HomeMy WebLinkAboutEngineer's OWTS Design Plan129 CAINS LANE CARBoNDALE, CO 81623 970.309.5259 CARLA.oSTBERG@GMAIL.CoM Fil':t"l' r(' ('('\'F;r't.'l't :i(i May 10,2024 Project No. C1877 Jeremy Keranen ie remv@vou nq-services.com Subsurface lnvestigation and Onsite Wastewater Treatment System Design 4-Bedroom Residence + 1-Bedroom Accessory Dwelling Unit (ADU) 449 Ram Lane Garfield County, Colorado Jeremy, CBO lnc. performed a subsurface investigation and completed an onsite wastewater treatment system (OWTS) design for the subject residence. The 10.21-acre property is located outside of Silt, in an area where OWTSs and wells are necessary. Legal Description: Section: 32 Township: 5 Range: 91 A TR lN SENENW CONT. 10.21 AC AKA LOT 4 PIFFER SUB-DIV EXEMPTION. Parcel lD: 2125322001 99 SITE CONDITIONS The property is currently developed with a 3-bedroom residence. The residence is served by an existing OWTS. The system consists of a 1250-gallon, two-compartment Copeland concrete septic tank followed by a soil treatment area (STA) comprised of gravelless chamber trenches. Garfield Count lndividual Sewage Disposal System (ISDS) Permit 4193 documents the system. The system was sized to accommodate 3 bedrooms. The permit received final approval on November 6, 2006. The existing STA is experiencing slow draining. There is a desire to size the new system to accommodate an additional bedroom in the residence (total 4 bedrooms) and for a 1-bedroom accessory dwelling unit (ADU). The residences will be served by a private well on the property. There are several wells located to the south of the residence. The wells are at least 50-feet from any existing or proposed septic tank and at least 100-feet from the proposed STA. The water line must be located. We have approximated the location of the water line on our site plan. The water line must be at least 2S-feet from the proposed STA, at least 1O-feet from the proposed septic tank, and at least S-feet from any sewer line. Where the sewer line crosses the water line, it must be properly encased. See W3.0/5 Encasement Detail. The proposed soil treatment area (STA) location has an approximate ten percent slope to the southeast. The proposed area is sparsely vegetated. There should be no traffic or staging of material over the future STA site to avoid compaction of soils prior to construction of the STA. Page2 SUBSURFACE The subsurface was investigated on April 30,2024 by digging two soil profile test pit excavations (Test Pits). A visual and tactile soil analysis was completed by Carla Ostberg at the time of excavation.l The materials encountered in Test Pit #1 consisted of light brown silt clay loam topsoil to a maximum depth explored of 6.0-feet. No bedrock or groundwater was encountered. The materials encountered in Test Pit #2 consisted of light brown silt clay loam topsoil to a maximum depth explored of 7.O-feet. No bedrock or groundwater was encountered. A sample of the soil was taken from Test Pil#2 at 3-feet below grade. Soil structure grade was moderate. The soilformed a ball and a ribbon 1 to 2-inches in length before breaking. Soil structure shape was blocky and consistence was friable to firm. Soil texture was more smooth than gritty. The soil is consistent with Soil Type 3, Silt Clay Loam, with moderate structure grade. A long-term acceptance rate (LTAR) of 0.35 gallons per square foot will be used to design the STA. Test Pit #1 excavation near septic tank Test Pit #2 ' Carla Ostberg holds a Certificate of Attendance and Examination from the CPOWVisual and Tactile Evaluation of Soils Training. Page 3 Sieved sample Ribbon 1 to 2-inches DESIGN SPECIFICATIONS The existing STA will be abandoned in place. Desiqn Calculations: Main House = 75 GPD x 2 people/bedroom x 3 