HomeMy WebLinkAboutEngineer's Designl(t i'ffiiffi:nËsniiiå*"' Àn Employca Cnrncd Compony 5020 County Road 154 Glenwood Springs, CO 81601 phone: (970) 945-7988 fax: (970) 945-8454 email: kaglenwood@kumarusa.com www.kumarusa.com Office Locations: Denver (HQ), Parker, Colorado Springs, Fort Collins, Glenwood Springs, and Summit County, Colorado ONSITE WASTEWATER TREATMENT SYSTEM DESIGN PROPOSED RESIDENCE LOT 1, RIVER RIDGE TBD RIVER RIDGE DRIVE GARFTELD COUNTY, COLORADO PROJECT NO. 23-7-407.02 SEPTEMBER 8,2023 PREPARED FOR: JAMES GORNICK BUILDING SPECIALISTS ATTN: JIM GORNICK 1OO5 COOPER AVENUE GLENWOOD SPRINGS, COLORADO 81601 i eornickl 988@email.com TABLE OF CONTENTS INTRODUCTION PROPOSED CONSTRI ICTTON SITE CONDITIONS...... SUBSURFACE CONDITIONS OWTS ANALYSIS ... DESIGN RECOMMENDATIONS ........ SOIL TREATMENT A.R84............... owrs coMPoNENTS ..................... OWTS OPERATION AND MAINTENANCE OWTS HOUSEHOLD OPERATION OWTS MAINTENANCE....... OWTS CONSTRUCTION OBSERVATION LIMITATIONS........ FIGURES FIGURE 1 _ OWTS SITE PLAN FIGURE 2 - SOIL TREATMENT AREA CALCULATIONS FIGURE 3 _ SOIL TREATMENT AREA PLAN VIEW FIGURE 4 _ SOIL TREATMENT AREA CROSS SECTION FIGURE 5 - DISTRIBUTION LINE CLEANOUT DETAIL ATTACHMENTS VALLEY PRECAST I,OOO GALLON, THREE.CHAMBER SEPTIC TANK DETAIL ORENCO PF3OO5 PUMP PERFORMANCE CURVE 1 ..- I - I I -2- J aJ 4 -7 - _'7 - 7- -8- ....- I - Kumar & Associates, lnc.Project No. 23-7 -407.02 INTRODUCTION This report provides the results of an onsite wastewater treatment system (OWTS) design for a proposed residence to be located at Lot l, River Ridge, TBD River Ridge Drive, Garfield County, Colorado. The project site is shown on Figure l. The purpose of the report is to provide design details for the OWTS in accordance with the Garfield County Environmental Health Department Onsite Wastewater Treatment System Regulations and the Colorado Department of Public Health and Environmental Regulation #43. The services ware supplemental to our agreement for professional services with James Gornick Building Specialists dated August 18, 2023. PROPOSED CONSTRUCTION The proposed residence will be a one story wood-frame structure with a detached garage located on the site as shown on Figure l. The residence will have two bedrooms and the detached garage will have bathroom facilities. The OWTS will be designed for a total of three bedrooms. The soil treatment area (STA) for the OWTS will be located to the south of the residence as shown on Figure 1. Water service is provided by a public supply from River Ridge Drive. The route of the water service line is not yet designed. If proposed construction is different than that described, we should be contacted to re-evaluate our design recommendations. SITE CONDITIONS The site was vacant at the time of field exploration. The terrain has been graded relatively flat in the proposed building area. The ground surface at the proposed STA appears natural. The overall ground surface of the site is moderately sloping down to the south. Vegetation consists of grass and weeds. There are no visible surface water features in the vicinity of the site. SUBSURFACE CONDITIONS The field exploration for the OWTS was conducted on August 4,2023. Two profile pits (Profile Pits I and 2) were excavated with an excavator at the approximate locations shown on Figure I to evaluate the subsurface conditions for the planned soil treatment area for the OWTS. The pits were logged by a representative of Kumar & Associates. Logs of the proflrle pits are provided below. Kumar & Associates, lnc.Project No, 23-7 -407.02 a Log of Profile Pit I Log of Profite Pit 2 The soils encountered in profile pits consisted of about I foot of Topsoil