Loading...
HomeMy WebLinkAboutConditionscov Dtr I o N}'LDNGPLANNNG 6. One-quarter-inch (6.4 mm) cement-based millboard. 7. Batts or blankets of mineral wool or glass fiber or other approved materials installed in such a manner as to be securely retained in place. 8. Cellulose insulation installed as tested in accordance with ASTM E 119 or UL 263, for the specific appli- cation. R302.11.1.1 Batts or blankets of mineral or glass fiber. Batts or blankets of mineral or glass fiber or other approved nonngid materials shall be permitted for compliance with the lO-foot (3048 mm) horizontal fireblocking in walls constructed using parallel rows of studs or staggered studs. R302.11.1.2 Unfaced fiberglass. Unfaced fiberglass batt insulation used as fireblocking shall fill the entire cross section of the wall cavity to a height of not less than 16 inches (406 mm) measured vertically. Where piping, conduit or similar obstructions are encountered, the insulation shall be packed tightly around the obstruction. R302.11.1.3 Loose-fill insulation material. Loose-fill insulation material shall not be used as a fireblock unless specifically tested in the form and manner intended for use to demonstrate its ability to remain in place and to retard the spread of fire and hot gases. R302.11.2 Fireblocking integrity. The integrity of fire- blocks shall be maintained. R302.12 Draftstopping. In combustible construction where there is usable space both above and below the concealed space of a floor-ceiling assembly, draftstops shall be installed so that the area of the concealed space does not exceed 1,000 square feet (92.9 m2). Draftstopping shall divide the con- cealed space into approximately equal areas. Where the assembly is enclosed by a floor membrane above and a ceil- ing membrane below, draftstopping shall be provided in fl oor-ceiling assemblies under the following circumstances : 1. Ceiling is suspended under the floor framing, 2. Floor framing is constructed of truss-type open-web or perforated members. R302.12.1 Materials. Draftstopping materials shall be not less than tlr-inch (12.7 mm) gypsum board, 3/r-inch (9.5 mm) wood structural panels or other approved materials adequately supported. Draftstopping shall be installed par- allel to the floor framing members unless otherwise approved by the building fficial. The integrity of the draftstops shall be maintained. R302.13 Fire protection of floors. Floor assemblies that are not required elsewhere in this code to be fire-resistance rated, shall be provided with a rlr-inch (12.7 mm) gypsum wall- board membrane, s/r-inch (16 mm) wood structural panel membrane, or equivalent on the underside of the floor fram- ing member. Penetrations or openings for ducts, vents, elec- trical outlets, lighting, devices, luminaires, wires, speakers, drainage, piping and similar openings or penetrations shall be permitted. Exceptions: 1. Floor assemblies located directly over a space pro- tected by an automatic sprinkler system in accor- dance with Section P2904, NFPA 13D, or other approved equivalent sprinkler system. 2. Floor assemblies located directly over a crawl space not intended for storage or fuel-fired appliances. 3. Portions of floor assemblies shall be permitted to be unprotected where complying with the following: 3.1. The aggregate area of the unprotected portions does not exceed 80 square feet(7.4 m2) per story 3.2. Fireblocking in accordance with Section R302. I 1 I is installed along the perimeter of the unprotected portion to separate the unprotected portion from the remainder of the floor assem- blv. 4. Wood floor assemblies using dimension lumber or structural composite lumber equal to or greater than 2-inch by lO-inch (50.8 mm by 254 mm) nominal dimension, or other approved floor assemblies dem- onstrating equivalent fire performance. R302.14 Combustible insulation clearance. Combustible insulation shall be separated not less than 3 inches (76 mm) from recessed luminaires, fan motors and other heat-produc- ing devices. Exception: Where heat-producing devices are listed for lesser clearances, combustible insulation complying with the listing requirements shall be separated in accordance with the conditions stipulated in the listing. Recessed luminaires installed in the building thermal envelope shall meet the requirements of Section Nl102.4.5 of this code. sEcTtoN R303 LIGHT, VENTILATION AND HEATING R303.1 Habitable rooms. Habitable rooms shall have an aggregate glazing area of not less than 8 percent of the floor area of such rooms. Natural ventilation shall be through win- dows, skylights, doors, louvers or other approved openings to J the outdoor air. Such openings shall be provided with ready access or shall otherwise be readily controllable by the build- ing occupants. The openable area to the outdoors shall be not less than 4 percent of the floor area being ventilated. Exceptions: 1. The glazed areas need not be openable where the opening is not required by Section R310 and a whole-house mechanical ventilation system is installed in accordance with Section M1507. 