Bedrooms + 75 GPD (4th Bedroom) = 525 GPD ADU = 75 GPD x2 people/bedroom x 1 bedroom = 150 GPG Average Daily Flow = 675 GPD LTAR = 0.35 GPD/SF 675 GPD / 0.35 GPD/SF = 1928 SF x 1 .0 (gravity, trenches) x 0.7 (chambers) = '1359 tt The OWTS design is based on 4-bedrooms in the Main House and 1-bedroom in the ADU. An average daily wastewater flow of 675 GPD will be used. The existing 1250-gallon, two-compartment concrete septic tank serving the Main House will remain. We recommend exploring the sewer line with a camera to assure it is in good condition. A double-sweep clean out should be installed between the house and the septic tank. The septic tank must have an inlet sanitary tee and an Orecno@ Biotube Effluent filter must be installed on the outlet side of the septic tank. Page 4 Risers must bring the manhole lids to grade for access. lf more than one riser is added to the septic tank, an extension handle must be installed on the effluent filter. Pipes used for access will be replaced with proper risers. A new minimum 4-inch diameter SDR-35 sewer line will be installed to serve the ADU with double-sweep clean out and a minimum2o/o grade to the septic tank. Any area under a driveway or traffic area must be minimum Schedule 40. The sewer line will cross the water line. The sewer line must be properly encased within S-feet of the crossing (See W3.0/5 Encasement Detail). A new 10OO-gallon, two-compartment lnfiltrator@ poly septic tank with an Orenco@ Biotube effluent filter on the outlet tee must be installed to serve the ADU. Any state-approved concrete or poly septic tank may be substituted. Risers must bring the manhole lids to grade for access. lf more than one riser is added to the septic tank, an extension handle must be installed on the effluent filter. For the purposes of this OWTS design, Benchmark Elevation has been established as 100' as the existing sewer line exiting the existing septic tank. CBO lnc. should be notified of any discrepancies or problems with grade elevations of proposed components during installation of the OWTS. *Elevations are based upon sta OWTS installation practices. Component elevations may change g installation due to site conditions. Minimum grade refers to piping between components. Sewer lines exiting the septic tank must be minimum 4-inch diameter SDR-35 with a minimum 1% fall to the distribution box. The sewer line from the ADU septic tank must tie into the sewer line from the septic tank serving the Main House with a wye fitting before the distribution box. Minimum ElevationOWTS Component Approximate horizontal distance 76' I min.2% lall I min. 19" fall Primary Tank lnlet lnvert (ADU Tank) Approximate horizontal distance 115' from ADU septic tank / min.1o/o fall/ min. 26.75" lall Approximate horizontal distance 30'from Main House septic tank / min. 1o/o fall / min. 3.75" fall Distribution Box Approximate horizontal d istance 44' to fu rthest trench / min. 1% fall to STA / min. 5.5" fall lnfiltrative Surface Page 5 Effluent will gravity flow to a distribution box, and then to six gravelless chamber trenches. The distribution box must be accessible from grade and must have flow equalizers, or similar product, installed on each outlet pipe in the distribution box to assure equalflow to each trench. Each trench will consist of 19 'Quick 4' Standard Plus lnfiltrator@ chambers for a total of 1 14 chambers and 1368 square feet of infiltrative area. There must be at least 4-feet of undisturbed soil between each trench. lnspection ports must be installed at the beginning and end of each trench. Ports may be cut to grade and placed in sprinkler boxes for access. COMPONENT SPECIFICATIONS The component manufacturers are typical of applications used by contractors and engineers in