Bruce,
This letter is to address a few items from a recent framing inspection.
• The 6x12 Deck beam on Gridline B is only bearing on (2)-2x6 flat in the framing.
Structurally this work for the load. On our original redlines we had this called out as (2)-
2x6, so this item works structurally as is.
• The floor framing at the shower was changed to have a dropped shower pan. The framing
in this location had to change to accommodate this. The attached picture is how it was
framed which meets the load requirements. The end LVL is attached to the cantilevered
LVL's with HUC410 hangers. The framing works as installed in this locaiton.
i
• The roof framing at the Dining room on Grid 11 between F & K has the outlookers
cantilevered out for the 36" eave. The outlookers need a minimum of a 1:1 cantilever,
and they currently have a 4' backspan which works as installed. Following is a photo of
the existing condition.
P.O. Box 2544 • Crested Butte CO 81224 USA • ph: 970.349.5922 • E 970.349.5926
• The roof framing over the Master Bedroom was revised to work with a 5 %" eave.
Attached is a detail of the plans showing how the roof was framed. This is different than
the original plans submitted, and works as shown and as installed.
P.O. Box 2544 • Crested Butte CO 81224 USA • ph: 970.349.5922 • f: 970.349.5926
A42
FRAME RAKE W
BEARING WALL TO MATC
STRUCTURAL FASCIA
TO SUPI
ATTACH W!(4) TI
2,
GALLON F
MATCH
SUPPORT
0 4'-0 O.0
6.7
2xE
• The electricians and the plumbers have drilled numerous holes and sometimes very close
proximity. We have checked the joists in questions and all the holes we observed work
structurally as installed. Following are two photos showing the worst scenarios which are
all fine structurally.
P.O. Box 25AA • Crested Butte CO 8122A USA • ph: 970.349.5922 • f: 970.349.5926
c
P.O. Box 2544 • Crested Butte CO 81224 USA • ph: 970.349.5922 • f: 970.349.5926
P.O. Box 2544 • Crested Butte CO 81224 USA • ph: 970.349.5922 • f: 970.349.5926
To our knowledge this was the extent of the structural items that the inspector had for us. Please
let us know if you have any further questions or need anything else.