2. The glazed areas need not be installed in rooms where Exception I is satisfied and artificial light is provided that is capable of producing an average 4. One thickness of 3/o-inch (19.1 mm) particleboard with joints backed by 3lo-inch (19.1 mm) particle- board. 5. One-half-inch (I2.7 mm) gypsum board. ** 2015 INTERNATIONAL RESIDENTIAL CODE@ 55 'i * rt, t,ct, t,t* rs i* " BUTLDING prnruuNc, * d t* ,tt,o I :i' i f"? illumination of 6 footcandles (65 lux) over the area of the room at a height of 30 inches (762 mm) above the floor level. 3. Use of sunroom and patio covers, as defined in Sec- tion R202, shall be permitted for naturalventilationif in excess of 40 percent of the exterior sunroom walls are open, or are enclosed only by insect screening. R303.2 Adjoining rooms. For the purpose of determining light and ventilaticn requirements, any rocm shall be ccnsid- ered to be a portion of an adjoining room where not less than one-half of the area of the common wall is open and unob- structed and provides an opening of not less than one-tenth of the floor area of the interior room and not less thanZl square feet (2.3 nf). Exception: Openings required for light or ventilation shall be permitted to open into a sunroom with thermal isolation or a patio cover, provided that there is an openable area between the adjoining room and the sunroom or patio cover of not less than one-tenth of the floor area of the interior room and not less than 20 square feet (2 m2;. The minimum openable area to the outdoors shall be based upon the total floor area being ventilated. R303.3 Bathrooms. Bathrooms, water closet compartments qnrl nfhcr cimiler rnnmq chall he nrnrrirled rxrith aooreonf e. slaz--oo_-o--- o^-- ing area in windows of not less than 3 square feet (0.3 m2), one- half uf whi'Jh must bc openable. Exception: The glazed areas shall not be required where artificial light and a local exhaust systcm arc providcd. The minimum local exhaust rates shall be determined in accordance with Section M1507. Exhaust air from the space shall be exhausted directly to the out4oors. R303.4 Mechanical ventilation. Where the air infiltration I rate of adwelling unitis 5 air changes per hour or less where tested with a blower door at a pressure of 0.2 inch w.c (50 Pa) in accordance with Section Nl102.4.1.2, the dwelling unit shall be provided with whole-house mechanical ventilation in accordance with Section M1507.3. R303.5 Opening location. Outdoor intake and exhaust open- ings shall be located in accordance with Sections R303.5.1 and R303.5.2. R303.5.1 Intake openings" Mechanical and gravity out- door air intake openings shall be located not less than 10 feet (3048 mm) from any hazardous or noxious contami- nant, such as vents, chimneys, plumbing vents, streets, I alleys, parking lots and loading docks. For the purpose of this section, the exhaustfuom dwell- in6 unit toilet rooms, bathrooms and kitchens shall not be considered as hazardous or noxious. Exceptions: 1 Tha 1O-fnnf 1'lO/R mm l ccnqrqf inn ic nnf renrrirerltv aaa"t/ where the intake opening is located 3 feet (914 mm\ nr orc^tpr helnrrr fhe cnntqmi nent cnrrrceulrrl vr 2. Vents and chimneys serving fuel-burning appli- ances shall be terminated in accordance with the applicable provisions of Chapters 18 ano24. 3. Clothes dryer exhaust ducts shall be terminated in accordance with Section M1502.3. R303.5.2 Exhaust openings. Exhaust air shall not be directed onto walkways. R303.6 Outside opening protection. Air exhaust and intake opening,s that terminate outdoors shall be protected with cor- rosion-resistant screens, louvers or grilles having an opening size of not less thatl/oinch (6 mm) and a maximum opening size of tlrinch (13 mm), in any dimension. Openings shall be protected against local weather conditions. Outdoor air exhaust and intake openings shall meet the provisions for exterior wall opening protectives in accordance with this code. R303.7 Interior stairway illumination. Interior stairways shall be provided with an artificial light source