HomeMy WebLinkAboutComCheck Certificate ReportCoMcfieck Software Version 4. 1, 5. 5 Hnvelope Compliance Certificate Project lnformation Energy Code: Project Title: Location: Climate Zone: Project Type: Vertical Glazing / Wall Area Construciion Site: Donegan Storm King Rd Glenwood Springs, CO 81601 Additional Efficiency Package{s} Credits: 1.0 Required 1.0 Proposed Reduced Lighting Power, 1.0 credit Building Area 2018 |ECC Glenwood Springs Flex OfficeMarehouse Glenwood Springs, Colorado 5b New Construction 25o/o OwnerlAgent: Dan Kunau Citadel Self Storage 502 572 7BB0 dkunau@andovermgt.com Floor Area Designer/Contractor: Sally Kaufman Kaufman Design Group, inc. 9415 E Harry St #405 Wichita, KS 67207 3r.6-618-0448 sally@kdginc.co 1-Office : Nonresidential 20350 Envelope Assemblies Assembly Gross Area or Perimeter Cavity R-Value Cont. R-Value Proposed U-Factor Budget U- Factor1"1 Roof 1: Other Metal Building Rool [Bldg, Use 1 - Office] (b) Floor 1: Slab-On-Grade:Unheated, [Bldg. Use 1 - Office] (d] NORTH Exterior Wall 3: Steel-Frame d, 24" a.c., fBldg. Use 1 - Officel Window 3: Melal Frame wiih Thermal Break:Fixed, Perf. Specs.: Produci lD Guardian Sunguard SN 68 on grey, SHGC 0.24, VT 0.60, lBldg. Use 1 - Officel (c) Door 1: Glass {> 50% glazing):Metal Frame, Entrance Door. Perf. Specs.: Product lD Guardian Sunguard SN68 on grey, SHGC 0.24, PF 0.56, VT 0.60, [Bldg. Use 1 - Office] (c) EAST Exterior Wall 1 : Steel-Framed,24" o.c., [Bldg. Use 'l - Office] Window '1 : Metal Frame with Thermal Break:Fixed, Perf. Specs-: Product lD Guardian Sunguard SN68 on grey tint, SHGC 0.25, VT 0.60, [8ldg. Use 1 - Office] (c) SOUTH Exterior Wall 4: Wood-Framed,24" o.c., [Bldg. Use 1 - Office] Door 2: Oiher Door, Garage door 14% glazing, [Bldg. Use 1 - Office] Door 3: lnsulated Metal, Swinging, [Bldg. Use 1 - Office] WEST Exterior Wall 2: Steel-Framed,24" o.c., lBldg. Use 1 - Office] 700 20350 1976 1125 164 BB4 226 32S9 816 168 884 0.037 0.730 0,054 o.245 o.245 0-054 o.245 0.046 0.f30 0.210 0-o54 0.035 0.540 0.064 0.3B0 4,770 0.064 0.380 0.064 0.310 0.370 0.064 13,5 9-0 13.5 13.5 13.5 9.0 9.0 s.0 Project Title; Glenwood Springs Flex Office/Warehouse Report date: 05118/24 Data filename: S:\Projects\AndoverMgmt\GlenwoodSpringsCO\FlexC\comcheck\Glenwood*Springs*Flex-Office- Page L of 10 arehouse (l-).cxl Assembly Gross Area Cavity or R-Value Perimeter Cont. R-Value Proposed U-Factor Budget U- Factorpt Window 2: Metal Frame with Thermal Break:Fixed, Perf. Specs-: Producl lD Guardian Sunguard SN68 on grey, SHGC 0-25, VT 0.60, [Bldg. Use 1 - Office] (e) 226 o-245 0.380 (a) Budget U-faclors are used for software baseline calculations ONLY, and are not code requirements- (b)'Other'components require supporting documentation for proposed U-factors. (c) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation (d) Slab-On-Grade proposed and budget U-factors shown in table are F-factors- Envelope Gompliance Statement Compliance Sfafemenf; The proposed envelope design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed envetope systems have been designed to meet the 20LB IECC requirements in COMcheck Version 4.1.5.5 and to comply with any applicable mandatory requirements listed in the lnspection Checklist. Sally Kaufman -architect Sa//"/- /<a/r4.rrar/.5-18-2424 Envelope PA$$E$: Oasign {5% bettar than cade Name - Title Signaturyf U Llate Project Title: Glenwood Springs Flex Office/Warehouse Report dater 05/18/24 Data filename: 5:\Projects\AndoverMgmt\GlenwoodSpringsCO\FlexC\comcheck\Glenwood*Springs*Flex*Office- Page 2 of 10 arehouse (L).cxl s0s8ss CoMcheck Software Version 4.1.5.5 lnspection Checklist Energy Code: 2OLB IECC Requirements: 0.0% were addressed directly in the COMcheck software Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate tabfe, a reference to that table is provided. Add itional Comments/Assu mptionsl Project Title: Glenwood Springs Flex OfficeAffarehouse Report date: 05118/24 Data filename: 5:\Projects\AndoverMgmt\GlenwoodSpringsCO\FlexC\comcheck\Glenwood_Springs*Flex*Office_ Page 3 of 10 arehouse (L).cxl Section # & Req.lD Flan Review Gomplies?Comments/Assumptions , Plans and/or specifications provide all lnComplies ; , information with which compliance :nDoes Not can be determined for the building -r,-! ^L:envetope and documeni';;;;;"'' ,INot observable i ,exceptions to the standard are UNot Applicable : 'claimed^ ': c103.2 lPRl]1 percent of the gross above-grade wall area. iln nil Complies Does Not Not Observable Not Applicable c402.4.t lPRLoll jThe vertical fenestration area <- 30 : ,The skylight area <E 3 percent of the nComplies : gross roof area. [Does Not . INot Observable . ;nNot Applicable ; c4a2.4.1 lPRLU1 : service, manufacturing. non- i refrigerated warehouse, retail store, i distributionlsorti ng area, itransportation, or workshop, the .following requirements apply: iai the :daylight zone under skylights is >- :half the floor area; (b) the skylight c402.4.2 IPR].41r area to daylight zone is >= 3 percent with a skylight W >= 0.40; or a minimum skylight effective aperture>- 1 percent. innoes Not lnNot observable iilNot Applicable ln enclosed spaces > 2,500 ft2 directly under a roof with ceiling heights >1,5 ft. and used as an office, lobby, atrium. concourse, corridor, storage, gymnasiumlexercise