this area. CBO lnc. must approve alternative components prior to installation of the OWTS. Requests must be submitted, in writing, to our office for approval prior to installation. Component technical data sheets are available upon request. Construction must be according to the jurisdiction's adopted On-Site Wastewater Treatment System Regulations, the OWTS Permit, and this design. PERMIT APPLICATION INSTRUCTIONS An OWTS Permit Application must be submitted to Garfield County Environmental Health Department. https://www.qarfield-countv.com/environmental-health/filesqcco/sitesi16/OWTS-Application-Complete- Packet-Dec.-2019.pdf. lf the OWTS Permit Application will be submitted with a Building Permit Application, it should be submitted directly to Garfield County Building Department. All questions regarding permit submission can be directed to Garfield County Environmental Health Department, 970-945-66 14 x81 50. INSTALLATION CONTRACTOR CBO lnc. expects that the installer be experienced and qualified to perform the scope of work outlined in this design. The installer must review this design thoroughly and coordinate with our office in advance of installation. Any additional conditions in this design or county permit must be completed and documented prior to final approval of the OWTS installation. Communication between the installer and this office is expected throughout the installation. INSTALLATION OBSERVATIONS CBO lnc. must view the OWTS during construction. The OWTS observation should be performed before backfill, after placement of OWTS components. Septic tanks, distribution devices, pumps, dosing COMPONENT MANUFACTURER MODEL NO.COMMENTS Septic Tank lnfiltrator@ M-1060-2CP 1000-gallon, two- :ompartment poly septic lank Effluent Filter Orenco@ 4-inch diameter, full size Tank Risers and Lids Orenco@ Double-walled PVC Rlsers and Lids (24" diameter) Distribution Box Polylok Dlstrlbution box, rlsers, llds, and flow eoualizers (6) Chambers lnttltrator(E 'GlurcK 4', Plus Standard 114 Chambers Page 6 siphons, and other plumbing, as applicable, must also be observed. CBO lnc. should be notified 48 hours in advance to observe the installation. ln an effort to improve the accuracy of the record drawing, we request that the installer provide a sketch of the installation, including path of the sewer lines, water line installation (if applicable), septic tank location, STA location, and measurements from building cornens or another fixed objects on the property. This sketch is most easily provided on Sheet W2.0 of the OWTS Design Packet. Photographs of the installation and final cover are also requested to supplement our installation documentation. REVEGETATION REQU IREMENTS An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing characteristics (but without taproots), provides a maximum transpiration rate, and competes well with successional species. No trees or shrubs, or any vegetation requiring regular irrigation shall be placed over the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation cover. OPERATION INFORMATION AND MAINTENANCE The property owner shall be responsible for the operation and maintenance of each OWTS servicing the property. The property owner is responsible for maintaining service contracts for manufactured units, alternating STAs, and any other components needing maintenance. Geo-fabrics or plastics should not be used over the STA. No heavy equipment, machinery, or materials should be placed on the backfilled STA. Machines with tracks (not wheels) should be used during construction of the STA for better weight distribution. Livestock should not graze on the STA. Plumbing fixtures should be checked to ensure that no additionalwater is being discharged to OWTS. For