HomeMy WebLinkAboutDuct Test JEDI Balancing, Inc. 568 Briggs Street (physical) P.O. Box 525 (mail) Erie, CO. 80516 Phone (720) 839-5333 www.jedibalancing.com Duct Air Leakage Testing DALT Report Project 64 Talon Trail DALT Address 64 Talon Trail Parachute, CO 81635 Architect Unavailable Mechanical Engineer Unavailable Contractor Rapid Creek Mechanical Company Date 6/6/2024 Job Number 2024-10223 Donald W. Pittser TABB Certified Supervisor TABB Firm Certification #BB009003C Stamp Expires 9/30/2024 Warranty Information: The data presented in this report is a record of system measurements and final adjustments that have been obtained in accordance with the current edition of the SMACNA DALT Manual. The measurements shown, and the information given, in this report are certified to be accurate and complete, at the time and date information was gathered. Any variances from design quantities, which exceed SMACNA tolerances, are noted in the report project summary. This DALT has a one-year guarantee from the date listed on this cover page as long as the duct work has not been altered or changed. Instrumentation: Digital Manometer Retrotec DM-32 Fan Blower Retrotec 340 Method of Duct Air Leakage Testing: JEDI Balancing followed the SMACNA DALT Manual. JEDI Balancing is a SMACNA Contractor signatory to the International Association of Sheet Metal, Air, Rail and Transportation Workers (SMART) Local #09 Denver, Colorado, USA. Mr. Bryan Hund is a General Foreman Union Sheet Metal Journeyman with 25 years in the union performing TAB, DALT and ductwork fabrication / installation. Abbreviation Index TAB: Testing, Adjusting & Balancing Cx: Commissioning OD: Outside Diameter AHU: Air Handling Unit Motor FLA: Full Load Amperage T1: Terminal 1 RTU: Roof Top Unit S.F.: Service Factor T2: Terminal 2 PACU: Packaged Air Conditioning Unit RPM: Revolutions per Minute T3: Terminal 3 MAU: Make Up Air Unit P.F.: Power Factor CS: Circuit Setter FCU: Fan Coil Unit Nom. Eff.: Nominal Efficiency BV: Balance Valve VAV: Variable Air Volume TDH: Total Dynamic Head K Factor: Correction Factor FPB: Fan Powered Box AK: Area Correction PSI: Pounds per Square Inch CUH: Cabinet Unit Heater Valve D.P.: Discharge Pressure UH: Unit Heater Valve S.P.: Suction Pressure ERV: Energy Recovery Ventilator ERU: Energy Recovery Unit EF: Exhaust Fan PEF: Power Exhaust Fan KEF: Kitchen Exhaust Fan SF: Supply Fan RF: Return Fan TF: Transfer Fan Diff.: Differential SEF: Smoke Exhaust Fan DX: Direct Expansion SACU: Spilt Air Conditioner Unit SP: Static Pressure TSP: Total Static Pressure in. wc: Inches Water Column ESP: External Static Pressure HW: Heating Water VP: Velocity Pressure CHW: Cooling Water SA: Supply Air CW: Condenser Water RA: Return Air HX: Heat Exchanger OSA: Outside Air SWD: Sidewall Diffuser MA: Mixed Air EAT: Entering Air Temperature OA: Outside Air CD: Ceiling Diffuser EWT: Entering Water Temperature SD: Supply Diffuser ER: Exhaust Register LAT: Leaving Air Temperature MVD: Manual Volume Damper RG: Return Grille LWT: Leaving Water Temperature OBD: Opposed Blade Damper NAC: No Access CFM: Cubic Feet Per Minute CMH: Cubic Meters per Hour NG: Not Given FPM: Feet Per Minute SSD: Square Supply Diffuser NIC: Not in Contract SRD: Square Return Diffuser E: Existing M: Meter TG: Transfer Grille cm: Centimeter Pa: Pascal l/s: Liters per Second mm: Millimeter kPa: Kilopascal ADM: Air Data Meter (manometer) SPF: Stairwell Pressurization Fan Design D.P.: Design Differential Pressure Actual D.P.: Recorded Differential Pressure Ind.Imp.Dia. Indicated Impeller Diameter CRAC: Computer Room Air Conditioning Unit Duct Leakage Test Form Customers Name·--------------­ Address: City: St.ite/Zip : Lot & Block: Permit#: Builders Name: Company Name: Address: City:. State/ Zip: R403.3.2 Sealing (Mandatory). Ducts, air handlers and filter boxes shall be sealed. Joints and seams shall with either the IMC ·International Mc�chanical Code or IRC • International Residenti;il Code, as applicable. R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods. 1: Rough-In Test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer air handlers enclosure if installed at the time of th<➔ test. All registers shall be taped or otherwise sealed during the test. 2: Post-construction test: Total leakage shall be measured with a pressure differential of 0.31 inch w.g. (25 PA) across the system, including the manufacturer air handlers enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. Exception: Duct air leakage test shall not be required where the dlicts .ind .iir handlers are located within the building thermal envelop�?. A written report of the results of the test shall be �igned by the conducting the test and provided to the code official. R403.3.4 Duct leakage (Prescriptive) The total leakage of the ducts. were measured in accordance with Section R403.3.3, shall follow: l: Rough-in test. The total leakage shall be less than or equal to 4 cubic feet per minute (113.3 l/min.) per 100 square feet (9.29 m2) of conditioned floor area where the air handlEar is installed at the time of the test. Where the air handler is not installed at the time of the test, the total leakage shall be less than or equal to 3 ctibic feet per minute� (85 l/min) per 100 square feet {9.29 m2) of conditioned floor area. 2: Post-construction test: Total leakage shall be less than or equal to 4 cubic feet per minute (113.3 L/min) per 100 square feet (92.9 m2) of conditioned floor area. R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenum's. No Panning of wall cavities for supply or return ducts & plenum's. Test Conditions: Date: Time: Indoor Temperature: Outdoor Temperature: Conditioned Floor Area: System Airflow (cfm): Cooling Size (btu): Heating Size (btu): Notes: Total Leakage Test Depress ___ Press _ Test Pressure: ___ (Pa) Test Pressure locati�n: Baseline Duct Pressure (optional): Zone Duct Flow Ring Fan Press Flow Press. (Pa) Installed (Pa) (cfm) Results: Tot.ii Leakage (cfm): Maximum Allowable Leakage (cfm): Pass/ Fail 4 dm per 100 ft2 3 cfm per 100 ni Test: 0 Post•constrqction, total leakage 0 Rough In Test. total leakage Test Performed By: Company; --- Name: Phone: Email: Signature: I 1689 SQFT don@jedibalancing.com Jedi Balancing Bryan Hund 720-839-6468 __________________________ James & Celia Lofink Colorado 64 Talon Trail BLRE-11-23-8418 25 Sup/Ret/Erv House location & Builder Information: 8:00 AM X 25.5 Luis Vargas Herrera 06/5/24 64 56 46 51 46 Parachute N/A N/A N/A MAIN DUCTS #4725.0 location