to illuminate the landings and treads. The light source shall be capable of illuminating treads and landings to levels of not less than 1 foot-candle (11 lux) as measured at the center of treads and landings. There shall be a wall switch at each floor level to control the light source where the stairway has six or more risers. Exception: A switch is not required where remoteo central or automatic control of lighting is provided. R303.7.L Light activation. Where lighting outlets are installed in interior stairways, there shall be a wall switch at each floor level to control the lighting outlet where the stairway has six or more risers. The illumination of exte- rior stairways shall be controlled from inside the dwelling unit. Exception: Lights that are continuously illuminated or automatically controlled. R303.8 Exterior stairway illumination. Exterior stairways shall be provided with an artificial light source located at the top landing of the stairway. Exterior stairways providing access to a basement from the outdoor grade level shall be provided with an artificial light source located at the bottom landing of the stairway. R303.8.1 Sunroom additions" Required glazed openings shall be permitted to open into sunroom additions or patio covers that abut a street, yard or court if in excess of 40 pcrcent of the exterior suffoom walls are open, or are enclosed only by inseet screening, and the ceiling height of the sunroom is not less than 7 feet (2134 mm). R303.9 Required heaiing. Where the winier design iempera- ture in Table R301.2(1) is below 60'F (16"C), every dwelling -,--ir ^L^Il L^ --^-,:l^.J .,,lrL L^^+i-^ f^^:l:+:^. ^^-^Ll^ ^f --:nWLLL JltAlt ug Pruvrupu wrtll ll!411116 r4vrtruvo w4P4urv vt rrr4lrr- taining a room temperature of not less than 68'F (20'C) at a point 3 feet (914 mm) above the floor and 2 feet (610 mm) from exterior walls in habitable rooms at the design tempera- ture. The instaiiation of one or more portabie space heaters shall not be used to achieve compliance with this section. 56 ^AhEOzu tc ilI I El-$rA I lvtrAl nEitruErt I IAL vvvE 1 I I MND tt t, I 3 t t t: I i t , 1 (min) (Note 3) cvlindor lillsd dt the point of use fmm bulk truck 5&147 J ft Central AC comoressor (source'ot ignllion) s ft (min) (Note 1) (mln) {Note 3) not filled Crawl space opening, windows, or exhaust lan For Sl unils, 1 ft = 0.3048 m. Notes:iii'i ti mtnimum lrom relief valve in any dir€ction away from any exterior source of ignilion, openings into direct-v€nl appllances' br'mechanical venlilation air inlal€s. Refer to Table 6'4'4'3' idi ii1r,jlvifi6u, id'tiiieo ai tnJ po]ni of use lrom a cargo.tank motor vehicle, the tllling conn€ction and vent valve must be al lsast ii tr iio, i,ry **terior sourceiii!l'iti"nl "pri"ing$ into-direct-vent appliances, or mgchanlcal ventilation air intakes. Refer to 6.4.4'3. (3) Refer to 6.4.4.3. A FIGLRE I.l (a) Cyhnders. (Figw for iltusnatiae prposes only; cocle cortpliance reEuired'. ) the point ot use '10 ft (min) {Note Sluded text=Revisions, A =Text deletions and figure/table revisions. . =section deletions. N=Nervmaterial.2020 Ediilon *,'? +:,t ,* \, s.*;il ir* rl,l lttrLf,ulvt uru uuu&5&148 For Sl units, 1 fl = O.3048 m. oft (min) 1) 10 1)b atr ft 1) 10 0fr line that 25It of adioinino cen be built $uch conlainor ii ,A HGURE I.l(b) Aboveground ASME Containers, (Figtrefor iltustratiae pt$Poses onlyi eode compliance required..) central AC (source ILfL --J1 to dk€ct- vent 2020 Edition Shacled rext = Revisions. A ='fcxt deletions and figure,/table revisions. . = Section delerions. .fV = New material. 1 t 1 I ANNEX I 58.14 { j ItI I I Window air ntake to direct- 10 ft (min) (Note 1) /'l0 ft (Note 1) 10 ft (min) (Note 2)Central AC complessol (source of ignition) Crawl space opening, window, or exhaust fan |*-*_10 ft (min)I (Note 2)-,,r '-------*z : /''W.g. .... For sr unirs, 1 ft - 0.3048 m. -"/u-fr:fttffllltt " "djoining propettv that can be Notes: t1) Tie rstigl valve, tiiling ognnection, and lixed maximum liquid level gquge_v€nl conneolion al the sontainor mu$t be at least 10 lt fiom any sxterior iiuii[ or ig;itibn, bpeniid'Jlnio Jiieir-venr appllances, or niechanicaf ventllation alr intakes. B€fer to 6.4.4'4. {e} No p6rr ot an unoergr;;ni';o*;iiilii.in 66 rE"*ih;n i0 tt tram an lrnportanl builcllng or llne ofad,oining property that can be built upon. RefertoTable 6.4.1.1. A FIGLiRE I.l (c) Underground ASME Contain ers. (Figare for illastrotive purpascs only; code complionce tequired') al.Shatletl r.r:xt=Revisious. A -'li:xtdclctionsandfigure/table revisi.ons. ' =section