example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA. lf an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned annually, or as needed. lf the OWTS consists of a pressurized pump system, we recommend the laterals be flushed annually, or as needed. The homeowner should pump the septic tank every two years, or as needed gauged by measurement of solids in the tank. Garbage disposal use should be minimized, and non-biodegradable materials should not be placed into the OWTS. Grease should not be placed in household drains. Loading from a water softener should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS. Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste only. ADDITIONAL CONSTRUCTION NOTES lf design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of freezing. The pump shall have an audible and visual alarm notification in the event of excessively high- water conditions and shall be connected to a control breaker separate from the high-water alarm breaker and from any other control system circuits. The pump system shall have a switch so the pump can be manually operated. Excavation equipment must not drive in the excavation of the STA due to the potential to compact soil. Extensions should be placed on all septic tank components to allow access to them from existing grade Backfill over the STA must be uniform and granular with no material greater than minus 3-inch. PageT LIMITS: The design is based on information submitted. lf soil conditions encountered are different from conditions described in report, CBO lnc. should be notified. AIIOWTS construction must be according to the county regulations. Requirements not specified in this report must follow applicable county regulations. The contractor should have documented and demonstrated knowledge of the requirements and regulations of the county in which they are working. Licensing of Systems Contractors may be required by county regulation. Please call with questions Sincerely, CBO lnc. {'tx',ta }vth-t*g Carla Ostberg, MPH, REHS W" l{xnq GARFIELD COUNTY BUILDING AND SANITATION DEPARTMENT t08 Elghth Street, $ulte 201 Glon$rood Sprlngs, Coloradof 81601 Fhone t970) 945;8212 Permlt Arsegsor's Parcel I'lo, This doos not conslilute a buildlng or use permil,INDIVIDUAL SEWAGE I}ISPOSAL PERMIT FROPERTY 'r /'i 'i t it 0wner's Name tt Fr6s6nl Addreis Pho System Locatio".*-**.0 q l'r .t !! ! Legal Sescriptlon ot Assossor's Farcel No. SYSTEM DESIGI'I ? rltre F,n*wvr'\*n, L*1\ -.;-----:- Septlc Tank Cepacity {gallon) : l; --' --{.;-.'- Percolation Rate (mi nules/inch} Ilequirod Absorption Area - $ee Attachsd $pecial Selback Requirements: lnspaclor - 0ther Numbsr ot Bodrooms (or olher) , ; :' ll i, Oale---- ,, ' .' ,r ' 'I FINAL SYSTEM INSPECTION AND APPROVAL {as installed) Call tor lnspeclion (24 hours notice) Before Covering lnstallation Syst€m lnslallsr.-.--.... Sgptlc Tank Cap $optic Tsnk Manulaclurer cr Trade Nnme Ssplic Tank Access wllhin 8" of surlace Ab$orption Area ..-.'.: . ,.. Absorption Area Type and/or Manufacturer or Trade Name Adsquals compliancs with Counly and StatB rsgulations/t€qulreme Dste ln$pector Olhor --*- tt t {aL RETAIN WITH NECEIPT BECORD$ AT CONSTRUCTION SITE *CONDITIONS: 1. All installation must comply wiih all r€quir€meflt5 of ths oolorado stats Board ot Hesllh lndividual $owage Dlsposal systems chapler 25. Article 10 C.R.S' 19?3' Revised 1984. ?. This psrmit is vslid only for connection to $lructur6s which have lully compliod with County zonlog and building requiromonls. Con' nection lo or use with any dwelling or slructures not approvod by lhe Building and Zoning oltic6 shall auioftallcally ba aviolalion or a raquir6mont ol the permit and cau$e for both logsl actlon and rovocalion of tho permil' 3, Any person who oon$tructs, alt6rs, or