HomeMy WebLinkAboutSubsoils Report for Foundation DesignHuddle ston-Berry Engingrring rt 'l'e$riilg, L,-C 2789 fuverside Parkway Grand Junction, Colorado 81501 Phone: 970-255-8005 Info @huddlestonberry. com Iuly I8,2023 Project#02692-0001 The Ace of Trades General Contractots,LLC 3020 N 14th Street Grand Junction, Colorado 81501 Attention: Mr. Will Simpson Subject Geotechnical Investigation 244Limberyine Circle Parachute, Colorado Dear Mr. Simpson, This letter presents the results of a geotechnical investigation conducted by Huddleston-Berry Engineering & Testing, LLC (HBET) for 244 Limberpine Circle in Parachute, Colorado. The site location is shown on Figure 1 - Site Location Map. The proposed construction is anticipated to consist of a single-family residence. The scope of our investigation included evaluating the subsurface conclitions at the site to aid in de'zeloping foundation recornmendations for the proposed construction. Site Conditions At the time of the investigation, the site was open with a general slight slope down to the north. Vegetation consisted of grasses and weeds. The site was bordered to the north by a residential properby, to the west by open land, to the south by a vacant lot, and to the east by Limberpine Circle. SgbgUrq&gLlg_v+S_tiegt!qI The subsurface investigation included two test pits at the site as shown on Figure 2 - Site Plan. The test pits were excavated to a depth of 8.0 feet below the existing ground surface. Typed test pit logs are included in Appendix A. As indieated on the logs, the subsnrface conditions at thc site weie consistcnt. The test pits encountered 0.5 feet of topsoil above brown to tan, moist, medium stiff to stiff sandy lean clay with gravel, cobble, and boulder soils to the bottoms of the excavations. Groundwater was not encountered in the subsurface at the time of the investigation. LabqratasJqstlae Laboratory testing was conducted on samples of the native soils collected from the test pits. The testing included grain-size analysis, Atterberg limits determination, natural moisture content determination, and maximum dry density and optimum moisture content (Proctor) determination. The laboratory testing results are included in Appendix B. 244 Limberpine Circle il02692-0001 07/18t23 The laboratory testing results indicate that the native clay soils are slightly plastic. In general, bascd on the Atterberg limits and our experience with similar soils in the vicinity of the subject site, the native cla5, s611t rnay hayc a sliglit potcptial fcr collapsc. Foundation Recommendations Based upon the results of the subsurface investigation and nature of the proposed construction, shallow foundations are generally recommended. Spread footings and monolithic (turndown) structural slab foundations are both appropriate alternatives. However, in order to provide a uniform bearing stratum and reduce the risk of excessive differential movements, it is recommended that the foundations be constructed above a minimum of 24-inches of struotural fill. The native clay soils, exclusive of topsoil, are suitable fol reuse as structural fill; provided particles in excess of 3-inches in diameter are removed. Imported structural fiIl should consist of a granular, non-expansive, ugfugJrylnllgmaterial approved by HBET. For spread footing foundations, the footing areas may be trenched. Howevero for monolithic slab fourrdations, the sti'ucfural fill should extend acioss ilre eiltire building pad area to a depth of 24- inches below the turndown edges. Structural fill should extend laterally beyond the edges of the foundations a distance equal to the thickness of