deleiions' N=Newmaterial'2020 Edltior lil IilLffi lf {11 I tlHrt |ill I [,r' l'fr I hililltld I'JilLl'il f I il I Reception$: A92542iaitliltzolz o4t19:@@ PFi Jean Flberioo ---. -iE' ;t' AT' i.;-F; ; 5@. b',i o6d-Feii : il. ila GnRFIELD couNrY c0 the devices in each row shall be staggered for a spacing ofno more than 24 inches on center measured parallel with the exterior wall line. Continuous snow barriers shall be secured to roof framing at no more than 48 inches on center. Continuous baniers shall be installed parallel with the exterior wall line and no more than 24 inches from the edge ofthe roof or eave. 33. Section R908.1 is amended to read as follows: R908.1 General. Materials and methods of application used for re-covering or replacing an existing roof covering shall comply with the requirements of Chapter 9. A separate permit is required for re-roofing. Exceptions remain. 34. Section Rl004 is amended to delete Sec. R1004,4. 35. Section R1005 is amended by adding new subsection to read as follows: R1005.8 Factory-built chimney chases shall be eflectively fire blocked within the chase enclosure at each floor-ceiling level and at the roof. The vertical distance between adjacent fire blocking shall not exceed 10 feet. 36. Replace Chapter I I Energy Efficiency from the 2015 IRC with Chapter I I 2009IRC 37. Section M1308 is arnended to add the following: M1308.3 LPG (liquid petroleum gas) appliances. LPG appliances shall not be installed in a pit, basement or similar location where heavier than air gases collect unless such location is provided with an approved means for removal of unburned gas. The policy in Garfield County to approve such a means is as follows: l. An untrapped drain with a minimum diameter of 4 inches located in the lowest area where heavier than air vapors may colleet is to run with a continuous slope to an exterior area, which is not within a depression or recessed below the adjacent tenain. 2. The area of termination is to be determined by the building inspector as likely to remain free of standing water, ise and other debris that may prevent the flow and dissipation of unbumed gas. 3. The upper inlet and the termination of the drain are to be provided with protection from the entry of debris or animals, which may cause blockage of the drain. 38. Section M1401 is amended to add the following subsection: Mf 401.6 LPG Fuel. See Sec. M1308.3 on using LPG appliances in a pit or basement. 39. Section M2001 is amended to add the following subsection: M2001.5 LPG Fuel. See sec. M1308.3 0n using LPG appliances in a pit or basement, l-5 fil flrril|lilFJlri,Tlll{i''#tirfiLlilltlrff hrlll4 ffi ] ltl Receotion*i A92542 I{' N iE""Z^i$ ; tE, EB 033"F.! lb?66'Ennr I euo couNrY co 40. Section G2404 is amended to add the following subsection: G2404.12 LPG Fuel. See Sec. M1308.3 on using LPG appliances in a pit or basement. 41. Section G2406.2is amended to .eal as follows: 1. G2406.2 Prohibited locations. Appltances shall not be located in sleeping rooms, bathrooms, toilet rooms, storage closets or surgical rooms, or in a space that opens only into such rooms or spaces, except where the installation complies with one of the following: 1. The appliance is a direct-vent appliance installed in accordance with the conditions of the listing and the manufacturer's instructions. 2. Vented room heaters, wallfurnace.r, vented decorative appliances, vented gas tir eplaces, vented gas fireplace heaters, and decorative appli anc es for installation in vented solid fuel-bwningfireplaces arc installed in rooms that meet the required volume criteria of Section A2407.5. 3 . The appliance is installed in a room or space that opens only into a bedroom or bathroom, and such room or space is used for no other purpose and is provided with a solid weather-stripped door equipped with an approved self-closing device. All combustion air shall be taken directly from the outdoors in accordance with Section G24A7.6 42. Section G2417.4.7 is amended to read as follows G2411.4.1 Test pressure. The test pressure to be used shall be not less than one and one-half times the proposed maximum working pressure, but not less than l0 psig, irrespective of design pressure. Where the test pressure exceeds 125 psig, the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. 43. Section G2433 Log Lighters is amended to add the following: G2433.1General. Log lighters are prohibited. 