HomeMy WebLinkAboutOWTS Installation Observations 12.28.2022CBO Inc. 129 Cains Lane Carbondale, CO 81623 970.309.5259 carla.ostberg@gmail.com December 28, 2022 Project No. C1721 Rick Bishop Tp1rsb@gmail.com Onsite Wastewater Treatment System (OWTS) Installation Observations 161 Oak Lane Garfield County, Colorado Permit Number SEPT-03-22-7384 Rick, CBO Inc. observed the installation of the onsite wastewater treatment system (OWTS) on September 9 and October 6, 2022 for the subject property. Zamora Excavating installed the system. The OWTS design is based on 4-bedrooms. An average daily wastewater flow of 525 GPD was used. The minimum required 10-foot property line setback was verified. A new 4-inch diameter Schedule 40 sewer line was tied onto the existing sewer line exiting the residence a minimum 2% grade to the septic tank. The system installation included a 1500-gallon, two-chamber Orenco® M1500P-W septic tank with an Orenco® PF3005 pump in the second compartment of the septic tank. There is a filter in this compartment that must be cleaned annually, or as needed. This septic tank, distributed by SCG Enterprises out of Conifer, Colorado, is new to Western Colorado. SCG Enterprises delivered the septic tank and assisted with start-up of the pumping system by instructing the installer. The floats were set to dose approximately 97 gallons each pump cycle. The control panel for the pump is located within line of sight of the septic tank. A 1.5-inch diameter Schedule 40 pump line was installed from the pump to an Orenco® automatic distributing valve (ADV), model 6402. This pump line has a minimum 1% grade for proper drain back into the tank after each pump cycle. The ADV was placed at a high point in the system in an insulated riser with access from grade. Effluent is pressure dosed through 1.5-inch diameter pipes to two beds, each with 3 rows of 15 ‘Quick 4’ Standard Plus Infiltrator® chambers, for a total of 90 chambers and 1080 square feet of infiltrative area. There was at least 6-feet of undisturbed soil between each bed. Effluent is pressure dosed to 1.5-inch diameter laterals, which were hung with zip ties from the underside of the chambers. Laterals have 5/32- inch diameter orifices facing up, with the exception of the first and last holes facing down for drainage. Orenco® Orifice Shields were placed under each downward-facing orifice. The orifices were placed 4- feet on center. Each lateral ends in a 90 degree ell facing up with a ball valve for flushing. Inspection ports were placed at the beginning and end of each trench. Valves and ports were placed in valve boxes, accessible from grade, for access. The OWTS was generally installed according to specifications. This observation is not a guarantee of workmanship and/or parts and materials. CBO Inc. should be notified if changes are made to the OWTS in the future. Any additional OWTS construction must be according to the county regulations. 2-2-2023 LIMITS: Observations are limited to components that are visible at the time of the inspection. The installer must have documented and demonstrated knowledge of the requirements and regulations of the county in which they are working. The quality of the installation is dependent on the expertise of the installer, soil type, and weather conditions. Please call with questions. Sincerely, CBO Inc. Reviewed By: Carla Ostberg, MPH, REHS Romeo Baylosis, P.E. M1500P-W septic tank (one riser and lid provides access to both compartments) Chamber beds View of new septic tank looking toward STA (south) Pumping system ClickTight wiring sysetm Control Panel ADV Effluent filter rand float tree Garfield County Public Health 2014 Blake Ave. Glenwood Springs,CO 81601 Phone:970)945 6614 ext.8150 For inspections,call:970 945 6614 ext.8150 and call the Design Engineer,if applicable. Project Address:161 Oak Lane,Glenwood Springs,CO 81601 Parcel No.:218535301023 Owner Name:Richard Bishop Owner Phone:562)631 5709 Contractor:Joe Zamora Contractor Phone:970)379 7171 Number of Bedrooms 4__Minimum Tank Capacity 1,250 gallon__Minimum Absorption_ OWTS PERMIT KEEP AVAILABLE AT PROJECT SITE Permit Number SEPT 7384 Revised_ Permit Type X New X Repair X Remodel/addition X Tank only Issue Date 09/22/2022 Expiration Date 09/22/2023 Permit Conditions: This OWTS Permit is approved on the condition of compliance with the application and plans of work as submitted by CBO Septic Consulting,Inc.dated June 16,2022.Changes must be approved by Garfield County Public Health and the designer prior to construction. The new OWTS will serve an existing 4 bedroom residence.The system will consist of a new,two compartment