structural fill for both foundation types. Prior to placement of structural fill, it is recommended that the bottom of the foundation excavation be scarified to a depth cf 6 to I inchcs, rncisturc condiiioned, and compactcd to a minimum of 95o/o of the standard Proctor maximum dry density, within +2%o of the optimum moisture content as determined in accordance with ASTM D698. Structural fill should be moisture conditioned, placed in maximum 8-inch loose lifts, and compacted to a minimum of 95o/o of the standard Proctor maximum dry density for fine grained soils and 90% of the modified Proctor ma;ririium dry ilensity for coarse grained soils, witltin t2Yo of the optimutn rnoisture content as determined in accordance with ASTM D698 and D1557, respectively. Structural fill should be extended to within O.l-feet of the bottom of the foundation. No more than 0.1-feet of gravel should be placed below the footings or turndown edge as a leveling course. For structural fill consisting of the native soils or imported granular materials, and foundation building pad preparation as recofirmended, a maximum allowable bearing capacity of 1,500 psf may be used. In addition, a modulus of subgrade reaction of 150 pci may be used for structural fiIl corisisting of tlie native soils and a mochrlus of 200 pei nay be used for suitable iniported structural fill. Foundations subject to frost should be at least 36 inches below the finished grade. rrr^a--- ^^l--l^1^ ^--lf^r^^ - t^ tL^ -^:1^:- tI/^^+^- r.\^l^-^l^ 'T'L^-^f,^-^ ^+ ^ *:-:*,,*watgl sutuuts sullaltis al(i uullllllull LU ]llti suils ltl vvvstEril \/ult raluu. lrlglErurE,4L 4llllllllllulll, Type I-II sulfate resistant cement is recommended for construction at this site. I{uddlcsion-Berry lirll{rr0itr Id{lrt. I I (: 2212008 ALL PROJECTS\02692 - The Ace ofTrades General Contractors, LLC\02692-0001 - 244 Limberpine CircleuOo - Geo\02692-0001 LR071823.doc 244Limberpine Circle #02692-0001 07/18/23 Any stemwalls or retaining walls should be designed to resist lateral earth pressures. For backfill consisting of the native soils or imported granular, non-free draining, non-expansive matcrial, we recommend that the walls be designed for an equivalent active fluid unit weight of 45 pcf in areas where no surcharge loads are present. An at-rest equivalent fluid unit weight of 65 pcf is recommended for braced walls. Lateral earth pressures should be increased as necessary to reflect &ny sut*h*t*e loading behind thc rn'alls. Non-Structural Floor Slab and Exterior Flatwork Recommendations In order to limit the potential for excessive differential movements of slabs-on-grade it is recommended that non-structural floating floor slabs be constructed above a minimum of 18- inches of structural fill with subgrade preparation and filI placernent in accordance with the Foundation Recommendations section of this report. It is recommended that exterior flatwork be constructed above a minimum of l2-inches of structural fill. Drelrrege"_&eep_reesg-r$ssg Grgdittg_and_drewrge are criticsl to the lon . Grading around the structure should be designed to carry precipitation and runoff away from the structure. It is recommended that the finished ground surface drop at least twelve inches within the first ten feet away from the structure. It is also recommended that landscaping within five feet of the stir-rctrue iircllrle priir:arily dcsert plants ..vith low rveter rcquiremcnts. In addition, it is recommended that automatic irrigation, including drip lines, within ten feet of foundations be minimized. HBET recommends that surface downspout extensions be used which discharge a minimum of 