center, convention center. automotive i Plans, specifications, and/or , calculations provide all information:with which compliance can be :determined for the additional energy c nc406 lPR9l1 ilNot observable ilNot Applicableiefficie Complies Does Not 1 hlm (Tier 1)2 Medium lmpact (Tier 2)3 Low lmpact (Tier 3) Section # & Req.lD Foottng / Foundation lnspection Complies?Comments/Assumptions ilComplies ; lilooes tttot j jnruot observable i :INot Applicable i c303.2 lFo4l2 Slab edge insulation installed per manufacturer's instructions. Exterior insulation protected against damage, sunlight, moisture, wind, landscaping and equipment maintenance activities. nn nil Complies Does Not Not Observable Not Applicable c303.2.1 lFO6l1 lnstalled slab-on-grade insulation type 'and R-value consistent with insulation specifications reported in plans and , C0Mcheck reports. see lhe Envelape Assemblies table far values. Does Not re5cr.05 IFO3]2 jlNot observable iilruot epplicable ,Slab edge insulation depth/length. 'Slab insulation extending away from 'building is covered by pavement or , >* l^0 inches of soil. iflDoes Not lnNot observable See fhe Envelope Assemblies table for values. lFoTl? Applicable Additional Comments/Assumptionsr Project Title: Glenwood Springs Flex OfficeMarehouse Report date: 05/18/24 Data filename: 5:\Projects\AndoverMgmt\GlenwoodSpringsCO\FlexC\comcheck\Glenwood_Springs-Flex*Office- Page 4 of 10 arehouse (1).cxl 1 High lm ct {Tier l")2 Medium lmpact (Tier 2)3 Low lmpact (Tier 3) Section # & Req.lD Framlng / Rough-ln lnspection Complies?Comme nts/Ass urn pticns :ilComplies lilDoes Llot lilNot observable lilNot npplicable c303.1.3 lFR1212 Fenestration products rated in accordance with NFRC. Fenestration products are certified as ;ilComplies to performance labels or certificates lilDoes NotProvided' [Not observable :ilNot Applicable c303.r..3 IFR13]1 Vertical fenestration SHGC value. :lComplies :see the Envelape Assemblies table for values. nDoes Not []Not Observable :tlNot Applicable ; c402.4.3 lFRr"0l1 c442.4.3, c402,4.3. 4 lFRBll lnstalled vertical fenestration U-tactor :[Complies and SHGC consistent with label :lnoes Not specifications and as reported in plans ;nruot Observableand coMcheck reports' :nNot Appricabte see the Envelape Assemblies table for values. Vestibules are installed on all building .entrances. Doors have self-closingidevices. ;ilNot :iltrtot plies Not Observable licable c402.5.7 lFR1713 Additiona I Commants/Assumptions: L High lmpact (Tier 1)2 Medium lm {Tier 2 3 Low lmpact (Tier 3) Project Title: Data filename Glenwood Springs Flex Office/Warehouse Report date: 05118/24 S:\Projects\AndoverMgmt\GlenwoodSpringsCO\FlexC\comcheck\Glenwood_Springs_Flex_Office_ Page 5 of 10 arehouse (1).cxl Section # & Rao.lD Mechanical Rough-ln lnspection €omplies?Comments/Assumptlons c402.5.5, c403.2.4. 3 lME313 .Stair and elevator shaft vents have motorized dampers that automatically rclose. Refernece section C4A3.7.7 tor ioperational details. IComplies lfDoes Not ilNot Observable INot Applicable Outdoor air and exhaust systems have ;motorized dampers that automaticaf ly:shut when not in use and meet , maximum leakage rates, Check gravity dampers where allowed.:Reference section language for ;operational details. :tr in c403.7.7 lME58l3 lINot Observable :fltrtot Applicable Compties Does Not Additional Comments/Assumptions: Project Title: Glenwood Springs Flex OfficeAA/arehouse Report date: O5/18/24 Data filename: S:\Projects\AndoverMgmt\GlenwoodSpringsCO\FlexC\comcheck\Glenwood-Springs*Flex*Office- Page 6 of 10 arehouse (L).cxl 1 (Tier L)2 Medium I tTier 2)3 (Tier 3)Low Complies?Comments/Assumptions Section # & Req.lD Rough-ln Electrical lnspection , Low-vottage dry-type distribution electric transformers meet the ' minimum efficiency requirements of Table C405.6. lnComplies I :ilDoes wot j i[Not observable i inNot Applicable i c405.6 lEL26l' Electric motors meet the minimum efficiency requirements of Tables C405.7(1) throush C4A5.7 (41. Efficiency verified through certification under an approved certification program or the equipment efficiency ratings shall be provided by motor : manufacturer (where certification Not programs do not ex c405.7 tEL2il2 flNot Observable ilNot Applicable Escalators and moving walks comply ,with ASME A1,7.1/CSA 844 and have automatic controls configured to reduce speed to the minimum permitted speed in accordance with ASME Al"7,L/CsA 844 or applicable local code when not conveying Applicable te5c405.8.2, c405.8.2. 