July 18,2023
TO: Norberto Varela, Grandmaster Construdion/ Garfield County Building Dept.
From: Tom Strizki, TCS Engineering Service
Subject lnspection of reconstruction of roof truss system for manufactured
Silt, Colorado
To whom it may concern,
On July 6, 2023 and inspection was performed on a roof truss reconstruction after a fire at the above
address. House was construded as a manufac{ured home using splittrussesfor construction of the roof.
The entire roof truss framing for the South Eposure was replaced as part of the reconstrudion.
Replacement roof trusses were designed to meet 2018 IBC Codes for a snow load of 40 PSF and an
Ultimate wind speed of 115 MPH. Below are pictures of the truss replacement.
\I
$
\$
E
0
v:t
L.N
rEEiE.l
E#-+ tlul lrre! gt
rdl -lEft
FE
=Et#E
EIrttN4lImN
I4tEI
Ilr
-EE
ln
trt
Elr
trt
vt
L
IE
IJ
Ntrt
-
SUIUECTTO NOTED EXCIP'l',lONS & rNSt,r (, i , '\\\
GARFIELDCOUNTY ()I)NIIJNT
DATE g.z2-33 BY
at 1354 Mineota Drive,
NO INSPECTION WI'[II()tIl 'l'IIlrsll !'1.,1 '','{ ON SITE
-i*t\s
s''
-l}'
#'
f;'trr,4
..SiJf
#
r Page2 July 19, 2023
The roof truss replacement and sheathing installation was found to meet the building codes stated in this
letter and was approved.
lf there are any questions regarding this letter, please feel free to call my office at the above number
Tom Strizki, Colorado PE# 30989
TCS Engineering Service
97G532-3326
Digitally
signed by
Tom Strizki
Date:
2023.07.19
O7:20:31
-06'00'
, ,: "rr;t ].{ q,: .. i ,,'$i. .IISi{..i, i i11:
ri r, :
:!i'i
Gaffield Coulnty
Reouired Ins nections for
Sinele Familv Homes
Garfield County lnspections: (970) 945-1377 EXf 1621
(lnspections are to be called in by 4:30 pm the previous business day)
State Electrical lnspections: (303) 869-3458
Utilitv lnspection - Water and Sewer connection. This inspection is to be performed by WaterMastewater
provider, HOA and Garfield County Public Health respectively'
Work in the Public Wav and Drivewav Permits
Please contact CarfietO County Road and Bridge departmentat9T0-625-8601
Footinq lnspection
prior to placennent of concrete, rebar, forms, and UFER ground rod are to be inspected. Provide
excavation observation report if required under Conditions of Permit.
Foundation Inspection
-prnroptacementofconcrete,rebarandformsaretobeinspected.
Underqround Plumbino lnsPection
priortoplacementofconcreteorfill.Pressuretestwasteto5psi.
Pressure test water to 100 Psi.
ln-floor HeaVSnow Melt lnspection
@concrete,heatpipingtobepressuretestedto100psiormfg
recommendation.
are in place, prior to the installation of insulation and
drywall, thi s inspection is performed bY the state electrical inspector. Please have the electrical
inspector sign the building card or provide documentation of passing inspection on site
Plumbinq Ro h lnsoection
Pressure test DVIiV to Spsi or a 10' head of water
Pressure test water pipe to 100psi or working water pressure of the system
to 10 psi, soap test permissible for minor additions
fF Auar9 paeD (G-e.arxen$Cr.
s, combustion air, supply ducting, range hood, fireplaces, and
mplete. A neutralizer is required on flue condensates.
pipes. Rough-in for chosen energy compliance path to be complete?
co
Mechanical Rouoh lnsPection
Ducting of bath
SPS| test on PVC flue
When allwood is in the electrical rough inspection has been approved. The plumbing
roug hs can be done with the framing inspection. Any structural steel to be
inspected and approved by a third-party inspeetor and inspection report available to county
inspector air-sealing provided in framed systems to prevent air leakage (201 s IECC)?
barrier to be in place for this inspection. Have insulation certificate from
at time of inspection
Joints to be , screws to be 12" OC and do not break the paper!
with living space above to be 6" OC.
Shower Pan lnspection
Pre-slope to be installed, liner in place, test ball in the waste line and fill the liner with water. The
test is for 24 hours and no visible leaks.
State Final Electrical lnspection
When all boxes and I res are complete, covers in place, this inspection is performed
inspector. Please have the electrical inspector sign the building card or
provide documentation of ng inspection on site
, the final inspections can be performed. Exterior lighting will be
in time. \Men this inspection is and all papenrork is received: the ILC
(survey); Fire District sign-off and/or 2018 Ene iance Path reports, as applicable
Miscellaneous lnspections
Stucco and stone lath to be inspected. Attachment of lath to be on studs 6' OC
Nat all inspections tc be evaluated hy the building official are required for all permit types. Additional
^- *,.lli-l- i--*-r:--- -t --.. -r__ !_ L_ -Lrr rrrurUFrc ilrsPELLrurrr ur dny r.ype dre dl5o [o oe evatuateo oytne ouilotng oTltclal ano may requtre
additional fees. Failure of an lnspectisn may require paym€nt of a re-inspectisn fee of $5S.00 to be
paid prior to the re-inspection being scheduled. See Sec, R109, 2009 IRC or Sec. 110, 2S09 tBe for
further information.
Electrjcal inspections are to be performed by the State of Colorado and the rough-in must precede
the framing inspection and the final must prerede the building final.
Septic permits require percolation testing for design and final inspection and shall be performed by
the designer of the system.
Access to verifo carbon mcnoxide alarm installations are required for all perrnits outside the home,
such as derks or reraofing. Scmeone is rreeded to escort the inspector through the horne.
Aggressive dogs need to he managed during the inspectcr's visit to a jobsite. A re-inspection fee of
$S0.00 may be assessed if the inspector cannot get sut of their vehicle due ta an aggressive or
barking dog.
approved,
rgy Compl
lnsulation and
lnsulation lnspection
r final