44. Section G2445 Unvented Room Heaters is hereby deleted in its entirety. Unvented heaters are not allowed, 45. Section P260l.l is amended to read as follows: P260l.l Scope. The provisions of this chapter shall establish the general administrative requirements applicable to plumbing systems and inspectionrequirements ofthis code. The intent ofthis code is to meet or exceed the requirements ofthe State of Colorado Plumbing Code. When technical requirements, specifications or standards in the Colorado Plumbing L6 llfl ll,l h lllil l{ ltffi t lllt tlr{\ I I fr h I llhllj il'!j lll I rrSI I I I I I Receptionft 892542 @5t1dt2@17 @4;19:@@ Pll J€an nlberico 11 oi 41 -Re;.Fea;$o.0@ Doc Fee:@.@0 GARFIELD couNTY c0 Code conflict with this code, the more restrictive shall apply 46. Section P2603.5.1 is completed by adding 12 in the first [] and l8 in the second set of []. 47. Section'P2910.1and 291 i.I are amended by adding the following section: P2910.1 .l (2gl1.i) At the time of amendment development, state ptumUing code, health code and state water law were being reviewed for use of grey water in Colorado. Section P2910 and2911 must be in compliance with all state requirements. 48. The entire Part VIII Electrical Chapters 34-43 is deleted. All electrical work shall be done in accordance with the State of Colorado Electrical Inspector, 49. The following Appendixes are adopted: Appendix E Manufactured Housing Used as Dwellings Appendix F Passive Radon Gas Controls is adopted for tested structures with radon issues. Appendix G Pipe Standards for various Applications Appendix H Patio Covers. Appendix J Existing Buildings and Structures Appendix M Home Day Care-R-3 Occupancy is adopted. When there is a conflict with State of Colorado regulations, State regulations rule. Appendix R Light Straw-Clay Construction Appendix S Strawbale Construction is adopted. Appendix V Tiny Homes ICC R8168-16 is adopted' ru. 2015_U{TEB$IATIONA!_B_UILDING q-qDE (l.B.C.) A. Additions and Modifications: The Sections of the I.B.C. are adopted subject to the following additions or modifications: 1. Section 101.1 is amended to read as follows: 101.1 Titlc. This code shall be known as the Cammercial Building Code of Garfreld County, Colorado. This code shall apply to all of the unincorporated area of Garfield County, Colorado. 2. Section 104.1 is amended to read as follows 104.1 General The building official or any authorized representative, is hereby authorized and directed to enforce all of the provisions of this code; however, a guarantee that all buitdings and structures have been constructed in accordance with all ofthe provisions of this code is neither intended nor implied. The building olficial shall have the authority to render interpretations of this code and to adopt policies and procedures in order to clarify L7 LIOUEFIED PETROLEUM GASES sEcTloN 6104 LOCATION OF LP.GAS CONTAINERS 6104.1General. The storage and handling of LP-gas and the installation and maintenance of related equipment shall com- lrith TI\XFPA's8 a-nd besu-bjeet to the approval-af the f,ire 6104.3 Container location. LP-gas containers shall becodefficial, except as provided in this chapter 6104.2 Maximum capacity within estatrlished limits.located with respect to buildings, public ways and lot lines of. Within the limits established by law restricting the storage of adjoining property that can be built upon,in accordance with liquefied petroleum gas for the protection of heavily popu-Table 6104.3. 6104.3.1 Installation on roof prohibited. LP-gas con- tainers used in stationary installations shall not be located on the roofs ofbuildings. 6104,3.2 Special hazards. LP-gas containers shall be located with respect to special hazards including, but not limited to, above-ground flammable or combustible liquid lated or congested areas , the aggregate caPacitY of anY one installation shall not exceed a water capacity of 2,000 gallons eration of special features such as topographical condi- tions, nature of occupancy, and proximity to buildings, capacity of proposed LP-gas containers, degree of fire pro- tection to be provided and capabilities of the local fire (7570L) (see Section 3 of the Sample Legislation for Adop- tion of the International Fire Code on page xxi). Exception; In particular installations, this capacity limit shall be determined by the fire code fficial, after consid- TABLE 6104,3 LOCATION OF LP-GAS CONTAINERS LP.GAS CONTAINER CAPACITY (water gallons) MINIMUM SEPARATION BETWEEN LP.GAS CONTAINEBS AND BUILDINGS, PUBLIC WAYS OR LOT LINES OF ADJOINING PROPERTY THAT CAN BE BUILT UPON MINIMUM SEPABATION BETWEEN LP-GAS CONTAINERSb' " (feet)Mounded or underground LP-gas