1 lEL2812 Does Not : Not Observable I Total voltage drop across the combination of feeders and branch circuits <- 5o/o. :nDoes Not ,ilNot Observable 9 lEL29l' ,lNot ble Additional CommentslAssumptions: 2 Medium I {Tier 2)3 Low lm (Tier 3)L ht (Tier 1) Project Title: Data filename Glenwood Springs Flex OlficeAlVarehouse Report date: 05/18/24 S:\Projects\AndoverMgmt\GlenwoodSpringsCO\FlexC\comcheck\Glenwood_Springs*Flex*office* Page 7 of 10 arehouse {1).cxl Section # & Reo.lD lnsulation lnspecticn Complles?Comments/Assumptions Roof insulation installed per manufacturer's instructions. Blown or poured loose-fill insulation is installed only where the roof slope is <-3 in !2. ilComplies ilDoes Not nNot Observable nNot Applicable c303.1 ItN3]r lnsulation installed on a suspended ceiling having ceiling tiles is not being specifi ed for roor/ceiling assemblies. Continuous insulation board installed in 2 or more layers with edge joints Complies Does Not Not Observable Not Applicable offset between c402.2.1 IrN2ol1 Building envelope insulation is labeted with R-value or insulation certificate 'providing R-value and other relevant data. lnDoes trlot inNot observable .nruot npplicable I ltNlol2 les es Not lAbove-grade wall insulation installed per manufacturer's instructions. ;nNot Observable: blejnruot c303.2 ltNTll Exterior insulation is protected from damage with a protective material. Verification for exposed foundation insulation may need to occur during ilComplies [fDoes Not INot Observable lNot Applicable lrNr.4l2 2.7 Foundation I tnstalled above-grade wall insulation type and R-value consistent with insulation specifications reported In plans and COMcheck reports. ,ilDoes Not lnruot observable inNot Appllcable see the Envelope Assemblies table for values.Compliesc105 ilN611 lnstalled floor insulation type and R- value consistent with insulation specifications reported in plans and COMcheck reports. :ilDoes tt'tot jENot observable :see the Envelape Assemblies table for values.re5 icablelilwot c402.2.3 ltN812 components, designed for heat lnDoes t1lot transfer from the panel surfaces to the:-i,^! ^Loccupanrs or indoor rpui"'"lu - * ' ",gl"l observable insulated with a minimum of R-3.5. UNot Applicabte Radiant panels and associated e5c402.2,6 IrNr8]3 |nstalled roof insulation type and R- value consistent with insulation specifications reported in plans and :ilooes trtot : :iltuot Observable j iilruot nppticaule I :See the Envelope Assefiblies table for values. Framinoccur du on. cr-05 ilN211 ,COMcheck reports. For some ceiling lsystems, verification may need to :All sources of air leakage in the ,building thermal envelope are sealed, ; caulked. gesketed, weather stripped ilComplies nDoes Not nNot Observabte ilNot Applicableor wrapped permeable with tntm tzem atr c402.5.1 t_ ltN1l1 Additiona I CommentslAssumptionsl Project Title; Glenwood Springs FIex Office/Warehouse Report date: 05/l-B/24 Data filename: 5:\Projects\AndoverMgmt\GlenwoodSpringsCO\FlexC\comcheck\Glenwood^Springs*Flex*Office_ Page B of L0 arehouse {1).cxl 1 hr {Tier L}2 Medium lmpact (Tier 2)3 Low lm (Tier 3) Complies?Comments/Assumptions Sectlon # & Req.lD Final l*spection :Building envelope contains a icontinuous air barrier that has been Itested and deemed to limit air leakage l<- 0.40 cfmlftZ.lnNot itrruot c402.5 ln55P Observable l Applicable l inComplies iilnoes tr,tot lWeatherseals installed on all loading :nComplies I rdock cargo door openings and provide inDoes Not : direct contact along the top and sides -^,^, ^, : ;; il;;;il;;;'i"il";5";;;: " - " iE il:l :iffffii:. i 6c402,5. IFr37]1 I Suilding operations and maintenance ldocuments will be provided to the :owner. Documents will cover : manufacturers' information, ; specifications, programmi ng iprocedures and means of illustrating Ito owner how building, equipment and lsystems are intended to be installed, : maintained, and operated. ilComplies nDoes Not nNot 0bservable ilNot Applicable c408.1.1 IFr57]1 Additional Comments/Assumptions r 1 (Tier L)h 2 Medium I {Tier 2}3 {Tier 3)Low Project Title; Data filename Glenwood Springs Flex OfficeAAlarehouse Report date: 05118124 S:\Projects\AndoverMgmt\GlenwoodSpringsCO\FlexC\comcheck\Glenwood_Springs_Flex*Office- Page 9 of L0 arehouse (1).cxl Project Title: Data filename Glenwood Springs Flex OfficeAArarehouse Report date: 05/18/24 5r\Projects\AndoverMgmt\GlenwoodSpringsCO\FlexC\comcheck\Glenwood_Springs_Flex*Office, Page 10 of 10 arehouse {1).cxl CoMcheck Software Version C0McheckWeb Mechanical Compllance Gertificate Project lnformation Energy Code: Project Title: Location: Climate Zone: Project Type: 202L IECC Glenwood Springs Flex Office/Warehouse Glenwood Springs, Colorado 5b New C0nstruction Construction Site: Owner/Agent: Designer/Contractor: Donegan Storm King Rd Dan Kunau Glenwood Springs, Colorado 81601 Citadel Self Storage : l3 "t"lt.t"t"tttve rm s t. c o m Additional Efficiency Package(s) Credits: 10.0 Required 0.0 Proposed Mechanical Systems List QuantitySystem Type & Description 2 Split System Furnace (Single Zone): Heating: 1 each - Central Furnace, Gas, Capacity = 58 kBtu/h Proposed Efficiency - 96.00% Et, Required Efficiency: 80.00 % Et or 80o/o AFUE Cooling: L each - Split System, Capacity - 3l- kBtu/h, Air-Cooled Condenser, Unknown Economizer Froposed Efficiency - l-6.00 SEER2, Required Efficiency - L3.40 SEER2 Proposed Part Load Efficiency = 0.00 , Required Part Load Efficiency - 0.00 Fan System: FAN SYSTEM 1- -- Compliance (Motor nameplate HP and fan efficiency method) : Passes Fans: FAN 1 Supply. Constant Volume, 1125 CFM, 0.8 motor nameplate hp, 0.00 fan energy index , fan exception: Single fan < L HP or < 0.89 kW 6 Mini-Splits (Unknown): VRF Condensing Unit, Air Cooled Heat Pump Heating Mode: Capacity = 1t k8tu/h, Proposed Efficiency = l-0.00 HSPF, Required Efficiency - 7.70 HSPF Cooling Mode: Capacity * tZ kBtu/h, Proposed Efficiency - 21.50 SEER, Required Efficiency - 13.00 SEER Proposed Part Load Efficiency - 0.00 , Required Part Load