HomeMy WebLinkAboutMechanical Balance Report Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave., Suite 220 – Eaton CO 80615 Phone (970) 454-5351 – Fax (970) 454-5391 CERTIFIED TEST, ADJUST, AND BALANCE REPORT DATE 7/29/2024 PROJECT Atlantic Aviaton -Rifle Hangar 6 Garfield County Airport Rifle, CO ***Pre-Final Balance Report*** ARCHITECT Tectonic Management Group, Inc. 6695 W 48th Ave Wheatridge, CO ENGINEER The Ballard Group, Inc. 2525 S. Wadsworth Blvd. Suite 200 Lakewood, CO CONTRACTOR MTech Mechanical 1353 Chambers Ave Eagle, CO Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 – Eaton, CO 80615 Phone (970) 454-5351 – Fax (970) 454-5391 PROJECT: Atlantic Aviation – Rifle Hangar 6 ADDRESS: Garfield County Airport Rifle, CO The data presented in this report is an exact record of the system performance and was obtained in accordance with NEBB Standard Procedures. Any variances from design quantities which exceed NEBB tolerances are noted throughout the report. The air distribution systems have been tested & balanced and final adjustments have been made in accordance with NEBB “Procedural Standards for Testing, Adjusting & Balancing of Environmental Systems” and the project specifications. NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:7/29/2024 The hydronic distribution systems have been tested & balanced and final adjustments have been made in accordance with NEBB “Procedural Standards for Testing, Adjusting & Balancing of Environmental Systems” and the project specifications. NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:7/29/2024 SUBMITTED & CERTIFIED BY NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. TAB SUPERVISOR: David C. Reichel REG. NO.: 2389 SIGNATURE: DATE: 7/29/2024 CERTIFICATION EXPIRATION DATE: 12/31/2024 Deficiency ReportPROJECT: LOCATION: Atlantic Aviation - Rifle Hangar 6 Rifle, CO DATE: CONTACT: AUTHOR: 7/29/2024 Emerson Moore Emerson Moore Issue ID:0001 Status:Open Issue Priority: Equipment:P-01 Created Date:16-Jul-24 Issue Description: System is not piped to design requirements. Pump diagram shows Boiler Piping and P-1 Piping to have respective Supply and Return Piping toed into AS-1. System is currently a single path system and it needs to be a coupled loop. Issue Type:Not Assigned Role Assignment:My Company Users L.H. Finn and Associates PreFinal Balance Report *System Has been re-piped since deficiency was originally created. System to be balanced on return visit. Table of ContentsPROJECT: LOCATION: Atlantic Aviation - Rifle Hangar 6 Rifle, CO DATE: CONTACT: AUTHOR: 7/29/2024 Emerson Moore Emerson Moore 1 Instrument Calibration Report.pdf............................................................................................................................1 2 Calibration Certificates.pdf.......................................................................................................................................2 3 Abbreviation Report.pdf............................................................................................................................................4 4 Fan Coil....................................................................................................................................................................5 4.1 F-01....................................................................................................................................................................5 4.2 F-02....................................................................................................................................................................6 4.3 F-03....................................................................................................................................................................7 4.4 F-04....................................................................................................................................................................8 5 Fan Unit....................................................................................................................................................................9 5.1 EF-01..................................................................................................................................................................9 5.2 EF-02..................................................................................................................................................................10 