Powerwall 2 AC lnstallation Manual
with Backup Gateway 2
BUILDING PLANNING
R326.4 Means of egress. The means of egress for habitable
attics shall comply with the applicablc provisions of Section
R311. ,/
sEcTloN R327
SWMMING POOLS, SPAS AND HOT TUBS
R327.1 General. The design and construction of pools and
spas shall comply withthe International Swimming Pool and
Spa Code.
sEcTloN R328
ENERGY STORAGE SYSTEMS
R32S.1 General. Energt storqge systems (ESS/ shall
comply with the provisions of this section,
Exceptions:
l. ESS listed and labeled in accordance with UL
9540 and marked "For use in residential dwelling
units" where installed in accordance with the
manufacturer's instructions and NFPA 70,
2. ESS less than 1 kWh (3.6 megajoules).
R328.2 Equipment listings. Energt storage systems (ESS)
shall be listed and lqbeled in accordance with UL 9540,
Exception: Where approved, repurposed uniisted baftety
systems from electric vehicles are allowed to be installed
outdoors or in detached sheds located not less than 5 feet
(1524 mm) from exterior walts, proper,ty lines and public
ways,
R328.3 lnstallation. ESS shall be installed in accordance
with the manufacturer's instructions and their listing,
R328.3.1 Spacing. Individual units shall be separated
from each other by not less than 3 f'eet (914 mm) except
where smaller separation distances are documented to be
adequate based on large-scale fire testing complying with
Section 1207,1.5 of lhe International Fire Code.
R328.4 Locations. ESS shall be installed only in the follow-
ing locations:
l. Detached garages and detached accessory structures.
2, Attached garages separated from the dwelling unit
living space in accordance with Section P.3O2.6.
3. Outdoors or on the exterior side of exterior walls
located not less than 3 feet (914 mm) ftom doors and
windows directly entering the dwelling unit.
4. Enclosed utility closets, basements, storage or utility
spaces within dwelling units with finished or
noncombustible walls and ceilings. Walls and ceil-
ings of unfinished wood-framed construction shall be
provided with not less than 5/u-inch (15.9 mm) Type
X gypsum wallboard.
ESS shall not be installed in sleeping rooms, or closets or
spaces opening directly into sleeping rooms.
R32E.5 Energy ratings. Individual ESS units shall have a
maximum rating of 20 kWh. The aggregate rating of the ESS
shall not exceed;
1. 40 kWh within utilify closets, basements and storage
or utility spaces.
2. 80 kwh in attached or detached garages and detached
accessory structures.
3. 80 kwh on exterior walls.
4, 80 kwh outdoors on the ground.
ESS installations exceeding the pgrmitted individual or
aggregate ratings shall be installed in accordance with
Section 1207 ofthe International Fire Code.
R328,6 Electrical installation. ESS shall be installed in
accordance with NFPA 70. Inverters shall be listed attd
labeled in accordance with UL 1741 or provided as paft of
the UL 9540 listing. Systems connected to the utility grid
shall use invefiers listedfor utility interaction,
R328.7 Fire detection. Rooms and areas within dwelling
units, basements and attached garages in which ESS are
installed shall be protected by smoke alarms in accordance
with Section R314, A heat detector, listed and intercon-
nected to the smoke alarms, shall be installed in locations
wirhin dwelling units and attached garages where stnoke
alarms carulot be installed based on their listing.
R328.8 Protection from impact. ESS installed in a location
subject to vehicle damage shall be protected by approved
barriers.
-utr
t
R328.9 Ventilation. Indoor installations of ESS that produce I
hydrogen or other flammable gases during charging shall be S.
g:il,t*i"tfr.mechanical ventitation in accordance *i,n I .S )
R32E.l0 Electric vehicle use. The temporary use of an
owner or occupant's electric-powered vehicle to power a
dwelling unit while parked in an attached or detached garage
or outdoors shall comply with the vehicle manufacturer's
instructions and NFPA 70.
R328.11 Documentation and labeling. The following
information shall be provided:
1. A copy of the manufacturer's installation, operation,
maintenance and decommissioning instructions shali
be provided to tbe owner or placed in a conspicuous
location near the ESS equipment.
2. A label on the installed system containing the contact
infonnation for the qualified maintenance and
service providers.
sEcTtoN R329
STATIONARY ENGINE G ENERATORS
R329.1 General. Stationary ongine generators shallbe listed
and labeled in accordance with UL 2200 and shall comply
with this section, The connection of stationary engine gener-
ators to the premise wiring system shall be by means of a
I is t e d tt ansf er sw itch.