Efficiency - 0.00 Fan System: None B RTU (Single Zone)l Heating: 1 each - Central Furnace,6as. Capacity: 53 kBtu/h Proposed Efficiency - 81.00% Et, Required Efficiency: 80.00 % Et or B0% AFUE Coolingl 1 each - Single Package DX Unit, Capacity - 34 kBtu/h, Air-Cooled Condenser, Air Economizer Proposed Efficiency = l-6.00 SEER2, Required Efficiency = 13.40 SEER2 Proposed Part Load Efficiency - 0.00 , Required Part Load Efficiency - 0.00 Fan System: FAN SYSTEM 2 -- Compliance (Brake HP and fan efficiency method) : Passes Fans: FAN 2 Supply, Constant Volume, 1500 CFM, 0.8 motor nameplate hp, 0.4 design brake hp (O.a max. BHP), 0.00 fan energy index , fan exception: Single fan < L HP or < 0.Bg kW 6 Duct Heater (Single Zone): Heating: L each - Duct Furnace, Electric, Capacity - 14 kBtu/h No minimum efficiency requirement applies L Wall Heater (Unknown W PerimeterSystem): Heating: l each - Unit Heater, Electric, Capacity - 5 kBtu/h No minimum efficiency requirement applies Project Title: Glenwood Springs Flex OfficeMarehouse Data filename: Report datet OAA724 Page L of 10 Quartlty$ystEm Type & lestrlption Fan System: FAN SYSTEM 3 * Compliance {Motor nameplate llP and fan efficiency method} : Passes Fans: FAN 3 Supply, Ccnstant Volume, 100 CfM, 0.1 nrotor nameplate hp, 0,00 fan energy index , fan exception: Single fan < 1 HP or < 0.89 kW Water Heateri Etectrlc lnstantanaou$ Water Heater, Capacity: 1 gallons No xinirnurn efficlency requirement applies Mechanlcal Compliarce St*t6m6nt Compliance Sisfemenf The prcpcsed rnechanical design represented in this docilmtni is consistent with the building pla*s, specificatlons, and other calculations submltted with this permit application" Tl* proposed mechanical sy$tems have been designed to meet th€ 20?1 lfCC requirements in COMc$eck and to comply with any applicable mandatory requlrements listed ln the lnspection Checklisr, U*,ro' $ */t*r* - fieoL ffi$k**t l{ame - Title s Project Titler Glenwood Springs Flex Officefi#arehouse Data filename: Report date: OSt{7124 Page 2 of 10 COMch eck Software Version C0McheckWeb lnspection Checklist Energy Code: 2O2L IECC Requirements: 0.0% were addressed directly in the COMcheck software Text in the "CommentslAssumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Add itional Comments/Assu mptions: Section # & Req.lD Plan Review Complies?Comments/Assumptions Plans, specifications, andlor calculations provide all information with which compliance can be determined for the mechanical and service water heating systems and document where exceptions to the starrdard are claimed. Load calculations per acceptable engineering standards and handbooks. Hot water system sized per manufacturer's sizing guide. c103.2 lPR2ll incomplies lilDoes Not lnruot observable ;.ruot applicable : Plans, specifications, and/or :calculations provide all information iwith which compliance can be idetermined for the additional energy i efficiency package options. tnComplies ,nnoes wot :[f Not Observabte :nNot Applicable c406 lPR9lr I Hish (Tier L)2 Medium lmpact (Tier 2 3 Low lm iTier 3) Project Title: Glenwood Springs Flex OfficeA/Varehouse Data filename: Report da|'.e: A5lA724 Page 3 of 10 Complles?CommentslAse umptions $ecllon # & ReE.lD Footing I Foundatlon lnspecUon , ,protection systems have sensors and C403.13.3 :controls configured to limit service for IFO9]3 , pavement temperature above 50F and 'outdoor temperature above 4OF" ilDoes trtot iilNot observable iilruot applicable 3.13.2 Snoflice melting system and freeze ilComplies Addltional Comments/Assumptions: 2 Medium {Tier 2i 3 Low lm (Tier 31(Tier U Project Title: Glenwood Springs Flex OfficeMarehouse Data filename: Report datel 05/07/24 Page 4 of 10 Complies?Ccmments/Assurrptions Sectlon # & Req.lD Flurnbing Rough-ln lnspectlon Heated water supply piping conforms :to pipe length and volume :requirements, Refer to section details. iilnoes ttlot j iilNot observable j ilNot applicable ; L, c444.5.7 lPL613 Additional Comments/Assumptionsr 2 Medium I {Tier 2i 3 {Tier 3LowLHigh lmpact {Tier 3- Project Title: Glenwood Springs Flex OfficeAffarehouse Data filename: Report date: 05/07/24 Page 5 of L0 Section # & Req.lD Mechanical Rough-tn lnspection Complies? C4A2.2.6 Thermally ineffective panel surfaces of lME41l3 sensible heating panels have insulation >- R-3.5. Comments/Assumptions ilDoes wot l ;ilNot Observable, ble : , HVAC fan systems at design :tlComplies 'conditions do not exceed allowable ,nOoes Not'fan system motor nameplate hp o, fun lNot ObservabtesYstem bhP' :frrrroi nppri."rrr" ;see the Mechanical Sysferns /lsf for values.c403,8.1 lME6513 nDoes Not ilNot Observable ilNot Applicable Fans have a fan energy index (FEl) >= ,nCompfiesc403,8.3 IME117i2 1.00. Variable volume fans will have an FEI >- 0.95. Fans have a fan energy index (FEl) >- I 1.00. Variable volume fans will have I an FEI >= 0.95. :: ilNot Applicable lNot Observable, c403.8.3 lME117l' Complies Does Not Motors for fans that are not less than 1/12 hp and less than L hp are electronically commutated motors or have a minimum motor efficiency of 70 percent. These motors have the :nooes Not .nNot Observable ;ilNot Applicable means to motor s c403.8.4 lME142l' system with fans > 1/4 hp are designed to vary the indoor fan airflow