inslall$ an lndlvidual soWagc disposal syslcm in a manner which involvas6 knowing and metsrial varidtion trom ihe terms or spocilicatlon$ containod in tho appllcatidn ol permii commils a Class l, Petly Ol{onse {$500'00 tlne - I months in iail or bolh). While " APPLICANT Yellow. DEPARTMENT INDIVIDUAL SE1VAGE DISPOSAT, SYSTEM APPLICATION owNER ijutr- *,u.,r Jnqn ri ttltrC':itol{ - noo*rrl # P,Jlogl{gg}d?egd CONTRACTOR olu'tu*:t\ pERMrr REeuEsr FOR r$ Nnw INsTALLATICIN ( ) ALTERATIoN { ) RErAIR Attach separate shccts or rcport sho,,ving entire arca with rcspect to surrounrling areas, topography of area, habitable building, location of potable watcr wells, soil percolation test holes, soil profiles ir test holes (See page 4). LocATIQjloF PROPpSED FACILITY: bf t{ f i$W -St lf b lfLet /8 44!! ):l 6Xvrry*to, Near what City of Lsgal Description WASTES TYPE: orAddress Su f4 ,n1E Lul ,)A]it/t4.-- D4 DWELLTNG ( ) TRANSTENT USE La*t l-n { ) COMMERCTAT. OR rN}rJSTRrAt. t ) NON-DOMRSTIC WASTES ( ) OTHER-DESCRItsE BUILDINC OR SERVICE TYPE: ..5rar &i-E L Number ol'Bcdrooms umber of Persons "3 {)4 Carbage Grinder ( $ Automatic Washer {$) Dishwasher SAU P!-Y: (K WELL ( ) sPRlNG ( ) STREAM ORCREEK If supplied by Community Water, give name of supplier: DISTANCE TO NEAREST COMMTINITV SEWER SYSTEM:3,6 Nrtxa Was au cffort made to connect to the Cornmunity System 'l Np A site plan is required to be_.tubr-niiled that indicates the following MINIMUM distances: L.each Field to Well: 100 feet Septic Tank to Well: 50 feet Leach Field to lrigation Ditches, Stream or Wnter Course: 50 feet Septie S.ystcm (septie tank & disposal field) to Property Lines: l0 feet you.R rNpjyrpuAl SEwAGE*D_]gposat sy_sTEM paRs{rT wtLL NQT BE tssuED wrTllo_U T A SITE Pr,A"N. CRQTIND CONDITIONS: Depth to first Ground Water Table Percoat Cruund Slope_ 2 TYPE OF INDIVIDTJAL SEWAGR NISPOSAL SYSTEM PROPO$ED: ()c) SEPTTC'I'ANK ( ) AERA'I'I()NPLAN'r ( ) VAULT PzuVY ( ) C0MPOSTING TOTLET ( ) PIT pRlvY i ) INCINERATION TOILET Minutes inch in hole No. 2 Minutes r ) CHEMICAL TOILETT ) OTHER.DESCRIBE FINAL DISPOSAL BY: il ABSOR}TION TRENCH, BF,D OR PIT ff) L|NDERCRTIUNDDTSPERSAL t ) ABOYE GROITND DISPERSAL ( ) OTHER-DESCRIB WTLL EFFLUENT BE DISCH,{RCED DIRECTLY INTO WATERS OF TI-IE STATE? NIT' PERCOL-AIION 'i'EST RE$IJIT$: (Io be ccmpleted by Registered Professional Engiueer, if thc Engineer does.the Percolation Tasti totinures-t*-.-*per inch in hole No. I Minutes )r'hole No. () () () {) () () VAULT RECYCLINC, POTABI-E USE RECYCLING, OTHER USE EVAPO'I'RANSPIRATION SAND FITTER WAS'IEWATER POI.ID 3 Name, address and telephone of RPE who made soil absorption tests: Namc, address and tclcphone of RPE rcsponsible for design of the system Applicant acknowledges that the cornpleteness of the application is conditional upon such further mandatcry and additional tosts and reporls as may be required by the local heallh departrnent to be made alrd fumished by the applicant or by the lccal hcalth deparlmart for purposed of thc evaluation of the application; and the issuancc of the permit is subject to sueh terms and conditions es deemed necessary io insure compliance with rules and regulaticns madc, infonnation and repcrts subrnitted herewith and requirul to be subrnitted by the applicant ire or will be represented to be true and coruect to the best ofmy knowle<ige and belief and are designed to be relied on by the local departnrent of health in cvaluaiing the same for purposas of issuing the permit applied tbr herein. I further understand that any falsification or misrcpresentation rnay rcsult in tle dcnial of :he applicafion or rcvocation of any pcrmit grantcd based upon said application and in legal action ibr perjury as provided by law. Signed Date MAP'I'O YOUR PROPERTY! !PLEASE:)AN 3 {t 6" r'5'0{, ,5;Ir rtr)Dfuis' ;-gb RA/'4&N€ k&tt*b**yse ,1,{,AlE 4,Nr 4, Sre s41i^sfis, fu& ?t t+t oF 6 l'/V'DesignateNo*h furow 70 County Road $iote the Road Number and Narne)Rnrq tg,k Your Neighbor's l'Iame & Address Stvl i{lr&) 4\ I I Your Plot - Shape to Fit (No Scale)fl iic' f,-t I i**-- * t4a, *--+ ^y- ppa}gsx) S€FnL rXAj(* <-- Argtrirrtrf u F"a?J) dprp,X 2ed rc u:*.D t{o lilre fi,lAf(A o^i $atuunuN ,Or,Si.