST FAN EF-2 PP-01:8 PP-01:4 LED PP-O1: 2 EXHAUST FAN EF-1 EXHAUST FAN EF-2 EXHAUST FAN EF-1 PP-01:6 PP-01 GENERAL PURPOSE PANEL SCHEDULE E2 REVISION DESCRIPTIONREVIEWED BY/DATE DRAWN BY/DATE PRELIMINARY FOR REVIEW WOOD GROUP USA FABRICATION 4057 CAMELOT CIRCLE LONGMONT, CO 80504 XCEL ENERGY 12' X 20' AIR COMPRESSOR BUILDING 5/20/2022JOB# 6655-DAD-22005/253677 JDH 5/20/2022 RIFLE CS QUESTAR FEED REV 0 FOR FABRICATIONJDH 7/12/2022 ONE LINE DIAGRAM E3 REVISION DESCRIPTIONREVIEWED BY/DATE DRAWN BY/DATE PRELIMINARY FOR REVIEW WOOD GROUP USA FABRICATION 4057 CAMELOT CIRCLE LONGMONT, CO 80504 XCEL ENERGY 12' X 20' AIR COMPRESSOR BUILDING 5/20/2022JOB# 6655-DAD-22005/253677 JDH 5/20/2022 RIFLE CS QUESTAR FEED REV 0 FOR FABRICATIONJDH 7/12/2022 BILL OF MATERIAL E4 REVISION DESCRIPTIONREVIEWED BY/DATE DRAWN BY/DATE PRELIMINARY FOR REVIEW WOOD GROUP USA FABRICATION 4057 CAMELOT CIRCLE LONGMONT, CO 80504 XCEL ENERGY 12' X 20' AIR COMPRESSOR BUILDING 5/20/2022JOB# 6655-DAD-22005/253677 JDH 5/20/2022 RIFLE CS QUESTAR FEED REV 0 FOR FABRICATIONJDH 7/12/2022