as a function of load and comply with Not rvaObse ble,ilNot tca bleApp:nNot ofrements tsrh section,detai ed c403,8.6 lME14312 Each DX cooling system > 65 kBtu and chiller water/evaporative cooling Large diameter fans where installed shall be tested and labeled in accordance with AMCA 230.nNot Observable ilNot Applicable : c403.9 lMEL44l2 illcomplies :nDoes Not :lComplies .see the Mechanical Systems list for values. :ilDoes Not ; i[luot observable: lnNot npplicable : HVAC equipment efliciency verifiedc403.3 lME55l2 , provided in accordance with tnternational Mechanical Code Chapter 4. Mechanical ventilation has :capability to reduce outdoor air supply lMcto minimum ilNot Applicable Not Observable Natural or mechanical ventilation is r4. ilDoes Not Compliesc403.2.2 lME59l1 Demand controlventilation provided IComplies :for spaces >500 ftz and >15 :nDoes Not Ipeople/1000 ft2 occupant density and -.,-. ^".served by systems *ith';l;;;"' """ ,EIo:observable:,u.ono-ii*., auto modulating outside LJltot Applicable : 'air damper control, or design airflow : >3,000 cfm. : c403.7.1 lME59l1 Enclosed parking garage ventilation :[JComplies , has automatic contamlnant delection i[Does Not and capacity to stase ":S""0::ff.itu. FNot observabtefans to 5oo/o ar less of dr rLJNot Appricabre I c443.7.7 lME11513 2 Medium I (Tier 2)3 (Tier 3)Low1Hih lmpact (Tier L) Project Title: Glenwood Springs Flex Office/Warehouse Data fllename: Report date: 0UA7l24 Page 6 of 10 Complies? HVAC systems serving guestrooms in 'Group R-L buildings with > 50 :guestrooms: Each guestroom is provided with controls that automatically manage temperature setpoint and ventilation (see sections C403.7.6.1 and C403.7.6.2). Com ments/Assum ptionsMechanical Rough*ln lnspectlon &,tD nComplies nDoes Not lNot Observable [1Not Applicable Section c403.7.6 lME14113 C403.7 .4 . Exhaust air energy recovery on IME57]1 ,systems meeting Table C403.7.4(1) ;and C403.7.4(2). :nooes Not : iilNot observable. licable Kitchen exhaust systems comply with , replacement air and conditioned supply air limitations, and satisfy hood 'rating requirements and maximum exhaust rate criteria. mplies Not c403.7.5 IME1]-613 :ilNot observable :iltrtot npplicable ,bypass valve or lower leakage positive closure dampers. Open-circuit tower within lreat pump loop have automatic valve to bypass all heat pump water flow around the tower. Open- or closed-circuit cooling towers used in conjunction with a separate heat exchanger have heat loss by shutting down the circulation pump on the cooling tower loop. Open- or closed circuit cooling towers have a separate heat exchanger to isolate the cooling tower from the heat pump loop, and heat loss is controlled by shutting down the circulation pump on the cooli tower loo c403.4.3 3.2 lME12113 nComplies ilDoes Not ilNot Observable lNot Applicable Closed-circuit cooling tower within heat pump loop have either automatic Heating for vestibules and air curtains with integral heating include automatic controls that shut off the heating system when outdoor air temperatures > 45F. Vestibule heating and cooling systems controlled by a thermostat in the vestibule with heating setpoint <= llDoes trtot l ;illtot Observable, :[JNot Applicable . mplies 60F and cool nt >* 80F c403.4.1. 4 lME63l, ilComplies ilDoes Not nruot npplicable : lINot Observable c403.3.3 IME35]1 .Hot gas bypass limited to: <-240 .kBtulh - 5Ao/o >240 kBtulh - 25% c408.2.2 1 lME53l3 Air outleis and zone terminal devices :lComplies ; have means for air balancing. :lDoes Not :ilNot Observable l !Not Applicable c403.11.3 .1,, c403.11.3 .2 IME123]3 Refrigerated display cases, walk-in coolers or walk-in freezers served by remote compressors and remote condensers not located in a condensing unit, have fan-powered condensers that comply with 5ections C403.11.3.1 and refrigeration compressor systems that comply with c403.11-.3.2.. :ilComplies : llDoes Not ] :ilNot Observable : lNot Applicable : c403.11.3 Add itiona I Com ments/Assumptions : 1 High lm ct (Tier l")2 Medium lmpact (Tier 2)3 Low lmpact (Tier 3) Project Title: Glenwood Springs Flex Office/Warehouse Data filename: Report date: 05/07/24 Page 7 of 1"0 Section & Req.lD Rough-ln Electrical lnspection Complies?Com mentslAssurnptions Low-voltage dry-type distribution electric transformers meet the minimum efficiency requirements of Table C405.6. :ilComplies l :lDoes Not l ,nNot Observable: :INot Applicable : c405.7 lEL26l? Electric motors meet the minimum ' efficiency requirements of Tables C405.7(1") through C40s.7(4). Efficiency verified through certification under an approved certification prog.am or the equipment efficiency ratings shall be provided by motor manufacturer (where certiflcation programs do not exist). ilComplies nDoes Not nNot Observable nNot Applicable c405.8 lEL2712 Escalators and moving walks comply with ASME A17.1/CSA B44 and have automatic controls configured to reduce speed to the minimum permitted speed in accordance with ASME 417.1/CSA 844 or applicable local code when not conveying passengers. e5 Not c405.9.1, c405.9.2 IEL2B],,nNot observable: :nNot Applicable : Total voltage drop across the combination of feeders and branch clrcuits <= 3o/". lDoes Not l ilNot Observable; nNot Applicable : mpliesc405.10 lEL29l2 