overlying Very Gravelly Loamy Sand down to the pit depths of 8 feet. No free water was encountered in the pits nor indications of seasonal high groundwater were observed at the time of the pit excavations. Based on the subsurface conditions, the soils at the STA have been classified as Type I and R-0 per State regulations, which equates to a long-term acceptance rate (LTAR) of 0.80 gallons per square foot per day. OWTS ANALYSN Based on the profile pit evaluations and our experience in the area, the soils contain greater than 35 percent rock-sized material and a sand filter on the natural soils will be needed for adequate treatment of the wastewater effluent. An aggregate bed overlying a minimum of 3 feet thick sand filter will be used. The STA will be sized for three bedrooms (six persons) and an average daily flow of 75 gallons per person, and an LTAR of 0.80 gallons per square foot per day for the natural Very Gravelly Loamy Sand soils. We assumed a third bedroom for the bathroom facilities at the detached garage. The efÍluent will gravity flow from the residence and the detached unit to the septic tank for primary treatment and then pressure dosed to the STA for dispersal and final treatment. The STA will consist of an aggregate bed over the sand filter. There are no known potable water supply lines in the vicinity of the proposed STA. The required setback to the potable water supply line is l0 feet from the septic tank, 5 feet from sewer and effluent lines, and25 feet from the STA. We should be notified for additional recommendations if these minimum setbacks cannot be met. 0-1'TOPSOL; organic Sandy Loam, firm, slightly moist, brown. 1'-8'LOAMY SAND; very gravelly, dense, slightly moist, mixed brown. o o Bottom of pit @ 8feet. No sroundwater or redoximorphic features observed at time of pit excavation. i,i,,1 ltriìit i i,:,.: t l,_,..fi : I ., i¿ ;t¡.:i ir il r r.ìt,i ij i r ¡ ¡ : 0-l'TOPSOIL; organic Sandy Loam, firm, slightly moist, brown. l'-8'LOAMY SAND; very gravelly, dense, slightly moist, mixed brown. a a Bottom of pit @ 8feet. No sloundwater or redoximorphic features observed at time of pit excavation. i.,),,ì l,r r'r,f I j þ r¡1.1;1; 1ii: 1 q:.¡,i t+; I:frri,r-¡ijir Kumar & Associates, lnc.Project No. 23-7 -407.02 -3- DESIGN RECOMMENDATIONS The design recommendations presented below are based on the proposed construction, the site and subsurface conditions encountered and our experience in the area. A layout ofthe proposed OWTS components is provided on Figure l. If conditions encountered during construction are different than those that are described in this report, we should be contacted to re-evaluate our design recommendations. SOIL TREATMENT AREA o The STA will consist of a l-foot-thick aggregate (gravel) bed that is 47 feet long by 12 feetwide (564 square feet) constructed over a three feet thick sand filter. The aggregate area size is based on an LTAR of 0.80 gallons per square foot per day for Soil Type 1. o A pressure distribution system will be used to dose the effluent to the STA at regular intervals. o Soil treatment area calculations are shown on Figure 2. . The sand filter material should meet the requirements of the current Garfield County OWTS regulations for "secondary sand media." ASTM C33 concrete sand is suitable. A sample of the sand media should be obtained within I month prior to installation for gradation analysis with the sample provided to us for testing or the test results provided to us for approval of the material. o The base of the excavation should be scarified prior to sand filter placement. o The sand flrlter material should be placed in lifts not exceeding 10 inches thick. Each lift should be