September 11, 2019
Corey DePaolo
779 East 17r' Street
Rifle, Colorado 81650
(cdepaolo67(c�gmail.com)
Project No. 19-7-238
Subject: Observation of Excavation, Proposed Residence, 9616 Lazy K Road, South of
Silt, Garfield County, Colorado
Dear Corey:
As requested, a representative of Kumar & Associates observed the excavation at the subject site
on August 8, 2019 to evaluate the materials exposed for foundation support. We subsequently
performed compaction testing on structural fill placed below the footing areas. The findings of
our observation, test results and recommendations are presented in this report. The services are
supplemental to our agreement for professional services to you dated April 16, 2019.
We previously conducted a subsoil study for design of foundations at the site and presented our
findings in a report dated May 21, 2019, Project No. 19-7-238. The proposed construction is
similar to that discussed in our previous report. The building has been designed to be supported
on spread footings bearing on 3 feet of imported structural fill and sized using an allowable soil
bearing pressure of 2,000 psf, as recommended in the previous report.
At the time of our August 8 site visit, the foundation excavation had been cut in two levels from
about'/2 to 8 feet below the adjacent ground surface. The materials exposed in the bottom of the
excavation consisted of stiff, sandy to very sandy silty clay in the shallower cut areas and
medium hard, weathered claystone bedrock in the deeper cut areas to the west. Results of swell -
consolidation testing performed on samples taken from the site, shown on Figure A-1, indicate
the soils are moderately compressible under conditions of loading and wetting with a low hydro -
compression potential, and that the weathered claystone possesses a moderate swell potential
when wetted. No free water was encountered in the excavation and the soils and bedrock
materials were slightly moist.
Corey DePaolo
September 11, 2019
Page 2
A 3 feet depth of minus 1'/ inch aggregate base course (CDOT Class 5 material) was then placed
and compacted in the footing areas as structural fill below the footings. We returned to the site
on August 20 to test compaction of the in -place fill. The results of the compaction testing are
attached and indicate the fill was compacted to at least 98% standard Proctor density as
recommended. Results of laboratory standard Proctor and standard properties testing on a
sample of the base course is attached as Figures 1 and IA.
The conditions exposed in the excavation are consistent with those previously encountered on
the site and the structural fill adequately compacted, and suitable for support of spread footings
designed for the recommended allowable bearing pressure of 2,000 psf. There is some risk of
foundation movement if the soils or bedrock below the structural fill were to become wetted and
precautions should be taken to prevent wetting. Prior to the footing construction any loose and
disturbed structural fill should be recompacted as needed. Other recommendations presented in
our previous report which are applicable should also be observed.
The recommendations submitted in this letter are based on our observation of the soils exposed
within the foundation excavation and the previous subsurface exploration at the site. Variations
in the subsurface conditions below the excavation could increase the risk of foundation
movement. We should be advised of any variations encountered in the excavation conditions for
possible changes to recommendations contained in this letter.
If you have any questions or need further assistance, please call our office.
Sincerely,
Kumar &
David A. Y
DAY/ljf
attachments Figure A-1, Swell -Consolidation Test Results
Field Compaction Testing Report for August 20, 2019
Figures 1 and 1 A, Laboratory Standard Proctor Test Results
cc: Garfield County Building Dept. — Jim Wilson (jwilsonggarfield-county.com)
Kumar & Associates, Ina ,t, Project No.19-7-238
1
0
0
J
J
W
N
—1
I
z
0
—2
a
0
J
O
0 —3
z
0
U
—4
—5
1 1.0 APPLIED PRESSURE — KSF 10 100
2
9
=
v
1
3
J
J
_
3 0
Ln
0 —1
Q
_
0
0
z —2
O
n
of
i
A 1.0 APPLIED PRESSURE — KSF 10 100
m
19-7-238
Kumar & Associates
SWELL —CONSOLIDATION TEST RESULTS
Fig.A-1
m%
H>
SAMPLE OF: Sandy Silty Clay with Gravel
FROM: Bottom of NE Portion of Excavation
WC = 7.9 %, DID= 103 pcf
ADDITIONAL COMPRESSION
UNDER CONSTANT PRESSURE
DUE TO WETTING
I
i
I
I
SAMPLE OF: Weathered Claystone
FROM: Bottom of SW Portion of Excavation
WC = 8.6 %, DD = 121 pcf
EXPANSION UNDER
PRESSURE UPON
CONSTANT
WETTING
—
—
-
-
- -
- -
-
i
-
Those test Ito apply only
emplea tastedu The testing report
shall not De reproduced, except
full, without the written approval
Kumar and Associates, Inc. Swell
Consolidation feeling performed
accordance with ASTM D-4546.
to the
In
of
in
-
-
-
1(+AKumar ni AssociaieInc.®
Geotechnical and Materials Engineers
and Environmental Scientists
5020 County Road 154, Glenwood Springs, CO 81601
Phone: (970) 945-7988, Fax: (970) 945-8454
Email: kaglenwood(a)kumarusa.com
Earthwork Compaction Testing Report
Client: Corey DePaolo Project No.: 19-7-238 Day:
779 East 17th Street Date:
Rifle, Colorado 81650 Page
Tuesday
08-20-19
1 of 1
Project: Proposed Residence, 961 6 Lazy K Road, South of Silt, Garfield County, Colorado
Weather: Clear, calm, dry Temperature: 880 at 12:30 pm
Earthwork Contractor: I
Equipment Used: Mini Track Floe, Compactor
Description of Earthwork We performed compaction testing on in -place structural fill below footing areas
Tested: at footing grade.