5.3 EF-03..................................................................................................................................................................11 6 Hydronic Pump.........................................................................................................................................................12 6.1 P-01....................................................................................................................................................................12 7 2024.07.12 MECH.pdf..............................................................................................................................................13 L.H. Finn and Associates PreFinal Balance Report Manufacturer Model Serial Application Cal. Date Alnor HM-680 71043011 Hydronic Press. & Diff. Press.9/29/2023 Extech 461895 Q590099 Rotation Measurement 8/10/2023 Fluke 335 12990071 Electrical Measurement 8/8/2023 Evergreen Telemetry S-PVF-1 1700213 Pressure Velocity Module 1/12/2024 Evergreen Telemetry RM-T-1 1900172 Radio Module - Temperature 1/12/2024 Evergreen Telemetry PR-T-2 1900177 Temperature Probe (Surface)1/12/2024 Evergreen Telemetry PR-T-4-6 1900119 Temperature Probe (Insertion)1/12/2024 Evergreen Telemetry PR-T-5 1900172 Temperature Sensor (Air)1/12/2024 Evergreen Telemetry S-H-3-5"1900155 Humidity Sensor 1/12/2024 REMARKS: Not all equipment shown was used on this project. Project: Atlantic Aviation - Rifle Hangar 6 Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 - Eaton, CO 80615 Phone (970) 454-5351 - Fax (970) 454-5391 INSTRUMENT CALIBRATION REPORT Page 1 of 19 NEBB LAERIE Calibration & Metrology Services Environmental:73.4 °F±(9°F) RH(40 to 65)% Calibration Event: UUT Manufacturer: Description S/N: ID: PO# CAL-DATE: CAL-DUE: Environmental: Eng. / Metrologist:NDH Percent of Range REF RPM Min RPM UUT Ind RPM Max RPM Compilation 20.0 500 488 500.0 512 Calibrated 50.0 1000 978 1000.0 1022 Calibrated 80.0 5000 4898 5000.0 5102 Calibrated Calibration Performance Report for: Tachometer, Laser, Contact 68° +/- 2ºF RH(10 to 45%) Extech Lawrence Finn and Associates RPM ±2% R ± 2 RPM RANGE 0-5000 RPM Calibration Performed: NEBB FOUND-LEFT Calibration Q590099 Q394479 10-Aug-2023 10-Aug-2024 www.laerie.com This report shall not be modified or reproduced except in full and with the written approval of Laerie Inc. LAERIE Calibration & Metrology Services 56 Gateway Circle Berthoud, Colorado 80513 Office: 970-532-7990 TF: 1-877-532-7990 Fax: 970-532-7992 Laboratory Altitude: 5,044 ft Veridical Review: VR@Laerie.com Page 1 of 1 Page 2 of 19 Page 3 of 19 Project: Atlantic Aviation - Rifle Hangar 6 Symbol Description Symbol Description A Airflow (L/S)NA Not Applicable AF Air Foil NI Not Installed ANA Access Not Available NIC Not In Contract BI Backward Incline NM Not Measurable CD Ceiling Diffuser NPT No Pressure Tap CFM Airflow (Cubic Feet / Minute)NR Not Readable DD Direct Drive NS Not Shown DWDI Double Width Double Inlet NT No Information Tag EAT Entering Air Temperature OD Outside Diameter EF Exhaust Fan RPM Revolution Per Minute EG Exhaust Grille SD Supply Diffuser ER Exhaust Register SNKL Snorkel ESP External Static Pressure SP Static Pressure EWT Entering Water Temperature SPD Static Pressure Drop FC Forward Curve SR Supply Register GPM Waterflow (Gallons / Minute)SWSI Single Width Single Inlet HC Heat Coil T Temperature ( F ) HEX Heat Exchanger TSP Total Static Pressure HRC Heat Recovery Coil VFD Variable Frequency Drive Hz Hertz VS Variable Speed ID Inside Diameter W Waterflow (L/S) In. WC Inches of Water Column LAT Leaving Air Temperature LWT Leaving Water Temperature REMARKS: Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 - Eaton, CO 80615 Phone (970) 454-5351 - Fax (970) 454-5391 ABBREVIATION REPORT Page 4 of 19 Fan CoilPROJECT: LOCATION: Atlantic Aviation - Rifle Hangar 6 Rifle, CO DATE: CONTACT: AUTHOR: 7/29/2024 Emerson Moore Emerson Moore Tested By:Emerson Moore Date:7/16/2024 SYSTEM/UNIT: F-01 Unit Data Unit Manufacturer York Unit Model Number TM9E040A10MP12B Unit Serial Number W2L3939340 Filter Type Disposable Filter Qty 1 Filter Size 14x24x1 Test Data Total CFM Design 700 CFM Total CFM Actual 734 CFM Outside Air CFM Design 75 CFM Outside Air CFM Actual 76 CFM Return Air CFM Design 625 CFM Return Air CFM Actual 658 CFM Motor Volts T1-T2 121 Volts Amps T1 4.5 Amps Fan RPM Actual Medium RPM E.S.P. In -0.42 In. wc. E.S.P. Out 0.1 In. wc. Unit E.S.P. Actual 0.52 