HomeMy WebLinkAboutConditions of PermitCOND ITIONS OF PE RMIT BLCO -0Ù23-8248 Cal lahan Compressor Station Replace Existing Housing of Air Compressor and Air Drying Packages 8121 CR 21 5, Parachute Parcel : 240902200148 1) ALL WORK SHALL COMPLY WITH THE 2015 INTERNATIONAL BUILDING CODE (I.B.C.)AND MANU FACTU RER'S I NSTALLATION INSTRUCTIONS. 2) ALL WORK MUST COMpLy W|TH CONDTTTONS OF THE CURRENT LAND USE PERMIT. 3) ALL WORK MUST COMPLY WITH STATE AND FEDERAL REGULATIONS. 4) LOCKS, LATCHES AND LANDTNGS SHALL COMPLY WITH 2015 lBC, SECTION 1010.1.9 - DOOR LATCH TO BE OPERABLE FROM INSIDE WITHOUT A KEY OR SPECIAL KNOWLEDGE. s) pRovtDE A LANDtNc OUTSTDE THE EXTERTOR DOOR. CAN BE 7" BELOW THE INTERIOR d) coNTRACTOR TO VER|Fy CDOH CERTTFTCATTON PRIOR TO SCHEDULING BUILDING FINAL INSPECTION 7) ELECTRTCAL PERMtTTtNG AND TNSPECTIONS BY COLORADO STATE ELECTRIC BOARD. ELECTRICAL ROUGH-IN APPROVAL IS REOUIRED AT FRAME INSPECTION. ELECTRICAL FINALAPPROVAL IS REOUIRED FOR FINAL INSPECTION & CERTIFICATE OF OCCUPANCY. B) LtcHT AND VENTTLATTON pER 2015 rBC, CHAPTER 12 AND 2015 IMC CHAPTER 3-4 9) H|GH STRENGTH BOLTTNG / FrELD WELDTNG (rF ANY PERTAINS), SHALL BE REOUIRED BY SPECIAL INSPECTOR. COPY OF SPECIAL INSPECTOR REPORT TO BE AVAILABLE FOR BUILDING FINAL. 10) GARFTELD COUNTY FINAL / COMPLETION INSPECTION lS REOUIRED. 11) PROV|DE AN EXCAVATTON OBESERVATTON REPORT FROM A GEOTECH ENGINEER AT THE FOOTING INSPECTION, 2OOO PSF TO BE VERIFIED.