15 feet from thc structxrc or beyonel thc backfill zone, u'hichever is greater. $6v,rsi'gs, if subsurface downspout drains are utilized, they should be carefully constructed of solid-wall PVC and should daylight a minimum of 15 feet from the structure. In addition, an impermeable membrane is recommended below subsurface downspout drains. Dry wells should not be used. _Ggngal ryqtes The recommendations included above are based upon the results of the subsurface investigation and on our local experience. These conclusions and recommendations are valid only for the proposed construction. As discussed prcviously, tlte subsurfacc conditic*s encou*tcrcd in thc test pits rvere consistent. However, the precise nature and extent of subsurface variability may not become evident until construction. As a result, it is recommended that HBET provide construction materials testing and engineering oversight during the entire construction process. In addition, the homeowner and any subcontractors working on the project should be provided a copy of this report and informed cf tlie issiit:s asscciaicd.with tlie pioseiice of iiiaisfi-ue si:iisiiive subgi'ar1e in;rterials at this site. I{uddlc.rton-Bcrn' lirtirfl lit* l.ldilt, I lC JZ:V008 ALL PROJECTS\02692 - The Ac€ ofTmde$ General ContmctoN. LLC\026924001 - 244 LimbeFine Circlcu00 - Grc\02692-0001 LR07l 823.doc 244 Limberpitic Circle #02692-0001 07/18123 It is important to note that the recommendations herein are intended to reduce the risk of sttuctural m.ovement und"/or damage, to vawing degrees, associated with volume change of the g1@:q__ i{S:.-!!tztlst,_l:L9-#_Z Se;Za_at_pi:gditl_,*;$e:ie!at clasases in s#!}s#rfaffi ?ilsisture canditions and/or the nrecise neagnitade or extent of volume chanse. Where sienificant increuses in subsurface moisture occar due to ooor grad.ing. imDroper stormwater ma,nqgentent,_ or the resalt of actions of the propertv owner, several inches of movement are possible. fn adsliti*ft, qxsfer#€:e:s=tq.e?rjii;!-h; r{it* tk':. rq*E{:}ri:q;t:!€!!*i:F,iri tlz€s rr**:i relcases tr'Ec:{:!!tst*#: Berw Ensineerins & Testins. LLC of $Fev liabilttv rgitls resard to the struetare oerfornaanee. We are pleased to be of service to your project. Please contact us if you have any questions or comments regarding the contents of this report. I{espectfi.rlly Submitted : Huddleston-Berry Engineering and Testing, LLC Michael A. Berry, P.E. Vice President of Engineering @ l{uddlr,ston-Bcrrl litgirc,Ir4I t/ilkre, I I (l 4Z:V008 ALL PROJECTS\02692 - The Acc ofTrades General Contractors, LLC\026924001 - 244 Limbsrpine Circle\2O0 - Geo\02692-0001 LR071823.doc FIGURES R49049-4, 24,07,48478028' RISINGiTIDESiENTERPRISESiUEC . ROW' e{ 3t?{e '.{.ij;<fr I Location Map ot D ate cr eated: 6 / 23 /2O23 Last Data Uploaded: 6/23/2O23 2:06:55 AM Dever o oed bvqf, *J 9shg}"if, pl ffiqPublic,net '' Garfield County, Co ! 6.:. lvtu'fi E-qI 0,e/ P.a /1 tue ,:*:RAOOOZ€ ,rg ^no73l t'*rr* ':f-i" TP-I .{r. rn;z ^.r\95L'lo- BATTLEMENT.M D ate cr eated: 6 / 23 / 2023 Last Data Uploaded: 6/23/2O23 2:06:55 AM i. .: . . l-r1; q:i.i.,,r, t FIGURE 2 Plan D eve r o oed bv{;t) F..5'gFiH Fl APPENDIX A Typed Test Pit Logs GEOTECH BH 244 LIMBERPINE LAB.GDT 7h7t23 !no lrto zc =Enr7 otr mz l --rIJ lo oo o -.{do (D6 oo5 (D $.oo ;'sop -t-o \O A N,J FI oot 6x Stt fl65 d O =:+ "i t'uo o.w560 o ;"*do*F -Sctr;E F'ox oo R" Flo ga FFo ! 