At least 9}o/o af dwelling unit permanently installed lighting shall have lamp efficacy >= 65 lm/W or luminaires with efficacy >= 45 lmAlV ;[lNot Applicable :0r with C405.2.4 or C405.3 c405.1.1 lEL3o12 :ilNot Observable lComplies lDoes Not 51o/o of 15i20 amp receptacles installed in enclosed offices, conference rooms, copy rooms, break rooms, classrooms and workstations and > 25o/o of branch circuit feeders for modular furniture will have automatic receptacle control in accordance with C405. L1.1-. tes :nDoes Not ,nNot observable ;nruot npplicable c405. lEL31 ,11, .11-.1 12 Additiona I Comments/Assu mptions: Medium (Tier 2)3LHigh lmpact (Tier 1i 2 Low I (Tier 3) Project Title: Glenwood Springs Flex Office/Warehouse Data filename: Report date: OS|ATP4 Page 8 of 10 Sectian # & Req.lD Final lnspection Cnmplies?Comments/Assumptions c303.3, c408.2.5. 3 lFr813 Furnished O&M manuals for HVAC systems within 90 days of system : acceptance. incomplies inDoes Not .INot Observable :ilNot Applicable C403;3.L rHVAC systems and equipment [F127]3 capacity does not exceed calculated loads. nDoes Not ilNot Observable nNot Applicable ;nComplies Heating and cooling to each zone is .controlled by a thermostat control. Minimum one humidity control device per installed , humidification/dehumidification system. lnCompliesc403.4.1 IFt47 j3 ilDoes Not ' ilNot Observable, Not Applicable : c403.4.L 1 lFt4213 Heat pump controls prevent :IComplies supplemental electric resistance heat ,lDoes Not i from coming on when not needed. iiltrtot Observable. [JNot Applicable c403.4.r. 2 lFt38l3 lnComplies : lnDoes trtot l ;nruot Observable; :ilruot npplicable : Thermostatic controls have a 5 oF deadband. C403.4.L. Temperature controls have setpoint3 overlap restrictions. IFt20]3 :ilNot Applicable :nNot Observable; iEach zone equipped with setback controls using automatic time clock or programmable control system. ,ilComplies : jlDoes wot : :nNot Observable, tilruot epplicable : c403.4.2 lFt39l3 c403.4.2, 1, c443.4.2. 2 lFr40l3 Automatic Controls: Setback to 55"F lf]Complies {heat) and 85"F (cool}; 7-day clock, 2- iIooes Not l::t.:-..uOuntoverride,Lo-hour :ilruotObservableoacKup. :iltrtot Applicable c403.4.2 3 IFr4].13 ,nComplies ;nooes Not iflNot observable ;nruot nppllcable Systems include optimum start controls. Heat traps installed on supply and discharge piping of non-circulating systems. :ilComplies : :ilDoes Not . t[ttot Observable; :nNot Applicable ' c404.3 lFn 113 documents will be provided to the owner. Documents will cover manufacturers' information, specifications, programming procedures and means of illustrating maintained, and rated. iBuilding operations and maintenancec408.1.1 IFr57]1 lilDoes trlot j lilruot observable . :INot Applicable , :to owner how building, equipment and :systems are intended to be installed, Medium lm ct (Tier 2)3 (Tier 3)LowLHigh lmpact (Tier 1)2 Project Title: Glenwood Sp.ings Flex OfficeA/Varehouse Data filename: Report date: 05/07/24 Page 9 of 10 Section # & Req.lD Final lnspection Complies?Comments/Ass urnptions Commissioning plan developed by registered design professional or approved agency. :nComplias : inDoes tuot I lflNot observable l ;[JNot Applicable : c408.2.1 lFt2811 c408.2.3 t_ lFt31l1 ;HVAC equipment, systems and ; system-to-system relationships have I been tested to ensure proper ;operation. ilComplies , inDoes wot : igNot observable, jilNot Applicable : c408.2.3. 2 lFtloll iHVAC and service water heating ;control systems have been tested to : ensure proper operation, calibration land adjustment of controls. es jfltrtot ble Not :flNot observable . : Preliminary commissioning report ,completed and certified by registered :design professional or approved , agency. ;nNot applicable pliesc408.2.4 IFr29]1 nDoes Not I []Not observabte i Furnished HVAC as-built drawings submitted within 90 days of system acceptance, ;lComplies :IDoes Not : jnruot observable . ;Eruot applicable , c408.2.5 IFr7]3 c408.2.5 t- lFl43lr ,An air and/or hydronic system lnCompties , ,balancing report is provided for HVAC ;nDoes Not I.s'stems' Eil:r:iff::1i".: c408.2.5. 2 lFt30ll :Final commissioning report due to , building owner within 90 days of :receipt of certificate of occupancy ; :nDoes Not ,nNot Observable :[lNot Applicable e5 Additional Comments/Assumptions: 2 Medium (Tier 2)3 Low I (Tier 3)1 High lmpact ti Project Title: Glenwood Springs Flex Office/Warehouse Data fllename: Report date; A5107124 Page 10 of L0 COMch eck Software Version CoMchecklllleb lnterior Lighting Gompliance Certificate Project lnformation Energy Code: Project Title: Project Type: Construction Site: Donegan Storm King Rd Glenwood Springs, Colorado 81601 Additional Efficiency Package(s) Credits: 10.0 Required 0.0 Proposed Allowed lnterior tighting Power A Area Category 2021_ tEcc Glenwood Springs Flex OfficelWarehouse New Construction Owner/Agent: Dan Kunau Citadel Self Storage 5A2 5]2 7B8A dkunau@andovermgt.com Designer/Contractor: B Floor Area (ftz) c Allowed Watts / ft2 D Allowed Watts L-Office 20350 0.64 13024 Total Allowed Watts - 13024 Proposed lnterior Lighting Power A Flxture lD : Description / Lamp / Wattage Per Lamp / Ballast B Lamps/ Fixture CDE # of Fixture (C X D) Fixtura Watt. 1-Office LED: A2: 2X2 FLAT PANEL: LED