containers' (feet) Above-ground LP-gas containersb (feet) Less than 125"'d t0 5"None 125 to 250 10 10 None 251 to 500 10 10 3 501 to 2,000 10 25't 3 2,001 to 30,000 50 50 5 30,001 to 70,000 50 75 (0.25 of sum of diameters of adjacent LP-gas containers)70,001 to 90,000 50 100 90,001 to 120,000 50 125 For SI: I foot = 304.8 mm, i gallon = 3.785 L' a. Minimum distance for undJrgr.ound Lp-gas containers shall be measured from the pressure relief device and the filling or iiquid^level gauge vent connection at the container, except that JL parts of ai unclerground LP-gas container shall be not less than 10 feet from a building or lot line of adjoining property that can be built upon. b. For other than instaliations in which the overhanging stmcnrre is 50 feet or more above the relief-valve discharge outlet. In applying the distance between buiidings and ASME Lp-gas containers with a warer capaciry of 125 gallons ormore, not less than 50 percent ofthis horizontal distance shall also apply to all portioni of the building tliJproject more rhan 5 feet from the building wall and that are higher than the relief valve discha'ge outlet. This horizontal distance shall be measured f.ollr "poiniOetennined by projecting the outsidtedge of such overhanging structure vertically downward to grade ol other level upon which the Lp-gas containei is installed. Distancis to the builcling wall shall be not less than those prcscribed in this table c. where underground multicontainer instaliations are composed of individual.LP-gas containers having a water capacity of [25 gallons ot tnote, such containers shall be installed so as to provide access at their ends or sides to facilitate working with cranes or hoists. d. At a consumer site, if the aggrcgate water capacity of a multicontainer installation, comprised of individual LP-gas containers having a watel capacity of less than 125 gallons, is 500 gjions"or more, the minimum distance shall comply with the appropdate portion of Tabie 6104.3, applying the aggr€gate capacity rather than the capacity per Lp-gas container. If more than one such installation is made, each installation shall be separated fiom othel installations by not less than 25 feet. Minimum distances between LP-gas containers need not be applied. e. The fotlowing shall apply to above-gfound containets installed alongside buildings: 1. Lp-gas containers of less than a I25-gallon water capacity are allowed next to the building they serve where in compliance with Items 2, 3 and 4. 2. Department of Transportation (DoTn) specification LP-gas containers shall be located and installed so that the discharye ffom the containel pressule reliefdevice is not less than 3 feet horizontally from building openings below the level ofsuch discharge and shall not be beneath buildings unless the space is well ventilated to the outside and is not enclosed for more than 50 percent of its perimeter. The dischalge from LP-gas container pressure relief devices shall be located not less than 5 feet from exterior sources of ignition, openings into dircct-vent (sealed combustion system) appliances or mechanical ventilation ail intakes. 3. ASMELp-gascontainersoflessthanal25-gallonwatercapacityshallbelocatedandinstalledsuchthatthedischargefrompressnrereliefdevicesshall not terninate in or beneath buiidings and shall be located not less than 5 feet horizontally from building openings below the level of such discharge and not less than 5 feet from exterior iources of ignition, openings into direct vent (sealed combustion system) appliances, or mechanical ventilation air intakes. 4. The filling connection a1d the vent from liquid-level gauges on either DOTn or ASME LP-gas containers filled at the point of installation shall be not less than l0feetfl.omexteriorsourcesofignition,openingsintodirectvent(sealedcombustionsystem)appliancesormechanicalventilationailintakes. f. This distance is allowed to be reduced to not less than 10 feet for a single LP-gas container of 1,2OO-gallon water capacity or less, provided such containet is not less thali 25 feet frorn othel LP-gas containers of mole than I 25-gallon watef capacity' 4s8 20IS |NTERNAT|ONAL FIRE CODE@ Colleen Wirth From: Sent: To: Colleen Wirth Wednesday, March 6,2024 7:40 AM Colleen Wirth BLRE-02-24-8525 - plat researchSubject: Matthies Exemption Plat, Lot 2 Reception 47[OSL BLRE-02-24-8525 Performed research from home Colleen Wirth Building Plans Examiner Garfield County Community Development 108 8th Street, Suite 401 (970) 945-1377 ext L61O cwi rth @ga rfi e ld-co u nty.com fr}S NffiT" qtr"ee-E 1