7to(- mo ooI 6z !n P mo-{z =m N5I J5o =' D ? J D {m CN{ ! {zc =E mv {!t ! o m o"Tt zo m an ooomo @ {mo mxo t 6z =m-{Io(, -l 0)oT u, o,o-=oo mx() 6zooz-{a o{ov o{ m an{ v mo O) No) N(/) =oq. 0) =ao I moxmo @ @ oo3!rm mo OJ n=o) N(r) 'l'l -{ fiH>m<x>o dtt9 F I I I I I o7o>,rO #f 9S XE iH 6z I ? oAoczo m m Ioz m @-{ 3{ CA Nm ob DEPTH (ft) GMPHIC LOG {mn t- o m U)on-It _-.1o2 SAMPLE ryPE NUMBER RECOVERY % (ROD) BLOW COUNTS (N VALUE) POCKET PEN (tsf) DRY UNITWT (pcf) MOISTURE coNTENT (%) -l- -'{ =m =n-l(D cDmno FINES CONTENT (Y,) LIQUID LIMIT PLASTIC LIMIT PLASTICITY INDEX rs-..r_. rr.. l,r l,-.. .r.: . rt. . rs-- {\. lz-. J\ .,t/l (t q) o qt €. o o O)f.o Ch IoTaIt- o @* r- 01(t o 0to @. oo. oade5d.J(< 3s--o Jro>6',<-_€ oJgo SilJ<o9-*-a 6goo +6- lo 0)fo. @o do 6 ot- (3 -o@ ! N)o N)o @ O)(o TDo o 3 o oo p. o ob oo Huddleston-Berry Engineering & Testing, LLC 2789 Riverside Parkway Grand Junction, CO 81501 s70-255-8005 CLIENT The Ace of Trades Genefal Contractors, LLC PROJECT MME TEST PIT NUMBER TP.z PAGE 1 OF 1 244 Limberoine Circle PROJECT LOCATIONPROJECT NUMBER GROUND WATER LEVELS: ATTIME OF EXCAVATION AT END OF EXCAVATION AFTER EXCAVATION --- TEST PIT SIZECOMPLETED 6126123 CHECKEDBY MAB 6t26t23 Drv Drv EXCAVATION METHOD Trackh/Backhoe EXCAVATION CONTRACTOR Wiseland DATE STARTED GROUND ELEVATION NOTES LOGGEDBY TEC ATTERBERG LIMITS _orf= lJ otrt 3=(L t0t 42 fL FzulFzOGo 3,)q ulz IL LIJ o->x.FUJ 5g&=>z U) s ty.-uJq es H au =Fl;asoz z llJ TLrCup oo{L IF TLulo oo o EE (, MATERIAL DESCRIPTION .'3.'.S t j-r $!J ?.E Sandy Clay with Organics (TOPSOIL) Sandy Lean CLAY with Gravels, Cobbles, and Boulders (cl), brown to tan, moist, medium stiff to stiff F =F^ 205s to 3tll o\tr---lz 'rolrJ Oz>oo Bottom of test pit at 8.0 feet. !! F F Foq 6 5 al Fzo I m IouFou(, APPENDIX B Laboratory Testing Results N l! N F6o di J al F4o I ui Jo 5uzdEuo & oo N @No uN @ o Engineering & Testing, LLC GRAIN SIZE DISTRIBUTION Riverside Junction, CO 81501 970-255-8005 CLIENT TheAce ofTrades General Contractors, LLC PRo.JECT }{AME 244 Limberpine Circle PROJECT NUMBER 02692-0001 PROJECT LOCATION Parachute. CO U.S. SIEVE OPENING IN INCHES I U.S. SIEVE NUMBERS I HYDROMETER 1 FI(, IJJ =dl E IJJztr Fzulot uJ .L 100 95 90 B5 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 100 10 1 GRAIN SIZE IN MILLIMETERS 0.1 0.01 0.001 SILT OR CLAY I I q !. t GRAVEL SANDCOBBLES coarse fine coarse medium fine Specimen ldentification Classification LL PL PI Cc Cu a TP-1, GB-l 6t26 SANDY LEAN CLAY(CL)28 8 Specimen ldentification D100 D60 D30 D10 %Gravel %Sand %silt o/oClay o TP-1, GB-l 6t26 9.5 0.2 30.7 69.1 Huddleston-Berry Engineering & Testing, LLC ATTERBERG LIMITS' RESULTS Riverside Parkway Junction, CO 81501 970-255-8005 CLIENT The Ace of Trades General Contractors, LLC PROJECT NAME 244 Limberoine Circle PRo.'ECT NUMBER 02692-0001 PROJECT LOCATION Parachute, CO @ P L A S T I c I T I N D E X 50 40 20 10 CL-ML @ 0 40 LIQUID LIMIT Specimen ldentification LL PL PI #200 Classification o TP.1, GB.1 6126 28 20 8 69 SANDY LEAN CLAY(CL) N N Foq 6Ial N eo No@No ab = N F N F6 diIo:f Fz o uiJ (_)t U =cduE l N oo No@No zIF I oo Huddleston-Berry Engineering & Testing, LLC 2789 Riverside Parkway GnndJunction, CO 81501 970-255-8005 CLIENT TheASC of]@de6 Genoral Contractors, L!C_ PROJECT NUMBER 02692-0001 MOISTU RE.DEN SITY RE LATIONSH I P PROJECT NAME _244 Lrpbelplne_Qi1clg _ PROJECT LOCATION Parachute, CO rUl \ \ \ \ \ \ \ \ \ \ \ /\ 7 /\ \\ Sample Date: Sample No.: Source of Material: Description of Material 6126t2023 23-0394 145 TP-1 GB.1 SANDY LEAN CLAY(CL) Test Method (manual):ASTM D698A 140 135 TEST RESULTS Maximum Dry Density 105.0 PCF Optimum Water Content 17'5 o/o 130 125 GRADATION RESULTS (% PASSING) #200 #4 3t4" 69 100 100 oo-tFazulo to ATTERBERG LIMITS 1 20 LL PL 20 PI 28 8 115 Curves of 100% Saturation for Specific Gravity Equalto 110 2.80 2.70 2.60 10s 100 95 90 5 15 WATER CONTENT. % 0 10 20 25 30