Loading...
HomeMy WebLinkAboutPlan Review CommentsGarfield County Building Department 108 8rh Street, Suite 401 Glenwood Springs, CO 81601 970-945-8212 www. g a rfi e ld-co u nty. com IBC 2015 Plans Analyst Plan Review Gomments List Date: Wednesday, 30 Mar 2022 Project Description: BP NO: BLCO-7361 Electronics Building & 6' Fence around 100'x100'Site \A/ith Solar panels Project Location: 1058 CR 215 Parachute Peak Site - SESW of Section 15 Township 55 Range 97W Parcel# 21 3715300009 Owner: Union Telephone Company PO Box 160 Mountain View \A/Y 82939 Ph. 307.747.4827 aaredondo@unionwireless.com jhaws@unionwireless.com Architect: Designer: Owner Engineer: Matt Fisher PO Box 160 Mountain View \iAlY 82939 307.747.4900 mfi sher@unionwireless. com Construction by: Justin Haws c/0 Union Telephone PO Box 160 Mountain View \A/Y 82939 Ph. 307.747.7054 Code Study by: Cadfish LLC 970.618.0230 cell cadcode@hotmail.com email The comments listed below are required to be resolved for the plans to verify compliance with the 2015 lnternational Building Code (lBC) by lCC. The purpose of this review is to provide for minimum protection of life, limb, health, proper$, environment and for the safety and welfare of the consumer and general public as regulated by the 2015 lnternational Building Code and other applicable Codes, including but not limited to the lnternational Building Code 2015 the International Fire Code 2015, lnternational Fuel Gas Code 2015, the lnternational Mechanical Code 2015, lnternational Plumbing Code 2015, the lnternational Energy Conservation Code 2015, the current Edition of the National Electric Code, and, other applicable Codes and regulations as adopted and amended by the Town of Basalt. The Focus of this review and correction list is the life safety provisions of the 2015 lnternational Building Code. Other referenced codes are only spot checked or reviewed by others. The owner and contractor are responsible for compliance with all applicable csdes. Electrical plans and installations are reviewed and approved by the State of Colorado. These corrections shall be resolved prior to issuance of the Building Permit for the project. Any and all deviations from the original plans and specifications approved by the Building Department shall be submitted to the Building Department for approval prior to installation The approval of plans and specifications does not permit the violation of any section of the lnternational Building Code(s) and other applicable Codes adopted and amended by the Town of Basalt, and, any applicable federal, state or local regulations. Refer to the Approved Plans, Code Analysis & Gonditions of Permit, other Garfield Gounty departments reviewing the plans and other adopted codes for additional code requirements not noted on this list. lf plans are revised, changes should be clouded to facilitate review and minimize expense to the applicant. The designer shall also submit a written response to each item on this list and specify the location on the plans of the applicable plan change. Submittal of a separate addendum sheet(s) with all revisions may also be acceptable. 1 : :Allsheets to be stamped and signed by a design professional registered in this state, Colorado. The Building Structural plans are stamped by an Engineer from Kansas, a stamp by Colorado engineer is required. MEP plans shall be stamped by an Engineer licensed in the state of Colorado, Anchor Details on Architectural plans should be stamped by an engineer or architect licensed in the State of Colorado. (107.1) 2 : : lnclude a complete to scale site plan per Sec. 107 .2.5 showing all structures, dimensions between structures, distances to property lines and public ways, etc and adjacent properties. Show what structures are new and what are existing and new on the site plan. Are the ground solar structures new or existing, etc? (107.2.5) 3 : : Speciff the Occupancy Classification and Type of Construction.4 : : Specify fuel source of mechanical equipment. Propane? Provide stamped fuel gas and electrical plans that include specifying compliance with adopted Garfield County Building Codes. Specify compliance of mechanical plans with adopted Garfield County Building lnternational Mechanical Code. Any plumbing installed?5 : : The wall and ceiling finish material in this area must comply with Class requirements