bucket compacted until settlement ceases. o Distribution lines, consisting of 1.5-inch diameter Schedule 40 piping with 3/ro-inch orifice holes drilled at 4-feet spacings, should be installed as shown on Figure 3. The fîrst hole should be 6 inches from the manifold and the last hole should be 6 inches from the looped end. There should be a total of eleven holes in each distribution line. The distribution lines should be installed level in the aggregate bed. The orifice holes should face down. o Orenco Orifice Shields, or equivalent, should be installed on the effluent distribution piping within the aggregate bed at each orifice location to limit potential masking of the holes by the gravel. . The aggregate bed will consist of a minimum of 6 inches of aggregate below the distribution lines and extend to at least 4Y' inches above the lines for a total thickness of at least I foot. The aggregate should consist of clean, graded gravel which may range in size from Yzinchto2Yz inches, see Figure 4 for gradation specifications. . The bed should be oriented lengthwise along the ground contours to minimize soil cut and cover. Kumar & Associates, Inc.Project No. 23-7 - 407.02 4 . The top ofthe aggregate bed should be at or below the existing ground surface. o Prior to placement of the cover soil, a Hanes Geocomponents Pro Silver 2 ounce/yard filter fabric, or equivalent, should be placed over the aggregate bed. Mirafi l40N or 160N filter fabric is not suitable for this use. . A minimum of 12 inches and a maximum of 36 inches of cover soil should be placed over the aggregate bed. Backfill should be graded to deflect surface water away from the STA and should be sloped at 3 horizontal to I vertical or flatter. A shallow swale to divert surface water flow away from the STA may be needed along the upslope side. o Disturbed soil should be re-vegetated as soon as possible with a native grass mix. No trees, shrubs or other plants with deep roots should be planted on or near the STA as this may damage the system piping. . Four-inch diameter inspection ports should be installed vertically into each comer of the aggregate bed. The inspection port piping should extend down to the sand filter and not be connected to the distribution piping. The portion of the pipe that lies within the gravel should be perforated. The inspection ports should extend at least 8 inches above the finished ground surface or be protected in a valve box at finished grade. . The STA must be a minimum of 25 feet from any potable water supply line. . The STA must be a minimum of 20 feet from the residence. . The STA must be a minimum of l0 feet from property lines. o The STA must be a minimum of 5 feet from the septic tank. o A plan view of the STA is presented on Figure 3 and a cross section of the STA is presented on Figure 4. o Cleanouts are required at the end of each of the three distribution lines. See Figure 5 for the cleanout detail. OWTS COMPONENTS Recommended OWTS components provided below are based on our design details and our experience with the specific component manufacturers. Equivalent components may be feasible but need to be approved by us prior to consttuction. Septic Tank o A Valley Precast 1,000 gallon, three-chamber septic tank (1,500 gallons total) should be used for primary treatment. The first two chambers of the tank will be utilized for treatment and settling, and the third chamber of the tank will contain the dosing pump. A detail of the tank is provided as an attachment. o An effluent filter should be installed in the tank outlet tee. . The tank must be a minimum of 5 feet from the residence. Kumar & Associates, lnc.Project No. 23-7 - 407.02 -5- o The tank must be a