Panel 40W: LED: E1: 4' STRIP: LED Linear 22W: l" 1 94 93 40 30 3760 2794 Total Proposed Watts - 6550 rLi ng Com ance Statement Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been designed to meet the 2021 IECC requirements in CoMcheck Version COMcheckWeb and to comply with any applicable mandatory requirements listed in the lnspection Checklist. Warren R. Law, Electrical Engineer 5-7-2024 lnt€rlor bettsr than codeD*sign Name - Title Signature Date Project Title: Glenwood Springs Flex OfficeMarehouse Data filename: Report dai.e: A5ft7124 Page 1 of 6 C0Mcheck Software Version C0McheckUlleb Exterior Lighting Gompliance Gertificate Project lnformation Energy Coder Project Title: Project Type: Exterior Lighting Zone Construction Site: Donegan Storm King Rd Glenwood Springs. Colorado 8L601 Allowed Exterior Lighting Power A ArealSurface Category 202L IECC Glenwood Springs Flex Office/Warehouse New Construction 2 {Neighborhood business district (LZz',} Owner/Agent: Dan Kunau Citadel Self Storage 502 572 7B8A dkunau@andovermgt.com B Quantity DE Tradable Allowed WattsWattage (B X C) Designer/Contractor: c Allowed Watts / kwav < 10 feer 692 ft of 346 Total Tradable Watts (a) = 346 Total Allowed Watts - 346 Total Allowed Supplementaf Watts {b} - 400 {a) Wattage tradeoffs are only allowed between tradable areaslsurfaces, (b) A supplemental allowance equal to 400 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces. 0.5 Yes Proposed Exterior tighting Power A Fixture lD : Description / Lamp / Wattage Per Lamp / Ballast B Lampsl Fixture CDE # of Fixture (C x Dl Fixture Watt. Walkway < l0 feet wide (692 ft of walkway length):-Tradable Wattage LED: N1: WALL PACK: LED A Lamp 25Wr Total Tradable Proposed Watts - 540 Exterior Lighting Compliance Statement Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been designed to meet the 2021" IECC requirements in CoMcheck Version COMcheckWeb and to comply with any applicable mandatory requirements listed in the lnspection Checklist. Warren R. Law, Electrical Engineer e"fu"*-A#- 5-7-2024 Name - Title Signature Date 1 30 1B 540 Project Title: Glenwood Springs Flex Office/Warehouse Data filename: Report datu: A5lA7R4 Page 2 ol 6 C0Mcheck Software Version C0McheckWeb lnspection Checklist Energy Code: 2OZL IECC Requirements: 0.07o were addressed directly in the COMcheck software Text in the "CommentslAssumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Addltional Comments/Assumptions Section # & Req.lD Plan Review Complies?CommsntslAssumptions and electrical systems and equipment i c103.2 IPR4]1 nComplies nDoes Not nNot Observable nNot Applicable :lightlng power calculations, wattage of , bulbs and ballasts, transformers and :control devices. and document where exceptions to the standard are claimed. lnformation provided should include interior : Plans, specifications, and/or icalculations provide all information :with which compliance can be ;determined for the interior lighting i Plans, specifications, and/or calculations provide all information rwith which compliance can be rdetermined for the exterior lighting :and electrical systems and equipment and document where exceptions to the standard are claimed. lnformation provided should include exterior lighting power calculations, wattage of bulbs and ballasts, transformers and control devices. Not c103.2 IPRBll ;lNot Observable :Ittot npplicable : Plans, specifications, and/or icalculations provide all information ;with which compliance can be idetermined for the additional energy flDoes Not : nNot Observable, ilNot Applicabte : Compliesc406 lPR9l1 I effi L High lm (Tier L)2 Medium lmpact (Tier 2)3 Low lmpact {Tier 3) Glenwood Springs FIex OfficeMarehouseProject Title: Data filename Report datet OS|Q7l24 Page 3 of 6 gectaon # & Req.lD Rough-ln Electrical lnspectlon Complies?Comments/llssumptions Spaces required to have light- reduction controls have a manual control that allows the occupant to reduce the connected lighting load in a reasonably uniform illumination pattern >- 50 percent. nComplies IDoes Not INot Observable Not Applicable c405.2.3 l- lEL22l1 ;Occupancy sensors installed in classrooms/lecture/training rooms, : conference/meeting/multipurpose rooms, copylprint rooms, , lounges/breakrooms, enclosed offices, .open plan office areas, restrooms, :storage rooms. locker rooms, ,corridors, warehouse storage areas. :and other spaces <- 300 sqft that are , enclosed by floor-to-ceiling height ipartitions. Reference section language :C4Q5.2.1.2 for control function in : warehouses and section C405.2.1-.3 e5 ;nNot :ilNot for o n lan office :nooes ttot c405.2.1, c405.2.r^ 1 lELr.Bll Observable : Applicable ; :controlled with occupant sensors that , automatically reduce lighting power 'by 5Aolo or more within 20 minutes of when the areas are unoccupied. The ;occupant sensors control lighting in leach aisleway independently and do ; not control lighting beyond the ,aisleway being controlled by the :sensor. Lights not turned off by :occupant sensors is done so by time- .switch. Compliesc405.2.1.' 