HomeMy WebLinkAboutManual J ReportZone Sizing Summary for Default System Project Name: Spanel Residence - Climate Zone 5 Preoared bv: AEC 051211202t O2:44PN Air System lnformation Sizing Calculation lnformation Calculation Months .......... Jan to Dec Sizing Data Calculated Zone Terminal Sizing Data Zone Peak Sensible Loads Space Loads and Airflows Number ofzones Floor Area Location Zone CFM Sizing ............... Sum of space airflow rates Space CFM Sizing ........... lndividual peak space loads Air System Name Equipment Class Air System Type . .......... .. Default System UNDEF SZCAV ft2 $ oF LtrsT - a-r5E 0erek Additisn E lg0 Piedmont Rd, EWS Ehelyn Acres, Tract 2 Zone Name Design Supply Airflow {CFM) Minimum Supply Airflow {CFM) Zone cFM/ft, Reheat Coil Load {MBH) Reheat Goil Water gpm @ 20.o"F Zone Htg Unit Goil Load (MBH) Zone Htg Unit Water gpm @ 20.0"F Mixing Box Fan Airflow {CFM) Zone 1 565 565 1.05 0.0 0.00 0.0 0.00 0 Zone Name Zone Cooling Sensible (MBH) Time of Peak Sensible Coolinq Load Zone Heating Load (MBH) Zone Floor Area (ft') Zone 1 8.'l Jul 1 500 8.3 540.0 Zone Name / Soace Name Mult. Cooling Sensible {MBH) Time of Peak Sensible Load Air Flow (CFM) Heating Load (MBH) Floor Area (ftr) Space cFM/ft1 Zone I 101 PRIMARY BEDROOM 1 3.8 Jul 1400 257 4.1 220.0 't.17 1 02 BATH AND CLOSET 1 4.5 Auq 1600 308 4.1 320.0 0.96 WNTER DESIGN CONDITIONS SUMMER DESIGN CONDITIONS OUTDOOR TEMPERATURE -2 .F OUTDOOR TEMPERATURE 88 F INDOOR TEMPERATURE 70 .F INDOOR TEMPERATURE 75 F TOTAL HEAT LOSS 8,300 BTU/HR SENSIBLE HEAT GAIN 8,'100 BTU/HR LATENT HEAT GAIN 0 BTU/HR TOTAL HEAT GAIN 8,1 00 BTU/HR Program 5 Page 1 of 1