minimum of l0 feet from any potable water supply line. o The tank must be a minimum of 10 feet from any property line. o The tank must be a minimum of 5 feet from the STA. . The tank must be set level. The excavation bottom must be free of large rocks or other objects that could damage the tank during placement. A road base or gravel bedding material may be needed to prevent tank damage during placement and act as a leveling course. o The tank lids must extend to final surface grade and made to be easily located. o Install the tank with2 feet minimum cover soil for frost protection. Maximum tank soil cover is 4 feet. Sewer Pipe o The sewer lines to the septic tank should not be less than the diameter of the building drains and not less than 4 inches in diameter. o The sewer pipe should have a rating of SDR35 or stronger. Schedule 40 PVC pipe is required beneath any driveway surfaces. o The sewer pipe should be sloped between 2o/o to 4o/o to help limit disturbance of solids in the tank and potential sewage bypass of the first chamber of the tank. If a steeper slope is needed, this can be accomplished with vertical step-downs in the sewer line. o A minimum 24 inches of cover soil should be provided over the sewer pipe. Paved areas, patios or other areas without vegetative cover may be more susceptible to frost and we recommend 48 inches of soil cover over the sewer pipe in these areas, and the pipe be insulated on top and sides with 2-inch-thick blue foam insulation board. If adequate soil cover is not possible, we should be contacted for re-evaluation prior to installation. o The sewer pipe should be bedded in compacted'A-inch road base or native soils provided that the native soils contain no angular rocks or rocks larger than 2Yz-inches in diameter to help prevent settlement of the pipe. Sags in the pipe could cause standing effluent to freeze and damage the piping. . Install cleanout pipes within 5 feet of the building foundation, where the sewer pipes bend 90 degrees or more and every 100 feet of sewer pipe. o All 90-degree bends should be installed using a 90-degree long-sweep or by using two 45-degree elbows. o The sewer lines should be joined with a wye-joint. ¡ The sewer line location shown on Figure I is considered conceptual. We assume that there will be only one sewer line exiting each structure. It is the responsibility of the owner/contractors to locate all sewer line exit locations and connections to the septic tank. We should be notified if there are other sewer lines exiting the buildings. Kumar & Associates, lnc.Project No. 23-7 -407.02 -6- Effluent Transport Piping o L5-inch diameter Schedule 40 effluent transport piping should be sloped at2Yo minimum to drain to the STA from the tank. . The effluent transport pipe should be bedded in compacted34-inch road base or native soils provided that the native soils contain no angular rocks or rocks larger than 2Yz inches in diameter to help prevent settlement of the pipe. Sags could cause standing effluent to freeze and damage the piping. ¡ A minimum l8 inches of cover soil should be provided over the effluent transport pipe. Paved areas, patios or other areas without vegetative cover may be more susceptible to frost. We recommend 48 inches of soil cover over the effluent pipe and insulation with at least2 inches of rigid foam insulation in these areas. If adequate cover soil is not possible, we should re-evaluate the condition prior to installation. o The effluent pipe should be double encased with larger diameter Schedule 40 PVC pipe underneath driveway surfaces and be provided with at least 48 inches of soil cover and be insulated on top and sides with 2-inch-thick foam insulation