2 lEL19l1 . Occupancy sensors control function in : warehouses: ln warehouses, the lighting in aisleways and open areas is ilDoes Not : ilNot Observable. ilNot Applicable : :Occupant sensor control function in :open plan office areas: Occupant :sensor controls in open office spaces :>- 300 sq.ft. have controls L) ,configured so that general lighting can :be controlled separately in control izones with floor areas <- 600 sq.ft. ;within the space. 2) general lighting in each zone permitted to turn on upon ;occupancy in control zone, 3) , automatically turn off general lighting :in all control zones within 20 minutes ,after all occupants have left the ,space, 4) are configured so that igeneral lighting power in each control ;zone is reduced by >- B0olo of the full :zone general lighting power within 20 :minutes of all occupants leaving that :control zone. c405.2.1. 3 lEL2oll ;looes Not : :flNot Observable, ;ilNot Applicabfe : Each area not served by occupancy sensors iper C405.2.1-.1) have time- switch controls and functions detailed in sections C405.2.2.1. :ilnoes lrtot I lf]wot Observab,e , inruot applicable : 1 lEL2112 e5 2.2. c405.2.2, 1 High lmpact (Tier 1)2 Medium lm (Tier 2)3 Low lmpact {Tier 3) Project Title: Glenwood 5prings Flex Office/Warehouse Data filename: Report date: O5lO7l24 Page 4 at 6 &-tD Sectaon # c405.2.4, c405.2.4. T, c405.2.4. 2 lEL23l2 Daylight zones provided with individual controls that control the lights independent of general area lighting. See code section C4A5.2.3 Daylight-responsive controls for applicable spaces, C405.2.3,1- Daylight responsive control function and section C4O5.2.3.2 Sidelit zone. Comments/Assumptions ilComplies Rough-ln Electrical lnspection Complies? i[f Does Not ilNot Observable. nNot Applicable : ,Additional interior lighting power ,allowed for special functions per the :approved lighting plans and is : automatically controlled and lilooes Not ; ;nftot Observable 'iilNot Applicable :.se parated from general li c405.2.5 IEL2711 .Automatic lighting controls for exterior ,lighting installed. Controls will be .daylight controlled, set based on business operation time-of-day, or Not reduce connected tiqhting > 30o/o. c405.2.7 lEL2Bjl nNot Observable: :lNot Applicable , Low-voltage dry-type distribution electric transformers meet the minimum efficiency requirements of Table C405.6. ilcomplies i nDoes Not : XNot Observable I ilNot Applicable c405.7 IEL2612 Electric motors meet the minimum efficiency requirements of Tables C405.7(1) throush C4A5.7 (4',. Efficiency verified through certification under an approved certification program or the equipment efficiency ratings shall be provided by motor manufacturer (where certification proqrams do not exist). !n n. Complies Does Not Not Observable Not Applicable c405.8 [EL27J2 C405.9.1, Escalators and moving walks comply C405.9.2 with ASME A17.1/CSA 844 and have [EL2B]'? automatic controls configured to reduce speed to the minimum permitted speed in accordance with ASME 4L7.1/CSA 844 or applicable local code when not conveying passengers. :ilDoes ttot l :iltrtot Observable , ;[JNot Applicable C405.11, 50% of 15/20 amp receptacles C405.11.L installed in enclosed offices, IEL3].1'z conference rooms, copy rooms, break rooms, classrooms and workstations and > 25% of branch circuit feeders for modular furniture will have auton"latic receptacle control in accordance with C405. Ll.. 1. or with C405.2.4 or C405.3. ilComplies mplies c405.1"0 lEL29l2 Total voltage drop across the combination of feeders and branch circuits <= Sa/o. c405.1.1- IEL30]2 At least 90% of dwelling unit permanently installed lighting shall have lamp efficacy >= 65 lm/W or luminaires with efficacy >* 45 lm/W :nnoes Not r UNot Observable :[ruot npplicable I .flOoes trtot . ,ilNot Observable, riltlot Applicable I ilDoes Not : INot Observable, ilNot npplicable : Add itional Com ments/Assumptions: L High lmpact {Tier L}2 Mediunr er 2)3 Low lm ct {Tler 3) Project Title: Glenwood Springs Flex Office/Warehouse Data filename: Report date'. A5fi7124 Page 5 of 6 Complies?CornmentslAssumptions Section # & Res.lD Final lnspection Furnished O&M instructions for 'systems and equipment to the building owner or designated representative.lFt17l3 :XNot Observabfe: ilNot Applicable j c303.3, c408.2.5. Complies Does Not rExterior lighting power is consistent .with what is shown on the approved i tignting plans, demonstrating i proposed watts are less than or equal ito allowed watts. nComplies lDoes Not nNot Observable See fhe Exteriar Lighting fixture schedule for values.c405.5.1 IFt19]1 :nr'lot applicable : procedures and to owner how b , equipment and to be installed, esButdirationsmaandintenancengope WI be rovt toded theocumednts Noes otinDp Docuowner ments il cover bservableo,nNotnufamacturersation,inform ecabl:ilwot Appliificatispecons,programmrng eam ofns ustrating U tdi ng as intendedresystem rated.ntainedmai nd c408.1.1 lFr5711 Furnished as-built drawings for ilComplies : electric power systems within 90 days :flnoes Not of system acceptance. [Not observable [ruot applicable c408.2.5 lFl16l3 Lighting systems have been tested to lilComplies : lensure proper calibration, adjustment, :nDoes Not lprogramming,andoperation. j[,]NotObservable inruot npplicabte i c408.3 IFI33]1 Additional Comments/Assumptions: 2 Medium lm act (Tier 2)3 Low lm {Tier 3}L High lm ct {Tier 1) Pro.iect Title: Glenwood Springs Flex Office/Warehouse Data filename: Report datet OSIAT/24 Page 6 of 6