*r_ S"*r"well, all streams, irigation ditchs, and any water courses. Draw in your houss" septic tank & systern, detached garages, and driveway" If a change of location is neces:T.#,SiffffiJ;:flf*o drawing, before a Name & Your N Aefi {n." 7i hc&*ry r{cres.sflop\ ac clsprin6tARt d€glolirc *fFfo( .r,4ttns $en lHri cr{ L3 n) ,,ts 7a c g6D G)qPublic.nef' Garfield County, Co Account RO42343 Number Parcel Number 212532200799 Acres 10 Land SqFt O TaxArea O2O 2019 Mill Levv 6t5t7O 449 RAM LN SILT OwnerAddress KERANEN, JEREMY& GLORIA 449 RAM LANE srLT co 81652 Physical Address 2019Total Actual Value Overview Legend l-l Parcels Roads Parcel/Account Numbers Owner Name I r Lakes&Rivers - CountyBoundary Line $688,450 Last2Sales Date Price ,tto/2075 $464,000 6/!/2006 $175,000 81,652 Date gealed:5I24/2024 Last Data Uploaded: 5/24/2024 2:t8:56 AM Deve I ooed bv1f, -) Fst gt"id*r 5124124, 11:22AM Garfield County, CO qPublic.net - Garfield County, CO - Property Record Card: R042343 Summary Account Parcel Property Address Legal Descrlption Acres Land SqFt TaxArea MlllLeW Subdivblon ActualValues Assessed Year Land Actual lmprovement Actual Total Actual Assessed Values Assess€d Year Land Assessed lmprovement fusessed Total Assessed TaxHistory Bulldlng# Units BuildingType Abstract Codes / (Prop€rty Type) Archltectural Style Storles Frame Actual Year Built BasementArea Gross Living Area Total Heated SqFt Bedrooms Baths Heating Fuel HeatingType Alr Condltlonint RoofType RoofCover R042343 272532200t99 449 RAM LN, S|LT, CO 8r6s2 Section:32Township:5 Range: 91ATR lN SENENWCONT. 1O.21 AC AKA LOT4 PIFFERSUB-DIV EXEMPTION. 70.27 0 20 51.5170 Vlew Map Owner KERANEN, JEREMY & GLORIA 449 RAM LANE stLTco 81652 Land UnltType SINGLE FAM.RES.-LAND - 1112 (RESIDENTIAL PROPERTY) SquareFet 0 Buildings t t SFR SINGLE FAM.RES-IMPROVEMTS-1212 (RESIDENTIAL PROPERTY) 1-STRY/BSM I WOODFRAME 2006 2,0!6 2,0L6 2,Ot6 3 2 GAS FORCEDAIR CENTRAL RIDGE FRME PRO PANEL Tax Year Taxes Billed 2024 $170,000.00 $518,4s0.00 $588,4s0.00 2024 $11,390.00 $34,740.OO $4,6,130.q) 2023 $156,420.00 $477,030.0O $533,450.00 20.23 $10,480.00 $31,960.00 t42,440.@ 2023 $2,610.80 2022 $110,000.00 $378,74O.OO $488.7r10.00 2022 $7,650.00 $26,320.O0 $33,970,00 2022 $2,2s3.48 2021 $110,000.00 $378,740.00 $488,740.OO 2021 $7,870.00 $27,080.00 s34,9s0.00 2021 2020 $100,000.00 $339,470.00 $43eA7O,OO 2020 $7,15o.00 $24,27O.OO $31,420.00 2020 $2,132.88$2,670.72 https://qpublic.schneidercorp.com/Application.aspx?ApplD=1038&LayerlD=22381&PageTypelD=4&PagelD=9447&Q=1738926156&KeyValue=R0423... 'l13 5124124, 11:224M Click hereto viewthe tax informationfor this parcel on the Garield C Transfers qPublic.net - Garfield County, CO - Propefi Record Card: R042343 Sale Date 9/70/2015 6tU2006 8/3!2005 8t3U2005 7/70/2005 u29/2004 lu24t2002 u28/2002 a2a/2002 425/2002 s/3u2000 st3u2000 uur900 7/U7900 Receptlon Number 867838 699282 681725 687724 666955 687990 620764 594293 s9a292 598291- 568839 568837 Book - Page Sale Prlce $4640Ci0 Deed Type Warranty Deed WARRANWDEED DECLAMTION EASEMENT RESOLUTION POWEROFATTORNEY EASEMENT QUITCLAIM DEED WARRANTYDEED POWEROFATTORNEY QUITCLAIM DEED POWEROFATTORNEY Deeds Deeds 7806-777 7724-57 7724-53 76s5-225 1725-367 1433-973 1333-954 1333-952 1333-951 !205-575 1205-5L2 0457-O!O9 o22t-o249 $175,0OO $o $o $o $o $o $o $o $o $o $o $o $o Property Related Public Documents Click here to view ProDertv Rel3ted Public Documents Photos Sketches hftps://qpublic.schneidercorp.com/Application.aspx?ApplD=1038&LayerlD=22381&PageTypelD=4&PagelD=94 47&Q='1738926156&KeyValue=R0423... 