minimum 1,500 gallon septic tank set level with access to grade and a high head pump in the second compartment of the tank.Effluent will be pressure dosed to an Automatic Distribution Valve ADV)set level with access to grade at the high point of the system that will distribute effluent to 1,080 ft2 of STA.The new STA will consist of two three row gravelless chamber beds.The pump line shall consist of 1.5 inch diameter Schedule 40 PVC.Laterals shall consist of 1.5 inch diameter Schedule 40 PVC and have 5/32 inch diameter orifices facing up,every four feet on center O.C.).The first and last orifices on the lateral shall face down,to allow drainage of the laterals.Laterals shall end in a sweeping ell facing up with a ball valve for flushing.Inspection ports shall be installed at each corner of each bed.Maintain all setbacks and elevations as designed. Contact Garfield County Public Health at least 48 hours prior to requesting final inspection of the installed system prior to backfill. Agreement All installations must comply with all requirements of the Garfield County OWTS regulations including but not limited to the conditions specified above. In consideration of the issuance of the permit,the applicant hereby agrees to comply with all laws and regulations related to the zoning,location,construction and erection of the proposed OWTS and associated structures for which this permit is granted.The applicant further agrees that if the above said regulations are not fully complied with in the zoning,location,erection and construction of the above described OWTS and structure,the permit may then be revoked by notice from the Health Department and immediately become null and void. The issuance of a permit and specifications of terms and conditions therein will not constitute assumption of liability,nor create presumption that the local public health agency or its employees may be liable for the failure or malfunctioning of any system.Permit issuance will not constitute a certification that the system,the equipment used in the system,or any component used for system operation will ensure continuous compliance with the provision of the OWTS Act,the regulations adopted thereunder,or any terms and conditions of a permit. Permit Approval Plans and specifications for the proposed OWTS have been reviewed and are considered satisfactory.Permission is hereby given to the property owner(s)to perform the work indicated in accordance with the Garfield County OWTS Regulation.This Permit will expire 1 year from the date of issuance unless construction on the system has commenced.An as built"drawing must be submitted and inspection of the system must be completed by GCPH before final approval of the system will be issued. 09/22/2021 Issued By:Garfield County Environmental Health Department Date Garfield County Public Health Department – working to promote health and prevent disease   Public Health Richard Bishop 29 Oak Lane Glenwood Springs, CO 81601 Via email: tp1rsb@gmail.com Subject: Final Acceptance Letter 4-bedroom Residence 161 Oak Lane Glenwood Springs, CO 81601 OWTS Permit #: SEPT-7384 December 14, 2022 Richard, On September 9, 22, and 30, 2022, we visited the residence at 161 Oak Lane near Glenwood Springs in Garfield County, Colorado to observe the OWTS installation pursuant to OWTS Permit # SEPT-7384. At the time of our site visits, the contractor had installed the new sewer line, the new cleanout adjacent to the building, a new 1,500-gallon two-compartment septic tank with a pump in the second chamber of the tank, the new pump line, the Automatic Distribution Valve (ADV), and the two three-row gravelless chamber beds. The septic tank and ADV were installed level with access brought to grade. The ADV was also installed at the high point of the system. The chamber beds were level, and consisted of 15 Infiltrator Quick4 chambers per row, for 90 total chambers (1,080 ft2). Additionally, inspection ports were present at each end of each trench. The distribution laterals ended in a sweeping 90-degree bend facing up with a ball valve to allow flushing of the laterals. In our opinion, this system was installed in general conformance with Garfield County OWTS Regulations. No further action or review from Garfield County Environmental Health is required regarding this permit. Please provide an As- Built drawing of the system, when available, for our files. Thank you, Edward R. “Ted” White, P.E. Environmental Health Specialist III Garfield County Public Health 2014 Blake Avenue Glenwood Springs, CO 81601 (970) 945-6614 ext. 8106 twhite@garfield-county.com 195 W. 14th Street Rifle, CO 81650 (970) 625-5200 2014 Blake Avenue Glenwood Springs, CO 81601 (970) 945-6614 R 61" 10-1/2" QADrawn By:Sheet:1 OF 1Rev:2.04/19/20221" = 2'-0"Scale:M1500P-W DESIGN AIDDisclaimer:M1500P-W.SLDDRWOrenco Systems, Inc.