board. . All 9O-degree bends should be installed using a 90 degree long-sweep or by using two 45-degree elbows. Effluent Pumping System o An Orenco PF3005, I l5-volt, submersible effluent pump with a 1.50-inch diameter discharge assembly, or equivalent, will be required for effluent pumping. o The maximum effluent transport distance from the pump discharge to the manifold is estimated to be 15 feet. . The elevation difference from pump discharge up to the manifold is estimated to be 3 feet. o The pump should be enclosed in an Orenco Biotube Pump Vault for effluent filtering and protection of the pump from vibration. . An equivalent pump must be capable of operatin g at 32.2 gallons per minute at 12.2 feet of total dynamic head. A pump performance curve is provided as an attachment to this report. . The floats should be set to provide a dose volume of approximately 60 gallons. To achieve the desired dose volume, the upper ("ON") and lower ("OFF") floats should be set approximately 6 inches apaft. o The flow differential between the first and last orifices is estimated to be 1.0%. . The high-water alarm float should be placed approximately 3 inches above the "ON" float in the dose tank. The high-water alarm must be wired on a separate electrical circuit from the pump. Kumar & Associates, lnc.Project No. 23-7-407.02 -7 - OWTS OPERATION AND MAINTENANCE The OWTS will require periodic inspection and maintenance to function properly. A properly designed, installed and maintained system can greatly increase its lifespan. The level of maintenance will vary depending on the complexity of the system and water use habits of the residents. We recommend that an OWTS Operation and Maintenance (O&M) Manual be developed. Depending on the complexity of the system, a contract with an OWTS maintenance provider may be prudent. Below are some basic recommendations for the OWTS O&M. OWTS HOUSEHOLD OPERATION ¡ Use of high efficiency water fixtures is recommended to decrease the hydraulic load on the OWTS system. . Fix plumbing leaks immediately as this may cause a hydraulic overload of the soil absorption system. ¡ Do not irrigate the area on top of or directly upgradient of the soil absorption field as this may cause a hydraulic overload. ¡ Do not dispose of household waste down drains as this may clog or damage OWTS components. Examples of household waste includes: dental floss, cotton swabso coffee grounds, paper towels, feminine products and many other kitchen and bath items. o Use of kitchen garbage disposals is not recommended. If a garbage disposal is utilized, kitchen wastewater should be screened thoroughly. Many kitchen solids are not decomposed in the septic tank and may cause increased tank pumping frequency. o Do not dispose of household chemicals, greases, oils, paints, hot tub water or water softener backwash in household drains. A separate drywell, if feasible, may be necessary for hot tub water or water softener backwash disposal' o Limit the use of bleach as this may harm useful bacteria in the septic tank and soil absorption system. . Liquid dishwasher and clothes washer detergent is recommended for households served by an OWTS. Clay substances used as fillers in powder detergents may result in clogging of the soils absorption system. OWTS MAINTENANCE ¡ Inspect the septic tank, dose tank, Biotube pump vault, effluent pump, and STA at least annually for problems or signs of failure. o The effluent filter for the tank should be cleaned at least annually by spray washing solids into the first chamber of the septic tank. ¡ The septic tank should be pumped and cleaned every 3 to 5 years depending on use. Longer pumping intervals may increase the amount of solids