of 803.11 & Table 803.11 . Specify Class and verify and specifo compliance with required Class.6 : : At least 60 percent but not less than one entrance shall comply with accessibility requirements. (1105.1) General note will be OK.7 : : Provide a landing on both sides of door. Note: The step & size requirements. (1010.1.5) I : : The exit (door) from the Generator room does not appear to provide the minimum required width. (1005.3) 9 : : Emergency lighting shall be provided per Sec. 1008, 1008.3, 1008.3.3 (Generator Rooms) 10 : : All glazing in hazardous locations is required to be of safety glazing material. (2406J & 2406.4). General Note OK. 11 : : ls there water and sewer on site. Clariff. Specifi7. 12 : : lnclude a copy of the foundation and soils investigation for the site to be built on or provide a note on the plans requiring open hole site inspection, verification, and approval from a Colorado licensed soils engineer prior to pouring concrete. (1803.2) 13 : : ls Building heated? lf so speciff, lMC, IFGC compliance. Specify. IECC Compliance, specifo. 14 : :Any Hazardous Materials on site? 15 : : Provide ventilation per IBC and lMC, specifo and provide details as necessary on stamped MEP plans. Provide. 16 : :Amend building permit application to describe all new construction, eg. tower, ground solar, propane tank? etc. 17 : : Speclfy lf any loam plastlcs are to be used ln the proJect? 2603.4 18 : : Battery storage, any, how much? See 509. Separation requirements. 19 : : Ownership -Assessor's site says owner Chevron Corporation ... not Union Telephone Company. Provide letter of authorization from Ghevron to apply for the permit and do the work. ARTICLE 3. ZONING 20 : : Allowed Uses Table 3-403. Solar Small - P. Solar Large - Limited lmpact Review - Required? Specify the Solar System size to classify the solar system as noted. See #22 below. lf Telecommunication facility tower 100' or less in height - q OK, if not, see item#24 below. ARTICLE VII, STANDARDS 21 : :7-205 DRAINAGE & EROSION: Provide site drainage plan or notes specifying compliance with the soils report, Sec. 1804 lBC, and Garfield County Land Use code requirements. A stamped site and drainage plans may be required if a Land Use Change Permit is required. See solar system requirements below. 22 : : Provide a lighting plan or provide note specifying lighting will be compliant wit Sec. 7-304 ^trL^ ^^t^tl n^..-&, I ^-l I t^^ n^i^Ul Llltr \Jclll|EIU re(JUIll,y LallU \,rDE tvUUtr 23 : :7-1101 SOLAR ENERGY SYSTEMS - Size of systems not specified Provide Solar System Classification - Accessory - less than 15 kw, Small - 15-500 kW Large - 500 kw? Specify. lf the solar system is a medium or large system a Land Use Change Permit is required. Verify requirements with the Planning Department. At a minimum, provide a note on the plans stating the Solar system will comply with Division 11 of the Garfield County Land Use Code, the IBC 2015, and the most current edition of the NEC as adopted by Garfield County and the State of Colorado. When a solar system is installed on a flat roof it shall be raised no more than 6' above the roof. Speciry on plans. 24 : :7-IIO2TELECOMMUNICATIONS FACILITES. Verify the Tower is under 100 feet. lf so, provide a general note on the plans stating the Telecommunications Facility and Tower, etc. shall comply with the lBC2O15, FAA requirements, and all local, state, and federal regulations. lf over Tower is over100 feet Land Use Permit and a Building Permit and Plan Review for the Towerwill be required. Edits from Garco Mtq Work Session 4.1.22 (Colleen Wirth, Sheryl Bower, Glen Hartman,Brooke Winschell, Bruce Stolbach) NOTE: Strike through text below was deleted as approved at this work session meeting on the project. Garfield County Building Department 108 8rh Street, Suite 401 Glenwood Springs, CO 81601 970-945-8212 www. garfield-cou nty. com IBC 2015 Plans Analyst Plan Review Comments List Date: Wednesday, 30 Mar 2022 Project Description: BP NO: BLCO-7361 Electronics Building & 6' Fence around 100'x100' Site \A/ith Solar panels Project Location: 1058 CR 215 Parachute Peak Site - SESW of Section 15 Township 55 Range 97W Parcel# 213715300009 Owner: Union Telephone Company PO Box 160 Mountain View \Aff 82939 Pn.307.747.4827 aaredondo@unionwireless.com jhaws@unionwireless.com Architect: Designer: Owner