213 5124124,11:22AM qPubllc.net - Garffeld County, CO - Property Record Card: R042343 ::\i:.::'..:r..aii.aL,!ii.yjr.t:l:-::i':,.llt''-ll:,;i q:':l'r'ciilrilil:::r':li::.rii,::!lrririt:ii:':: i.-': ri,ier.;;iil.r:tn:!,li::ir,:.lrtulr;::ll: :. i].-a:!':1lr:' l:::iitr';r,:::r:'-'.-'ie:i;i:::rr'-:- : ! -:,:i iili .,sii:;i;:,!l;i::",:;iit:,i-lli-liirar::!i:fr:i:illa'::;:,lfi::i:;ii.:::iiiir-i:::i:::i{iii.ri.!':lfl,ii:ifi-iit:i,'i::::.::: ;;;.:1;1. 1_;1 11';r 1::111;';i User Prlvacy Po-licv : GDPR Privacy Notice Last Data Uplss*1442o?Ll3il&5€4M {r,1:",."1 :..3,ilrii.':.1+:iL.'ri iii. {."9s$nsidtr #r https://qpubtic,schneidercorp.com/Application.aspx?ApplD=1038&LayerlD=22381&PageTypelD=4&PagelD=9447&Q=1738926'l56&KeyValuo=R0423. '. 3/3 ! ,,# 'r{ /.l SITE PLAN DRAWINGS MUST BE USED IN CONJUNCTION WITH DESIGN LETTER DATED O5I 1OI2O241',= 50' - O- w1 .0 Sheet 1 0F 4 Date: OSl1Ol2O24 Designed by: CBO Drawn by: DD Keranen Residence 449 Ram Lane Garfi eld County, Colorado Project Number: C1877 CBO lnc. 129 Cains Lane Carbondale, Colorado 81 623 Phone 970.309.5259 carla.ostberg@gmail.com gl: + EXtSTtNG SEWER prpE TO REMATN (RECOMMEND EXPLORING WITH CAMERA TO ASSURE IT IS IN GOOD CONDITION STING 1 25o-GALLON, TWO.COMPARTMENT fi Ij ,1 I SEPTIC TANK TO REMAIN 4'DIA SDR.35 SEWER LI (MrN. 1% FALL TO STA) NE TO STA :o 4'DIA SDR-35 SEWER LINE TO STA (MrN. 1% FALL TO STA)DISTRIBUTION BOX : WITH ACCESS AT GRADE ?'@.q 'QU ICK-4' CHAMBER TRENCHES. 6 TRENCHES WITH 19 CHAMBERS PER FOR A TOTAL OF 114 CHAMBERS AND 1368 SF. ':5 ,'.,,*". EXISTING STA't TO BE ABANDONED TRENCH I OOL HOUSE 4- DIA SDR-35 DISTRIBUTION LINE TO EACH TRENCH'"i (M "Yar: IN. ,I% SLOPE TO TRENCH) 4" DIA SDR-35 INSPECTION PORT AT BEGINNING AND END OF EACH TRENCH ,,4': CBO lnc. 129 Cains Lane Carbondale, Colorado 81623 Phone 970.309.5259 carla.ostberg @g mail.com Keranen Residence 449 Ram Lane Garfield County, Colorado Project Number: C1877 Date: 0511012024 Designed by: CBO Drawn by: DD w2.0 Sheet 2 0F 4 I 3: IIIIIIIIIIII II IIIIIIIIIII IIIIIIIIIIIIII IIIIII IIIIIII IIIIIIIIII INFILTRATOR END PLATE GRAVELLESS 'QUICK4' CHAMBER (4'x 3') FINISHED GRADE 4'DIA SDR.35 DISTRIBUTION LINE TO EACH TRENCH (MtN. 1olo SLOPE TO TRENCH) 24'MtN. 19 CHAMBERS PER TRENCH 4'DIA SDR-35 SEWER LINE (MlN 2% SLOPE TO TANK, MtN. 1% TO STA) 4 PIPES PLACED IN TOP PORT OF CHAMBER END PLATES SCREENED OR SAND FOR BEDDING 3'MrN. 8'MtN. DIA SDR-35 INSPECTION 4'DIA SDR-35 EFFLUENT PIPE FROM SEPTIC TANK PORT AT BEGINNING AND END OF EACH TRENCH DISTRIBUTION BOXWITH ACCESS AT GRADE BOXAND COVER BROUGHTTO GMDE CONCRETE LID FINSHED GRADE + BAFFLE OR ANGLED PIPE TO BE USED AT INLET L DIA SDR-35 SCHEDULE 40 ENCASEMENT PIPE END CAP MUST BE GLUED OR SECURED IN A WATER TIGHT FASHION WITH UNDERGROUND SEALANT INSPECTION PORT H 40 RIGID END 4 max L UNDISTURB SOIL CAP AT EACH END OF PIPE LIMIT 2'minl 4' DIA SDR-35 SEWER LINE. MUST REST ON BOTTOM OF ENGASEMENT PIPE HOLE DRILLED IN END CAP MUST ONLY BE LARGE ENOUGH TO ALLOW SEWER LINE TO FIT THROUGH EXCAVATION SCARIFY GMVELLESS 'QUICK.4' CHAMBER (4'x 3') ACHAMBER TRENCH SECTION \,7 Normru BACKFILL OUTLETS oooo CBO lnc. 129 Cains Lane Carbondale, Colorado 81623 Phone 970.309.5259 carla.ostberg @gmail.com Keranen Residence 449 Ram Lane Garfield County, Colorado Project Number: C1877 0511012024 by: CBO rawn by: DD w3.0 Sheet 3 0F 4 DESIGN 4.BEDROOM RESIDENCE 75 GPD x 2 PERSONS/BEDROOM x 3 BEDROOMS + 75 GPD (4th BEDROOM) + 1-BEDROOM ADU (150 GPD) = WASTEWATER FLOW = 675 GPD TANK: MlN. 12s0-GALLON SEPTIC TANK MA|N HOUSE (USE EX|ST|NG SEPTTC TANK) MIN. lOOO-GALLON