that reach the STA, which may shorten its life span. Kumar & Associates, Inc.Project No, 23-7 -407.02 -8- . Pumping of the septic tank should take place when the level of the sludge and scum layers combined take up 25 to 33Yo of the capacity of the first chamber of the tank. OWTS CONSTRUCTION OBSERVATION The Garfield County Environmental Health Department requires that the designer of the system provide a record drawing and certification of the OWTS construction (As-Built inspection). We should be provided with at least 48-hour notice prior to the installer needing the inspections. Prior to issuance of our certification letter, we require observation of all system components prior to backfill. The number of site visits required for the inspection will depend on the installer's construction schedule. LIMITATIONS We have prepared this design in accordance with generally accepted engineering principles and practices in this area at this time. We make no warranty either expressed or implied. The recommendations provided in this report are based on the site conditions, profile pit evaluations and soil texture analysis, the proposed construction and our experience in the area. Variations in the subsurface conditions may not become evident until excavation is performed. If conditions encountered during construction appear different from those described in this report, we should be notifred so that re-evaluation of the recommendations may be made. This report has been prepared for the exclusive use by our client for design purposes. We are not responsible for technical interpretations by others of our information. As the project evolves, we should provide continued consultation and field services during construction to review and monitor the implementation of our recommendations, and to veriS, that the rccommendations have been appropriately interpreted. SignifTcant design changes may require additional analysis or modifications to our design. It is our opinion that the designed location of the OWTS components does not violate any setback requirements of the current Garfield County Regulations. Below is a table of common minimum horizontal setbacks to OWTS components. Refer to the Garfield County Regulations for a complete list of required setbacks. We recommend the OWTS component locations be surveyed by a Professional Colorado Land Surveyor. Table 1- Common Minimum Horizontal Setbacks from OWTS ents Lake, Irrigation Ditcho Stream Dry Ditch or Gulch Septic TankWells \ilater Supply Line Occupied Dwelling Lined Ditch 25 5100'25',20 t0'50'STA l0'5'l0'50 10'Septic Tank 50' 5'0'l0'50 l0'Buildins Sewer 50' Kumar & Associates, lnc.Project No. 23-7 -407.02 -9- Please contact us for any necessary revisions or discussion after review of this report by Garfield County. If you have any questions, or if we may be of further assistance, please let us know. Respectfu lly Submitted, Kumar & Shane M. Mello, StaffEngineer Reviewed David A. Young, SMMlkac 6 Gz3 Kumar & Associates, lnc.Project No. 23-7 -407.02 I 5955 5957 I I I 5956 '- s95¿ PROFILE PIT 1 --T I I I I tl ut k \I eL s .à -ós \zé \\ \\ \\ PROFILE ¡ ./Ptr2 \/ V \\ \\ \r. \ LOT TBD 1, RIVER RIDGE RIVER RIDGE DRIVE o,o o ()e ,-zJo() NOUTS PROPOSED VALLEY PRECAST 1,OOO-GALLON THREE-CHAMBER SEPTIC ANK WITH DOSING PUMP IN THIRD CHAMBER. PROPOSED SOIL TREATMENT AR EA (srA) GREGATE CONSISTING OF AN BED OVER A THREE FEET THICK SAND FILTER. 