Engineer: Matt Fisher PO Box 160 Mountain View \ /Y 82939 307.747.49OO mfisher@u nionwireless.com Construction by: Justin Haws c/0 Union Telephone PO Box 160 Mountain View \Aff 82939 Ph. 307.747.7054 Code Study by: Cadfish LLC 970.618.0230 cell cadcode@hotmail.com email The comments listed below are required to be resolved for the plans to verifo compliance with the 2015 lnternational Building Code (lBC) by lCC. The purpose of this review is to provide for minimum protection of life, limb, health, property, environment and for the safety and welfare of the consumer and general public as regulated by the 2015 lnternational Building Code and other applicable Codes, including but not limited to the lnternational Building Code 2015 the lnternational Fire Code 2015, lnternational FuelGas Code 20'15, the lnternational Mechanical Code 2015, lnternational Plumbing Code 2015, the lnternational Energy Conservation Code 2015, the current Edition of the National Electric Code, and, other applicable Codes and regulations as adopted and amended by the Town of Basalt. The Focus of this review and correction list is the life safety provisions of the 2015 lnternational Building Code. Other referenced codes are only spot checked or reviewed by others. The owner and contractor are responsible for compliance with all applicable codes. Electrical plans and installations are reviewed and approved by the State of Colorado. These corrections shall be resolved prior to issuance of the Building Permit for the project. Any and all deviations from the original plans and specifications approved by the Building Department shall be submitted to the Building Department for approval prior to installation The approval of plans and specifications does not permit the violation of any section of the lnternational Building Code(s) and other applicable Codes adopted and amended by the Town of Basalt, and, any aOOfpgble federal, state or local regulations. Refer to the Approved Plans, Code Analysis & Conditions of Permit, other Garfield Gounty departments reviewing the plans and other adopted codes for additional code requirements not noted on this list. lf plans are revised, cfitges should be clouded to facilitate review and minimize expense to the applicant. The designer shall also submit a written response to each item on this list and specify the location on the plans of the applicable plan change. Submittal of a separate addendum sheet(s) with all revisions may also be acceptable. 1 : :Allsheets to be stamped and signed by a design professional registered in this state, Colorado. The Building Structural plans are stamped by an Engineer from Kansas, a stamp by Colorado engineer is required. MEP plans shall be stamped by an Engineer licensed in the state of Colorado, Anchor Details on Architectural plans should be stamped by an engineer or architect licensed in the State of Colorado. (107.1)2 : : lnclude a complete to scale site plan per (Sec. 107.2.5 showing all structures, dimensions between structures, distances to property lines and public ways, etc and adjacent properties. Show what structures are new and what are existing and new on the site plan. Are the ground solar structures new or existing, etc? (107.2.5)3 : : Drawings on A1.1 not labeled, no scale. All drawings provided shall be to scale. Most are not. Provide revised plans.4 : : Only 2 elevatiens previded, Previde al{ L5 : : Specify the Occupancy Classification and Type of Construction.6 : : Specify fuel source of mechanical equipment. Propane? Provide stamped fuel gas and electrical plans that include specifying compliance with adopted Garfield Coung Building Codes. Specify compliance of mechanical plans with adopted Garfield County Building lnternational Mechanical Code. Any plumbing installed?7 : : The wall and ceiling finish material in this area must comply with Class requirements of 803.11 & Table 803.11 . Specify Class and veriff and specify compliance with required Class.8 : : At least 60 percent but not less than one entrance shall comply with accessibility requirements. (1 1 05. 1 )9 : : Provide a landing on both sides of door. Note: The step & size requirements. (1010.1.5) 10 : : The exit (door) from the Generator room does not appear to provide the minimum required width. (1005.3) 11 : : Emergency lighting shall be provided perSec. 