4730 South College Ave, Suite 201, Fort Collins, CO 80525
Phone (970) 225.2422 - Fax (970) 225.2622
March 29. 2024
Unity Mountain Builders
Attn: Luis Vargas
Re: Framing Inspection Items
543 Ponderosa Circle
Battlement Mesa, Colorado
Project No. 223115
Gentlemen:
A representative of Weeks & Associates reviewed framing items noted during the
framing inspection at the referenced site.
1) We understand there is a floor I-joist below the master bedroom that is spaced
19” from the neighboring joist. We also understand the floor joists installed are
11 7/8” BCI 6000 series I-joists. The joist in question spans no more than 17’-0”.
This joist at the spacing noted is sufficient to carry the design loads.
2) We understand the steel beam below the floor is attached to the steel cap
plates at the column locations with (4) 5/8”-diameter bolts into the bottom beam
flange. This connection is acceptable.
If we can be of further assistance, please contact us.
Sincerely,
Weeks & Associates, Inc.
Patrick Sanders, P.E. Gary G. Weeks, P.E.
Staff Engineer Structural Engineer