HomeMy WebLinkAboutCorrections and Conditions of Approval 01.16.2023Gurfield Coúlnty Community Development Department 01t16t2023 Owner: Aspen Polo Partners LLP 101 S Mill Street Suite 200 Aspen, CO 8161 1 Architect: Mark Ward 2801 20th Street Boulder, CO 80304 Contractor: Divide Creek Builders 75 North 2nd Street Carbondale, CO 81623 Re Corrections and Conditions of Approval Job Address: 16411 Hwy 82 BLCO-7952 Dear Mr. Ward, The plans have been reviewed to the currently adopted codes in Garfield County. lf an item is missed during review, it is the applicant's obligation to comply with all adopted codes in Garfield County. Please provide a response letter addressing each item listed in the "Corrections to be addressed prior to issuing a building permit" and how it is being addressed. Responses are not required for the "Conditions to be addressed during construction" but please address if clarification is needed. Please provide 2 complete sets of changed sheets, with clouded areas reflecting changes, for the resubmittal. 108 Eighth Street, Suite 401 Glenwood Springs, Colorado 81601 (970) 94s-82t2 Corrections to address priqr to issuinq a buildinq oermit: ,,lfn" posts for the new stairs are in the maneuvering clearances for the exterior door to one of the new restrooms. Please revise the drawings accordingly. (2009 ANSI A1 17.1 - 404.2.3.2) g Please show the accessible route to the new exterior restrooms. There are steps shown to the Covered Terrace. Please show the accessible route to the Terrace and to the accessible restrooms. (lBC 1104) ...8 Please provide the floor plan for the upper level for reference. (lBC 107) vir-Þlease provide a compliant roofing system over the new restrooms. Also, include roof venting details or an approved non-vented detail. The roof of the restrooms appears to be LVL's with a drip thru deck to some sort of under deck drainage system. vf Please provide insulation details for the restroom walls, roof, and slab edge insulation. (2009 IECC Table 402.1,1) r€zThe LVL joist supporting the drip thru deck are to be pressure treated. Please add the requirement to the plans. (lBC 2304.12.2.4) 1,ftn"r" appears to be an open gutter system for the upper deck that will be enclosed in the lower shed roof and inaccessible because of the soffit. Having an open gutter within construction could lead to moisture issues. lnside storm drainage piping is regulated and must conform to sanitary drainage piping requirements. (lPC 1102.2) I Please provide the soils report referenced in the structural notes, #106 0920 by HP Geotech. Conditions to be addressed durins construction: The approved plans are to be on-site for inspections. Sanitary facilities are required to be provided for workers. A list of required inspections will be attached to the plans. The State is to permit and approve the electrical work. https://wmrv.colorado.qov/pacific/dora/DPO Electrical Plumbinq Permits Underground utility locates is the responsibility of the owner or contractor. 811 is the Colorado Utility Locate Hot Line. Drainage across property lines shall not exceed that which existed prior to grading. Excess or concentrated drainage shall be contained on site or directed to an approved drainage facility. Erosion of the ground in the area of discharge shall be prevented by installation of non-erosive down drains or other devices. All backflow preventers are required to be tested and certified by a licensed backflow specialist after installation and prior to issuance of the Certificate of Occupancy. 108 Eighth Street, Suite 401 Glenwood Springs, Colorado 81601 (970)94s-8212 Electrical Code compliance will be determined based on field inspections performed by the State Electrical lnspector, (303) 869-3458. Please have the inspector sign the building card or provide written documentation of the inspections. The Elect¡cal Code requires a separate Electrical Permit for low voltage fire alarms that has an alarm panel and send a notification to the Fire District when under alarm. A Rough-ln inspection with the State Electrical lnspector is required (303) 869-3458. Please have the inspector sign the building card or provide written documentation of the inspection. The fire sprinkler and alarm are required to be inspected and approved by the Local Fire Protection District. Please provide shop drawings to the Fire District for review and schedule the inspections accordingly. Please have the Fire Marshal sign the inspection card when the rough inspection is approved and when the final inspection is approved. Geotechnical observation is required when the excavation is complete and written verification be supplied at footing inspection, 1500psf. Any membrane and through penetrations of the fire resistive construction will be required to beÎire-stopped with listed fire stopping assemblies. The contractor is to provide a cut sheet for the assemblies at the framing inspection. (lBC 713) The walls surrounding the toilets are to be non-absorbent for a height of 48" and2' past on each side of the toilet. All accessible door hardware shall have a shape that is easy to grip, including pocket and sliding doors. (ANSI A117.1 - 404.2.6) An exhaust fan is required in each new restroom. (lMC Table 403.3.1.1) The exterior wet bar counter/sink are to be 34" tall for accessibility Sincerely, John Plano Building Official CC via e-mail:Aspen Polo Partners Divide Creek Builders 108 Eighth Street, Suite 401 Glenwood Springs, Colorado 81601 (e70)94s-82r2