1008, 1008.3, 1008.3.3 (Generator Rooms) 12 : : All glazing in hazardous locations is required to be of safety glazing material. (2406.1 & 2406.4) 13 : : ls there water and sewer on site, provide bathrooms per-l-able 2902.1. Verify with Garfield County. 14 : : lnclude a copy of the foundation and soils investigation for the site to be built on or provide a note on the plans requiring open hole site inspecition, verification, and approval from a Colorado licensed soils engineer. (1803.2) 15 : : ls Building heated? lf so IECC Compliance? 16 : :Any Hazardous Materials? 17 : :Ventilation, stamped mechanical plans. Provide.18" @Amendbuildingpermitapplicationtodescribeallnewconstruction,eg towere ground solar, propane tank? etc. 19 : : Driveway / aeeess permit required? Veriff with Planning Department, 20 : : Any foam plastics to be used in the project? 2603.4 21 : : Battery storage, any, how much? See 509. Separation requirements. 22 : :THIS DOOR TO REMAIN UNLOCKED WHEN THIS SPACE lS OCCUPIED Sign ... Provide. 23 : : Ownership -Assessor's site says owner Chevron Corporation ... not Union Telephone ^^----.. h--.-:l- t-4-- -a -..1L--:--a:--- t,--,-- Ar-\/uiltPany. rtuvr(Ie relrer (,r aurnglrzauon Trom unevron Io appty Tor Ine permtl anq oo Inw worK. ARTICLE 3. ZONING plan-isl4€O0 sq, ft, Hew sheuld this be applied, VeriF.with Planning Department,ffiovcrage in Rt€S ie 15% (Table 3-2+1). Site plan not to scalerunable te ealeulate-Applieant sheuld previde let eeverage ealeCatiens en the plans, Dees the 15% apply 01, Site plan net te seale, Cimensiene Planning Department, Aeeess read net shewn, Adjaeent uses net shewn en eaeh side ef pr€Berylin€= 29 : :Allowed Uses Table 3-403. Solar Small - P. Solar Large - Limited lmpact Review - Required? Telecommunication facility 1100' or less in height - P. Verify with Planning Department. ARTICLE VII. STANDARDS 30 : : 7 105, A, Water Supply / System Required? 7, 105, B, Waste water System Required? 31 : : PROTECTION OF \|TIATERBODIES 7 203, Water bedies net shewn en site plan, Ne 32 : :7-205 DRAINAGE & EROSION: Provide site drainage plan or notes specifiTing compliance with the soils report, Sec. 1804 lBC, and Garfield County Land Use code requirements. A stamped site and drainage plans may be required if a Land Use Change Permit is required. See solar system requirements below. NOTE: ltems 33-37 OK a unless Land Use Change Permit is required. lf so these and other requirements will be reviewed by Planning Dept. at time of that application. 34 : : 7 205 ENVIRONMENTAT QUAIITY ??? Verify with Planning department, 36 : : 7 302 OFF STREET PARKING & tOADING Nene shewn, ??? Verify with Planning Bepa*men+ 37 : ; 7 405 ROAD IMPACT FEES Required fer this prejeet? Verify with Planning Department, 38 : :7-1101 SOLAR ENERGY SYSTEMS - Size of systems not spec'd, some roof (small) some free standing (existing?) Provide Solar System Classification - Accessory - less than 15 kW Small - 15-500 kw, Large - 500 kw? Specify. lf the solar system is a medium or large system a Land Use Change Permit is required. Verify requirements with the Planning Department. At a mimimum, provide a note the Solar system will comply with Div. 11 of the Garfield County land use Code, the IBC 2015, and the most current edition of the NEC as adpoted by Garfield County and the State of Colorado. 1. Roof Mounted Solar System: b. When flat roof raised no more than 6'above.. e, 3 feet setbaek frem reef edge; net previded, Previde, ? 2, Greund Meunted Selar System requirements: d. System limited te eembined 1Skw rated nameplate DC eapaeity te inelude equivalent kw 39 : :7-1102 TELECOMMUNICATIONS FACILITES. Verify the Tower is under 100 feet. lf so, provide a general note on the plans stating the TELECOMMUNICATIONS FACILITEY and Tower, etc. shallcomply with the 1BC2015, FAA requirements, and all local, state, federal, regulations. lf over Tower is over 100 feet Land Use Permi and a Building permit for the Towere will be required. ls Tewer existing? Engineering eemplianee? Design materials? tighting & Signage? Nen lnterferenee? G, Federal Aviatien Ageney Ferm? H Teleeemmunieatiens Aet & FAA eemplianee? Verify with Planning department, 40 : : Snew barriers fer selar panels 1503' 1503,7' 1507,1 as amended by Garee, ?? 41 ; : ls a fenee permit and buildingrand zening eede review ef the fenee required fer a 6' fenee