©Date:ITS VIABILITY FOR THE PROJECT, ARE AT THE SOLE DISCRETION OF THE SYSTEMS's DESIGNER.APPLICABLE). DESIGN DECISIONS, INCLUDING THE ACTUAL LAYOUT AND CONFIGURATION OF THE SYSTEM AND ORENCO (BASED ON THIRD-PARTY STANDARDS TESTING PROTOCOLS AND PERFORMANCE REPORTS, AS layout and configuration of a system by its designer.File Name:Reviewed By: THIS PROPOSED SYSTEM CONFIGURATION DRAWING IS PROVIDED SOLELY AS A DESIGN AID AND ILLUSTRATES ONE POSSIBLE CONFIGURATION OF A SYSTEM THAT WOULD COMPLY WITH ORENCO's DESIGN CRITERIA FOR THE REQUIREMENTS AND/OR SPECIFICATIONS THAT HAVE BEEN COMMUNICATED TO Portions or all of this Proposed System Configuration Drawing, asappropriate, may be reproduced and integrated into the site-specificDN/EBGeneral Notes:Primary Chamber: 960 Gallons at •59" liquid levelSecondary Chamber: 570 Gallons •at 59" liquid level (High Level Alarm)M1500P-W Tank End DetailScale: 1"=2'-0" 55" 71-1/2" 57" 59" M1500P-W Tank Side DetailScale: 1"=2'-0" 82-1/2" 35-1/2" 59" ChamberPump VaultScale: 1"=2'-0"Baffle Location30"AssemblyPrimary Baffle Overflow Location4"M1500P-W Tank Top DetailHanging Discharge AccessRiserSecondary InletChamber1-1/4" Sch. 80 PVC Outlet 105" 135° Orenco Systems® Inc., 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-CLK-2 Rev. 4 © 12/19 Page 1 of 4 ClickTight™ Controls Package Technical Data Sheet Applications Orenco’s ClickTight™ Controls Package is an integrated set of waste- water controls components designed to provide secure wiring con- nections. It connects a pump, up to four float switches, and a control panel in an onsite wastewater system, without the use of splice boxes, field-spliced wires, or watertight wire nuts. It also eliminates the need for conduit sealing. The Orenco ClickTight is UL-listed for the US and Canada. General Orenco’s ClickTight™ Controls Package is a complete, integrated pack- age for making fast and easy wiring connections. It greatly reduces the risk of electrical failures due to moisture, faulty splices, improperly installed waterproof wire nuts, or corrosion. The ClickTight Controls Package includes ... • ClickTight™ • ClickTight control panel • Up to four ClickTight float switches • Optional ClickTight pump adapter plug* *ClickTight-compatible PF-series effluent pumps are available. See NTD-CLK-1, ClickTight Products, for more information. Product Code Diagrams CLKP ---- Float switch cord length, ft (m): 10 = 10 (3) 20 = 20 (6) Pump cord adapter option: PA = Pump cord adapter NA = No pump cord adapter included Cable length, ft (m): 60 = 62 (19) Control panel; float switches: S11 = S1; 3P S12 = S1ETMCT; 3P S13 = S1HR; 2P S14 = S1PTRO; 2BN S15 = S1PTROETMCT; 2BN S16 = S1RO; 3PN S17 = S1ROETMCT; 3PN S18 = S1ROETMCTSA; 3PN S19 = S1ROMTSGR-NC; 3PN M11 = MVP-S1DM; 3P M12 = MVP-S1DMHT; 3P M13 = MVP-S1DMHTSA; 3P M14 = MVP-S1DMHTMTSGR-NC; 3P M15 = MVP-S1DM(DEMAND); 3P M21 = MVP-S2DM; 3P M22 = MVP-S2DMHT; 3P M23 = MVP-S2DMHTSA; 3P ClickTight™ controls package 1 ClickTight™ control panel 2 ClickTight unit 3 ClickTight float switch 2 3 3 3 1 ClickTight™ components (optional plug cord adapter not shown) Orenco Systems® Inc., 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-CLK-2 Rev. 4 © 12/19 Page 2 of 4 Technical Data Sheet ClickTight™ Unit Orenco’s ClickTightTM greatly reduces the risk of electrical failures in onsite wastewater systems by providing secure, water-resistant cable connections between a ClickTight-compatible pump, up to four ClickTight-compatible float switches, and a control panel. It eliminates the need for splice boxes, field-spliced wires, wire nuts, and conduit seals. ClickTight is UL-listed for the US and Canada for 120/240V applications. Materials of Construction Cable PVC/nylon, annealed copper Connectors Glass-filled thermoplastic, silicone Fastener Stainless steel Housing ABS O-ring Buna N Potting compound Urethane Specifications Cable 14 AWG; 3-conductor; UL TC-ER 600V (pump) 18 AWG; 2-8 conductor; UL TC-ER 600V (float) Cable length, maximum, ft (m) 62 (19) Float switch connectors 2-pole Pump connector 3-pole ClickTight™ Float Switches ClickTight™ float switches are mechanical, non-mercury switches. They are cUL-listed and CSA-certified for use in water or sewage. Materials of Construction Float switch collar ABS Float switch cord Flexible, 2-conductor (UL, CSA) SJOW; water-resistant CPE cord jacket with EPDM insulated conductors Float switch housing Impact-resistant, noncorrosive polyproylene