12 FEET WIDE BY 47 FEET LONG. 564 SQUARE FEET TOTAL. SCALE-FEET 23-7-407.02 Kumar & Associates OWTS SITE PLAN Fig. 1 OWTS SOIL TREATMENT AREA CALCULATIONS In accordance wfrlh the Gafield County OWTS Regulatbns and the Colorado Depaftment of Public Health and Environment's Reguhtbn #43, the soil treatment area was calculated as follows: CALCULATION OF OWTS DESIGN FLOW: q = 1F)(N) WHERE: Q = DESIGN FLOW F = AVERAGE FLOW PER PERSON PER DAY B = NUMBEROF BEDROOMS N = NUMBER OF PERSONS: 2 PERSONS PER BEDROOM f= $= [\= Q= 75 GALLONS PER DAY 3 BEDROOMS 6 PERSONS 450 GALLONSPERDAY CALCULATION OF OWTS TREATMENT AREA: MINIUMUM DISTRIBUTI9N çELL AREA = Q + SOIL trAR WHERE: Q= SOIL LTAR (SOIL TYPE 1)= 450 GALLONS PER DAY 0.80 GALLONS pER SQUARE FOOT PER DAY MINIMUM SOII TREATMENTAREA =563 SQUARE FEET OWTS DESIGN TREATMENT AREA: BED LENGTH = BED WIDÏH = TOTAL SOIL TREATMENTAREA = 47 FEEI 12 FEET s64 SQUARE FEET 23-7-407.02 Kumar & Associates SOIL TREATMENT AREA CALCULATIONS Fi1. 2 1.5 INCH DIAMETER NON-PERFORATED SCH 40 PVC EFFLUENT TRANSPORT PIPE SLOPED AI 2% MINIMUM TO DRAIN TO FIELD. 1.5 INCH DIAMETER NON-PERFORATED SCH 40 PVC MANIFOLD PIPE INSTALLED LEVEL. 1.5 INCH DIAMETER PERFORATED SCH 40 PVC DISTRIBUTION LATERAL tt'lllP' 3/tø INCH DIAMETER ORIFICE HOLES SPACED AT 4 FEET INTERVALS. FACE PERFORATIONS DOWN. FIRST ORIFICE TO BE 6 INCHES FROM MANIFOLD AND LAST ORIFICE TO BE 6 INCHES FROM LOOPED END (1 1 ORIFICES PER LATERAL). INSTALL ORENCO ORIFICE SHIELDS AT EACH ORIFICE. 4 INCH DIAMETER PVC OBSERVATION PORTS INSTALLED TO THE BASE OF THE AGGREGATE. THE PORTION OF THE PIPE THAT LIES IN THE AGGREGATE SHOULD BE PERFORATED. INSTALL PORTS IN EACH CORNER OF THE AGGREGATE BED. REMOVABLE LID TO BE PLACED ON TOP OF PIPE. PIPE MUST STICK UP AT LEAST 8 INCHES ABOVE FINISHED GRADE OR BE PLACED AT GRADE IN AN ACCESSIBLE VALVE BOX. Notes: 1 FOOT THICK AGGREGATE BED PLACED ON 5 FEET THICK SAND FILTER. 1.5 INCH DIAMETER NON-PERFORATED H 40 PVC LOOPED END PIPE INSTALLED LEVEL. Aggregate specif ications Standard Sieve Sizes 2!r' (1/2" drain gravel is suìtable for this application) % Passing by Weight 100% CLEANOUT INSTALLED AT THE END OF EACH DISTRIBUTION LATERAL. SEE FIGURE 5 FOR DETAIL. 5 SCALE-FEET 1 Yì' o'5/" 2. Aggregate bed placed on 3 feet of concrete sand placed in 1O-inch lifts on scarified natural ground. 3. Secondary sand media specifications (concrete sand is suitable for this application) Effective size: 0.15-0.60 mm Uniformity coefficient; < 7.0 Percent fines passing #200 sieve: < 3.0 4. Care should be taken by the contractor to avoid compaction of the native soils in the bed area. The base and side walls of bed excavation should be scarified prior to sand filter placement. S. Fill placed over the soil treatment area should be properly benched into the hillside. 6. Changes to this design should not be made without consultation and approval by Kumar and Associates. 7. AII Piping should have a rating of Schedule 40. 8. Refer to the Garfield County Onsite Wastewater System Regulations for other applicable specifications. l/u 3' 23-7-407.02 Kumar & Associates SOIL TREATMENT AREA PLAN VIEW Fig. 3 \ / l:l NATIVE SOIL 1 FoOT MrN./s FEET MAX. COVER SOIL. UPPER 6 INCHES SHOULD BE TOPSOIL. 4 INCH DIAMETER OBSERVATION PORT INSTALLED TO THE BASE OF THE AGGREGATE. ÏHE PORTION THAT LIES IN THE AGGREGATE SHOULD BE PERFORATED. HANES GEOCOMPONENTS PRO SILVER FILTER FABRIC OR EQUIVALENT OVER AGGREGATE BED.1 FOOT THICK LAYER OF 1/z INCH SIZE AGGREGATE WITH 6 INCHES BELOW PIPING AND 4/z INCHES ABOVE. 3 FEET THICK SAND FILTER SCARIFY GROUND PRIOR TO SAND PLACEMENT. 1,/Z INCH DIAMETER SCH 40 PVC DISTRIBUTION LATERAL PIPES. Notes: 1. Distribution lateral piping should be installed level in aggregate bed on top of 3 feet of concrete sand. The base and sidewalls of the bed should be scarified prior to sand placement. 2. Care should be taken by the contractor to avoid compaction of the native soils in the bed. 3. Changes to this design should not be made without consultation and approval by Kumar & Associates. 