Sample(s) Obtained: We obtained a sample of 1'/2" aggregate base course for laboratory Proctor
analysis, see Figures 1 and 1A for lab test results.
Verbal Communication: Corev DePaolo was informed of our field test results.
Placement and Compaction Procedure: Not observed by Kumar Associates
Lift Thickness: Max. Rock Size: 1'/2" Moisture
Conditioning:
Compactor(s) Used: Walk -Behind, Jumping Jack Number of Passes:
Nuclear Gauge Moisture/Densit Test Results
Test
Location
Depth or
Field Dry
Field
Field
Min.
Proctor
No.
Elev.
DensityMoisture
Content
Comp.Comp.
Req.
Lab No.
Below Footing Structural Fill
(pcf)
%
°
(/0)
1
Southwest corner
Footing
Grade
136.7
3.2
98
98
341-19
2
35' S of northwest corner
Footing
Grade
136.0
3.2
98
98
341-19
3
50' E of northwest corner
Footing
Grade
136.4
3.1
98
98
341-19
Proctor Samnle Reference:
Lab No.
Method
Description
Max. Dry
Dens. cf
Opt.
Moist. %
341-19
ASTM D 698
1%" Aggregate Base Course
139.4
4.2
nlJ 1C 11 11-N I J V r11VIVIVJ NO M K -1VLI Vr VVK VDJ A I IVIVJVr TILL rL "mmIV I, VVC KHVG KGLIGU VIV IML VUNI MAU I UK I U I.VN I INUt NYYLT INU IKt KtLUMMtNUtU
COMPACTIVE EFFORT AND MOISTURE TO FILL DURING THE TIMES WHEN OUR OBSERVER IS NOT OBSERVING OPERATIONS.
THE NUCLEAR DENSOMETER METHOD OF TESTING WAS USED IN SUBSTANTIAL ACCORDANCE WITH ASTM D 6938.
Distribution:
Corey DePaolo (cdepaolo67(&gmail.com)
/mj r
Justin Orgill David A. Young, P.E.
Field Technician Reviewed By
Laboratory Proctor Compaction Test Report
147
142
0
137
U
a
C
132
ZAV for
Sp.G. _
2.50
127
122
2 3 4 5 6 7 8
Water content, %
—� - Rock Corrected —o-- - Uncorrected
Test specification: ASTM D 698-12 Method C Standard
ASTM D4718-15 Oversize Corr. Applied to Each Test Point
Elev/
Depth
Classification
Nat.
Moist.
Sp.G.
LL
PI
% >
3/4 in.
% <
No.200
USCS
AASHTO
GP -GM
A-1-a
NV
NP
25
7.5
ROCK CORRECTED TEST RESULTS
UNCORRECTED
MATERIAL DESCRIPTION
Maximum dry density = 139.4 pcf
Optimum moisture = 4.2 %
134.6 pcf
5.2 %
1.5" Aggregate Base Course
Project No. 19-7-238 Client: Corey DePaolo
Project: Six Lazy K Road, South of Silt, Garfield County, Colorado
o Loc.: Northeast Corner of Project - Flag Sand & Gravel Sample No.: 341-19
Remarks:
See Figure I for classification results.
Figure 1
Kumar & Associates, Inc.
Glenwood Springs, Colorado
Tested By: KO Checked By:
MINE
I
111
�
GRAIN SIZE -
% +3„ % Gravel % Sand
Coarse Fine Coarse Medium
0 25 32 9 12
SIEVE
SIZE
PERCENT
FINER
SPEC.'
PERCENT
PASS?
(X=NO)
2
100
100
1.5
100
90 - 100
1
91
3/4"
75
50 - 90
3/8"
55
#4
43
30 - 50
#8
35
#16
31
#30
27
#50
16
#100
10
#200
7.5
3.0 - 12
% Fines
Fine silt C
14 8
Soil Description
1.5" Aggregate Base Course
Atterbera Limits
PL= NP LL= NV PI= NP
Coefficients
D90= 24.9474 D85= 22.8025 D60= 11.3272
D50= 7.1279 D30= 0.9964 D15= 0.2673
D10= 0.1500 Cu= 75.51 Cc= 0.58
Classification
USCS= GP -GM AASHTO= A-1-a
Remarks
See Figure 1 for standard Proctor compaction results.
CDOT Class 4 Aggregate Base Course (1.5")
Location: Northeast Corner of Project - Flag Sand & Gravel
Sample Number: 341-19 Date: 8/20/2019
Kumar & Associates, Inc. Client: CoreyDePaolo
Project: Six Lazy K Road, South of Silt, Garfield County, Colorado
Glenwood Springs, Colorado ;I Project No: 19-7-238 Fiaure 1A
Tested By: KO Checked By: DAY