for use in liquids up to 140˚ F (60˚ C) Float switch connector Glass-filled thermoplastic, silicone Float Switch Specifications Float State Type B Normally open Mechanical P Normally open Mechanical N Normally closed Mechanical ClickTight™ unit ClickTight™ mechanical float switch 1 Float input connector 2 Pump input connector 3 ClickTight housing 4 Stainless steel fastener 5 Mounting flange 6 Cable 1 1 1 1 2 3 6 54 1 Float switch 2 Float switch cord 3 Float switch connector 1 2 3 Orenco Systems® Inc., 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-CLK-2 Rev. 4 © 12/19 Page 3 of 4 Technical Data Sheet ClickTight™ Pump Cord Adapters Orenco’s ClickTight™pump cord adapters provide a means of retrofitting a ClickTight pump connector to an existing Orenco pump or a customer- sourced, single-phase, 120V/240V pump of up to 1 hp (0.75 kW) and rating of 13 FLA. Materials of Construction Connector Glass-filled thermoplastic, silicone Heat shrink Adhesive-filled polyolefin Splice connector Nylon, copper Specifications Connector 3-pole Cord 3-conductor, 16 AWG, SOOW, 600V Heat shrink 12-6 AWG, 600V Splice connector 16-14 AWG ClickTight™ pump cord adapter 1 Splice connector 2 Pump adapter cord 3 Heat shrink 4 Pump connector 2 3 4 1 1 1 Orenco Systems® Inc., 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-CLK-2 Rev. 4 © 12/19 Page 4 of 4 Technical Data Sheet ClickTight™ S Control Panels Orenco’s ClickTight S control panels are electromechanical panels spe- cifically engineered for controlling single pumps in conjunction with the ClickTight controls package. Materials of Construction Enclosure UV-resistant fiberglass, UL Type 4X (IP 66) Hinges and latches Stainless steel Dimensions, in. (mm) Height 11.5 (292) Width 9.3 (236) Depth 5.4 (137) Specifications Audio alarm 95 dB at 24 in. (600 mm), warble-tone sound, UL Type 4X Audio alarm 120 VAC, automatic reset, DIN rail mount silence relay Circuit breakers 120 VAC, 10 A, OFF/ON switch, single pole Motor-start contactor 16 FLA, 1 hp (0.75 kW), 60 Hz; 2.5 million cycles at FLA Panel ratings 120 VAC, 1 hp (0.75 kW), 16 A, 1-phase, 60 Hz Pump circuit breaker 20 A, OFF/ON switch, single pole (120 VAC) or double- pole (240 VAC), DIN rail mounting with thermal magnetic tripping characteristics Toggle switch Single-pole, double-throw HOA switch Visual alarm 7/8-in. (22-mm) diameter red lens, “push-to-silence,” 120 VAC LED, UL Type 4X Model-Specific Options Elapsed time meter 120 VAC, 7-digit, non-resettable. Limit of 99,999 hours; accurate to 0.01 hours Event counter 120 VAC, 6-digit, non-resettable Programmable timer Repeat cycle from 0.05 seconds to 30 hours; separate variable controls for OFF & ON time period Redundant high-on relay 120 VAC, DIN rail mount; provides a secondary pump-on during high-level conditions Redundant-off relay 120 VAC, DIN rail mount. Provides a secondary off; sounds alarm on low-level condition Surge arrestor Status light on unit; protects incoming power supply from electrical surges ClickTight™ M Control Panels Orenco’s ClickTight M control panels provide timed- or demand-dosing controls with an easy-to-use, programmable logic unit (PLU) that incor- porates many timing and logic functions, such as multiple timing inter- vals to adjust for changing flow conditions and a built-in elapsed time meter and counter. They are specifically engineered for controlling single pumps in conjunction with the ClickTight controls package. Materials of Construction Enclosure UV-resistant fiberglass, UL Type 4X (IP 66) Hinges and latches Stainless steel Dimensions, in. (mm) Height 11.5 (292) Width 9.3 (236) Depth 5.4 (137) Specifications Audio alarm 95 dB at 24 in. (600 mm), warble-tone sound, UL Type 4X Circuit breakers 120 VAC, 10 A, OFF/ON switch, single pole Dual-mode operation Programmable for timed- and demand-dosing. Motor-start contactor 16 FLA, 1 hp (0.75 kW), 60 Hz; 2.5 million cycles at FLA Panel ratings 120 VAC, 1 hp (0.75 kW), 16 A, 1-phase, 60 Hz Programmable logic unit 120 V programmable logic unit with built-in LCD screen and programming keys; provides control functions and timing for panel operation Pump circuit breaker 20 A, OFF/ON switch. Single-pole (120 VAC) or double- pole (240 VAC), DIN rail mounting with thermal magnetic tripping characteristics Toggle switch Single-pole, double-throw HOA switch Visual alarm 7/8-in. (22-mm) diameter red lens, “push-to-silence,” 120 VAC LED, UL Type 4X Model-Specific Options Heater Anti-condensation heater; self-adjusting: radiates additional wattage as temperature drops Surge arrestor Status light on unit; protects incoming power supply from electrical surges 832‐R‐13‐002