:$
f,N
3-66 2021 INTERNATIONAL RESIDENTIAL CODEO
COKNESFaqVD FNCE --h/ar /ne*a &nColleen Wirth
From:
Sent:
To:
Subject:
Attachments:
Edward Andersen < andersenedward3T@yahoo.com >
Tuesday, July 16,2024 1:24 PM
Colleen Wirth
Fwd: [EXTERNAL] Fw: BLRE-06-24-8707 - Anderson Utility Room UNDER REVIEW
POWERWALL 2 SPEC SHEET.pdf; 2023 Powerwall installation manual.pdf
Sent from my iPhone
Begin forwarded message:
From : J ere my Brown <j. brown@su nse nsesota r. co m>
Date: Juty 15,2024 at 09:46:08 MDT
To: Matt Petaisto <M.Petaisto@sunsensesotar.coffi), andersenedward3T@yahoo.com
Subject: RE: [EXTERNAL] Fw: BLRE-06-24-8707 - Anderson Utility Room UNDER
REVIEW
Edward -
Answer to 24: 40.5 kwh. Each PowerwaLL2 unit has 13.5 kwh capacity and we want to instatt (3)
Attached is the cut sheet and instatt manuaI for the Powerwa[[ 2, as we[[ as a nameptate sticker
FYl,NFPAS55CHl5timitstheinstalledESSkwhratingto40. wehavereceivedpermissionfrom
fire marshats in the Roaring Fork Vatty to instatt the 40.5, so we would atso tike to ask permission for
this from your fire marshat/buitding officiat.
Thank you for your time
Jeremy Brown
ESS/Power+ Program Project Manager
Sunsense Sotar
1629 Dotores Way Suite E
Carbondate CO 81623
wt
^Av..s
!.1 nsense-s g1al. co rn
Cetl,: 208-610-5050
From: Matt Petaisto <M. Peta isto@sunsensesola r.com>
Sent: Monday, July 15,2024 9:35 AM
To: Jeremy Brown <j. brown@sunsensesolar,com>
Subject: FW: [EXTERNAL] Fw: BLRE-06-24-87O7 - Anderson Utility Room UNDER REVIEW
$
N
.$
-\\s
1
Thank you,
Matthew Petaisto
Sotar and Battery Consultant
Sunsense Sotar
1629 Dotores Way, Carbondate
http ://www. s u n se n seso [a r. co m/
C:970-665-8981
From: Edward Andersen <andersenedward3T@vahoo.com>
Sent: Saturday, July 13,2024 6:40 AM
To: Matt Petaisto < M.Petaisto@sunsensesolar.com>
Subject: [EXTERNAL] Fw: BLRE-06-24-8707 - Anderson Utility Room UNDER REVIEW
IEXTERNAL EMAIL] Do not ctick tinks or attachments unless you recognize the sender and know the content is safe
Hello Matt, I'm working on my utility room permit. Can you help me with questions 2a and 2c. Thanks.
---- Foruvarded Message ---
From : Col leen Wirth < cwirth@garfield-cou nty.con>
I o: andersenedward3 /(o)yahoo.com < andersenedward3 /(cDyahoo.com>
Cc: John Plano .iplano@garfield-c
Sent: Tuesday, July 9,2024 at024811 PM MDT
Subject: FW: BLRE-06-24-8707 - Anderson Utility Room UNDER REVIEW
Hello Ed,
John Plano, CBO requested I resend this email for your viewing
Have a wonderful day!
Colleen Wirth
Building Plans Examiner
Garfield County Community Development
108 8th Street, Suite 401
(970) 945-1377 ext1610
cwirth@qarfield-cou nty. com
2
From: Colleen Wirth
Sent: Thursday, June 20,202410:48 AM
To: andersenedward3T@vahoo.com
Subject: BLRE-06-24-8707 - Anderson Utility Room UNDER REVIEW
BLRE-06-24-8707 - Anderson Basement Utility Room
5582 CR 309 Parachute
Courtesy Message for Edward Anderson
Hello, I'm beginning the code review for the proposed utility room of your unfinished
basement and have a few questions to verify before the building permit is issued:
QUESTIONS:
1 . The % = foot graph paper provided, graphically depicts a UTILITY ROOM with two stair systems
and two door locations.
1.a. The stair that is open to the utility room appears to lead up? Does it lead upward into habitable
finished living space OR into an attached garage occupancy OR other?
'1.b. A second set of stairs depicting a second door and no intervening landing leads where? To another
portion of the unfinished basement? Or perhaps, to the outdoor yard and finished grade? OR other?
2. To clarify in the building file records, what type of utility equipment is being installed in space
marked UTILITY ROOM?
2.a.lf solar battery storage is included in this space, what ESS Energy storage system and KWh is
proposed for the space?
2.b. Will the UTILITY ROOM include other household residentialappliances / equipment, if so, please
specify?
2.c. ll an ENERGY STORAGE SYSTEM (ESS) is proposed, can you please supply a manufacturer's 'cut
sheet' including copy of manufacturer's installation instructions or a ESS Listing / Label from the
supplie/s man ufacturer?
2.d. Are the two stainruays / doonrvays existing and already built?
2.e. Are the UTILITY ROOM framed partition walls existing or proposed? Non-bearing wood studs, metal
studs etc?
3
2.f. Will the UTILITY ROOM have existing / proposed finished 5/8 type X drywall installed?
2.9. SEE ATTACHED PDF GUIDE SECTION R328 R328.1, R328.2, R328.3, R328.4 and F328.5 for
related code references.
l'm requesting further information now so we have a clearer understanding what is going to be stored in
the basement UTILTIY ROOM and how building occupants travel through this space and into other
occupied portions of the building / property.
Thanks for your submittal application and content thusfar, I look fonrvard to working with you and learning
more about the project,
Golleen Wirth
Building Plans Examiner
Garfield Gounty Community Development
108 8th Street, Suite 401
(970) 945-1377 ext1610
cwi rth @qarfield-cou ntv. com
4