SEPTIC TANK ADU SOIL TREATMENT AREA (STA): LONG TERM ACCEPTANCE RATE (LTAR) = 0.35 GAU SF CALCULATED STA = Q/LTAR = 675 / 0.35 = 1928 SF GRAVITY, TRENCHES = 1928 SF X 1.0 = 1928 SF CHAMBERS =1928 SFX0.7= 1350 SF 112 SF/CHAMBER= 1'I3CHAMBERS SIX GRAVELLESS CHAMBER TRENCHES 19'QUICK4'CHAMBERS IN EACH TRENCH TOTAL 114 'QUICK 4' CHAMBERS CHART SOIL PROFILE TEST PIT NO. 1 SOIL PROFILE TEST PIT NO. 2 0 SLIP-ON PVCSMALL VALVE COVER BOX OR IRRIGATION VALVE BOX AT GRADE DO NOT GLUE 1 LIGHT BROWN SILT CLAY LOAM LIGHT BROWN SILT CLAY LOAM TTACH CAP OR THREADED INSULATED COPPE TMCERWIRE FINISHED GRADE2 3 4 5 6 7 8 9 10 CLEANOUT ASSEMBLY 4' DIA S COMPACT SEWER LINEF LrJ IIJl! I IF(L uJo BASE TO SUPPORT BOX 4' PVC PIPE CUT TO FIT USE HOLE SAW TO CUT THRU TOP OF TO TANK HOUSE - END AIL NO GROUNDWATER OR BEDROCK ENCOUNTERED DURING EXCAVATION LEGEND n silt clay loam OWTS COMPONENTS AND PHYSICAL FEATURES MINIMUM REQUIRED SETBACK APPROXIMATE PROPOSED SETBACK ADU TO SEPTIC TANK 5'76', ADU SEPTIC TANKTO WELL 50'338' SEPTIC TANK TO WATER COURSE 50'N/A STA TO HOUSE 20'67' STA TO WELL 100'221' STA TO WATER COURSE 50'N/A CBO lnc. 129 Cains Lane Carbondale, Colorado 81 623 Phone 970.309.5259 carla.ostberg@gmail.com Keranen Residence 449 Ram Lane Garfield County, Colorado Project Number: C1877 Date: 051'1012024 Designed by: CBO Drawn by: DD w4.0 Sheet 4 0F 4 Legend I ugRam Ln 449 Ram Lane Google Earth O 2024 Airhus JOB. NO: 15064 DATE:6/24/15 DWG BY: SRB REV IMPROVEMENT LOCATION CERTIFICATE Lot 4, Piffer Subdiuision Exemption Map Courttg of Garfield, State of Colorado II .: I I ':' .A 449 Ram Lane 667.77' I"-[ i t- t-d# I1..rbi!IAt7rl t' t' .t ll li I l:' I I .l:l 't' I , 't"'.t. I 'o 6 PROPERTY DESCRIPTION: 91 TRACT OF LAND BEINC nB SEr/4NEr/ 4NVtl/4 OF SnCIION S2, IOIVNSI'IP 5 ffi(mf, RNoE WF,SI OF NIA 6NI P.M AND BEINC MORE PAPI'CUWY DS@ A MU OM: BF,GINNING AT NE NORETWESI @RNER OF NN XE1/4N81/4NT'1/4 OF SAID S!c.ITON 32 WIIEI]CE ND ilORDflilEs' C'i'pVER OI' SAD SEC'IO.IV 32 BEARS NORTI] 7125'56" WESI 2090,56 FtsE4 TITENCE NOR'}I a9"5758' MST 667,77 FF,AU tUptCA sotmt 01.5231'WESI 66.13 FEEX TI{ENCE ffitmt 89"56',37 WESI 667.72 FEEII TT ENCE NORT I 01"52'11" EASI 666,39 FEEITO fiIE F,INTOF B'r:TNN,J['G. AI.SO KNOWN AS ITN 4 AS SEOWN ON TI'E PIFFER SUBDMSIo.N WEUMON UAP REEORDED SEFjEMBER 7,2OO5 AS RDCEP''ON NO, 6A172A SURWYOR'S CERTIFICATE: I SCOTI R MCW HEREBY CEEN,|y TTIAT THIS IMPrcVEMENT IT'CATON CERITFICATE WAS PREPARAD IDX TSEE BEINV NAT TT IS NOTA LAND S[,N/EY PT,AT OR IMPROWWNT SI]RWY PLAT, AND TTTAT N E NOT 10 M REUED UPON FOR TITE ESIIBUSHMENT OF FNCE, BUDNO, OR ONER FUTI]RE IMPrcWMEITT '.TNES. I ilJFETR CEFNFY ITTATTHE ulIuTv @NNrcITONS ARE EN''RELY WmtN mE BOUNDARIES OF nIE P,ARCEL, E TCEFI AS SHOWN, MATTHM ARE NO ENCrcACHUEN1E IJPON ND DF.WM PREId.SAAEY IMPROI,EMEI|IIS ON AIyAD.tO]LCp&EtfrSES, EI(CEPrAS INDICATE,D, AND TTI TmERE IS NO APPARENT EVIDENCE OR SIGIV O,.ffiBSruEITTCROSSNVC OR AURDAIVIIfC M PRT OF SAD PARCEL, E)rcEPIAS NOIE,D. .&MMOIiWEALET rmE @MpAIly OFCARngn @UNTY, mC. .oRDF,R NO, 15060541 'EFFECIIW DAIE: JUNE 16, 2015 scrofr R BLACI(ARD L.S. 38E42 DAN kb{d1/16tuffi323-l/4'Utuqp -not{ sun'+ ":-' * 'a-*Aa 12? E. 'TH\\STRTETRTFLE q,o\\8t6so 970-625- 7711/l/\t3$l IMPROVEMENT LOCATIO N CERTIFICATE Lot 4, Pilfer Subdiuision bcemption Map Countu ofGarfield, State ofColomdo 30.@'lg.,UftydhttuBpeht Lat+ 10.21 AG t wdawdufrlt',EF-.-Ft ls.oq UUty & lda& (@dl 73.6' ,A j 15,37 b J*'* kj6l/wd -.:_'-' ;"rraOI l NofICE: ffiRDINc fo cObRADo LAY YOD tust CoPAENCE ANY &AL ACfION BASAD UHN AM DEFM IN IBIS SURVEr VITEIN TEREE lEAN AtrER YOU F]RSf DISCOVERED SUCE DEFM. IN NO EVEM, TAY AN AC?IO{ BASED UHN Ifr DEFET IN TEIS SURYEY EE COY{ErcED IORE |EAN TEN YEAN TEE CERTIF]CA?ION SMTN EEMON. s49.56 3?"V 667 72 449 Ram Lane of7 7