2.5 0 SCALE-FEET 23-7 -407 .42 Kumar & Associates SOIL TREATMENT AREA CROSS SECTION Fis. 4 lnslqll 6" volve box ol grou surfoce Bockf ill volve box lo botlom lnsulole lid ¡lh 2" bluê Ground Surfoce of cop onsile with soil boord 5" sch. 40, reoded cop 1.5" Sch 40, 90' or g-sweeP lwo 45' elbows Notes NOT TO SCALE 1. All piping, fitiings and valves should be Sch. 40 PVC. 2. lnstall distribution line cleanouts at the end of each distribution line. 23-7 -407 .02 Kumar & Associates DISTRIBUTION LINE CLEANOUT DETAIL Fis. 5 IOOO Gallon Top $eam - 3GP with High Head Pumplû¡m # looor€GP.Hll (l5OO Gallon Total Volune) 32t-Top View DESIGN NO'IES¡ Design per performonce test par ASTM c1227¡ Top surfoce oreo 62.3 ft¿¡ fc O 28 do)6; concrete = 6,000 PSI M¡n. lDstoü.q$oDi-o Tonk to be set on 5' mln, sond bed or pao grovel¡ Tonk to be bockfilled uniformly on oll sides in lifts less thon 24'ond mechonlcılly compocted. Excovoted moterlol moy be used for bockflll, provlded lorge stones ore removedr Excovotion should be dowotered ond tonk f¡lled with wotor prlor to bêÌng put in servlce for lnstollotlon wilh woter toble less thon 2'below groder Mcets c16¡t4-06 for reslllênt connoctors¡ lnlet ond Outlet identified obotæ pipe¡ Delivered complete wlth intemol plpingr Control Ponel to be mounted in sight line of tonk¡ 4' Moxlmum bury depth JN6i BæI AI.IOWABLE BURY (Bosed on Woter Toble) WA1ER TABLE ALLUIYAtsLL FARTH FII I o'- o'3'- o" 1'- 0'3'- 0' 2'-o"4 -0" g'- o'c-0' DRY 4-o" *Seruice contracts available for maintenance" HdClr Punp:o l¡wettTSSand lmptorræefllt¡entqdl$bíeldo Gomplúln¡û¡llaüon(wldng,pæl,nntnüryand rû¡rt{¡p pmcedu¡u)o GomCûwananty Mlnlnrrn Rb.rH¡þmRlselrbffi Dbørpt V!hr! D¡düle R¡ü.r Section ]n6r View f*t^lrr_-lL-ID*J -] Irl Ch.r 1 1 Digging Specs lnvert Dimensions Net Copocity Net Weiqht 13' Long x I'Wide 56' below inlet lnlet Outlet I enoth width Mtn. Heioht lnlet Middle 0utlet Totol Lid Tonk Totol 56 54'or73'132'68'92"ô66 gol 132 gol 5OS gol 1501 gol 3600 lbs 11756 lbÉ 5556 lbs Phone: 719.395{70¡l Ful'.719-396€|12l Webclb: www.valleyprccastæm E¡nall: frontlesk@valleyprccastcomBuene Vlrta, Colo¡ado ffi PRTCAS[¡rnc. Pump Selection for a Pressurized System - Single Family Residence Project 23-7-407.02 / Lot l, River Ridge Parameters 300 Discharge Assembly Size Transport Length Transport Pipe Class Transport Line Size D¡stribut¡ng Valve Model Max Elevation Lift Manifold Length Man¡fold Pipe Class Man¡fold Pipe Size Number of Laterals per Cell Lateral Length Lateral Pipe Class Lateral Pipe Size Orifice Size Orifice Spacing Residual Head Flow Meter 'Add-on' Fr¡ction Losses Calculations 1.50 15 40 1.50 None 3 o 40 1.50 41 40 1.50 3/1 ô 4 5 None 0 feet inches inches feet feet 250 150 100 50 PumpData 5 10 15 20 25 Net Discharge (gpm) 30 35 40 inches feet inches inches feet feet inches feet 200oolt + ct d(!o .9 Et!Ê c¡ 6 o Minimum Flow Rate per Or¡fice 0.97 Number of Orifices per Zone 33 Total Flow RaÌe perZone 32.2 Number of Laterals per Zone 3 % Flow Differential lsvLastOr¡fice 1.0 Transport Velocity 5.1 Frictional Head Losses gpm gpm o/o fps Loss through Discharge Loss in Trensport Loss through Vâlve Loss in Manifold Loss in Laterals Loss through Flowmeler 'Add-on' Friclion Losses Pipe Volumes 3.1 0.9 0.0 0.1 0.1 0.0 0.0 feet feet feet feet feet feet feet 0 0 Vol of Transport Line Vol of Manifold Vol of Laterals per Zone Total Volume 1.6 0.6 13.0 15.2 gals gals gals gals PF3005 H¡gh Head Effluent Pump 30 GPM, 1/2HP 115123OV 1ø 6OHz,200V 3ø 60HzMinimum Pump irements Design Flow Rate Total Dynamic Head 32.2 12.2 gpm feet l I 7 System Curve:- Pump Curve:- Pump Optimal Range:- operating Point, O o Des¡gn Point: SY