In. wc. Motor Data Motor Manufacturer Genteq Motor HP 1/2 Motor RPM 1050(5 SPD) RPM Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 6.4 Amps Sheave Data Motor Sheave Make Direct Drive System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 107 CD-1 24x24 175 169 183 97 105 Outlet-02 107 CD-1 24x24 175 144 185 82 106 Outlet-03 107 CD-1 24x24 175 156 182 89 104 Outlet-04 107 CD-1 24x24 175 153 184 87 105 Totals:---700 622 734 89 105 F-01 Supply Outlet Summary L.H. Finn and Associates PreFinal Balance Report Page 5 of 19 Fan CoilPROJECT: LOCATION: Atlantic Aviation - Rifle Hangar 6 Rifle, CO DATE: CONTACT: AUTHOR: 7/29/2024 Emerson Moore Emerson Moore Tested By:Emerson Moore Date:7/16/2024 SYSTEM/UNIT: F-02 Unit Data Unit Manufacturer York Unit Model Number TM9E040A10MP12B Unit Serial Number W2L3939348 Filter Type Disposable Filter Qty 1 Filter Size 14x24x1 Test Data Total CFM Design 700 CFM Total CFM Actual 734 CFM Outside Air CFM Design 75 CFM Outside Air CFM Actual 77 CFM Return Air CFM Design 625 CFM Return Air CFM Actual 661 CFM Motor Volts T1-T2 121 Volts Amps T1 4.5 Amps Fan RPM Actual Medium RPM E.S.P. In -0.39 In. wc. E.S.P. Out 0.11 In. wc. Unit E.S.P. Actual 0.5 In. wc. Motor Data Motor Manufacturer Genteq Motor HP 1/2 Motor RPM 1050(5 SPD) RPM Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 6.4 Amps Sheave Data Motor Sheave Make Direct Drive System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 106 CD-1 24x24 175 216 183 123 105 Outlet-02 106 CD-1 24x24 175 218 185 125 106 Outlet-03 106 CD-1 24x24 175 165 186 94 106 Outlet-04 106 CD-1 24x24 175 173 184 99 105 Totals:---700 772 738 110 105 F-02 Supply Outlet Summary L.H. Finn and Associates PreFinal Balance Report Page 6 of 19 Fan CoilPROJECT: LOCATION: Atlantic Aviation - Rifle Hangar 6 Rifle, CO DATE: CONTACT: AUTHOR: 7/29/2024 Emerson Moore Emerson Moore Tested By:Emerson Moore Date:7/16/2024 SYSTEM/UNIT: F-03 Unit Data Unit Manufacturer York Unit Model Number TM9E040A10MP12B Unit Serial Number W2A4063539 Filter Type Disposable Filter Qty 1 Filter Size 14x24x1 Test Data Total CFM Design 700 CFM Total CFM Actual 740 CFM Outside Air CFM Design 75 CFM Outside Air CFM Actual 80 CFM Return Air CFM Design 625 CFM Return Air CFM Actual 660 CFM Motor Volts T1-T2 121 Volts Amps T1 4.4 Amps Fan RPM Actual Medium RPM E.S.P. In -0.35 In. wc. E.S.P. Out 0.11 In. wc. Unit E.S.P. Actual 0.46 In. wc. Motor Data Motor Manufacturer Genteq Motor HP 1/2 Motor RPM 1050(5 SPD) RPM Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 6.4 Amps Sheave Data Motor Sheave Make Direct Drive System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 105 CD-1 24x24 175 192 188 110 107 Outlet-02 105 CD-1 24x24 175 214 184 122 105 Outlet-03 105 CD-1 24x24 175 246 186 141 106 Outlet-04 105 CD-1 24x24 175 255 182 146 104 Totals:---700 907 740 130 106 F-03 Supply Outlet Summary L.H. Finn and Associates PreFinal Balance Report Page 7 of 19 Fan CoilPROJECT: LOCATION: Atlantic Aviation - Rifle Hangar 6 Rifle, CO DATE: CONTACT: AUTHOR: 7/29/2024 Emerson Moore Emerson Moore Tested By:Emerson Moore Date:7/16/2024 SYSTEM/UNIT: F-04 Unit Data Unit Manufacturer York Unit Model Number TM9E040A10MP12B Unit Serial Number W2L3939340 Filter Type Disposable Filter Qty 1 Filter Size 14x24x1 Test Data Total CFM Design 700 CFM Total CFM Actual 730 CFM Outside Air CFM Design 75 CFM Outside Air CFM Actual 78 CFM Return Air CFM Design 625 CFM Return Air CFM Actual 652 CFM Motor Volts T1-T2 121 Volts Amps T1 4.4 Amps Fan RPM Actual Medium RPM E.S.P. In -0.41 In. wc. E.S.P. Out 0.16 In. wc. Unit E.S.P. Actual 0.57 In. wc. Motor Data Motor Manufacturer Genteq Motor HP 1/2 Motor RPM 1050(5 SPD) RPM Motor Phase 1 Motor Hertz 60 Hz Motor Rated Volts 115 Motor FL Amps 6.4 Amps Sheave Data Motor Sheave Make Direct Drive System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Outlet-01 102 CD-1 24x24 125 174 132 139 106 Outlet-02 103 CD-1 24x24 125 203 131 162 105 Outlet-03 104 SG-1 8x8 50 69 52 138 104 Outlet-04 101 CD-1B 24x24 250 330 256 132 102 Outlet-05 110 CD-1 24x24 150 270 159 180 106 Totals:---700 1046 730 149 104 F-04 Supply Outlet Summary L.H. Finn and Associates PreFinal Balance Report Page 8 of 19 Fan UnitPROJECT: LOCATION: Atlantic Aviation - Rifle Hangar 6 Rifle, CO DATE: CONTACT: AUTHOR: 7/29/2024 Emerson Moore Emerson Moore Tested By:Emerson Moore Date:7/16/2024 SYSTEM/UNIT: EF-01 Log:EF-01 7/16/2024 Emerson Moore Design airflow based on summation of associated inlets. Unit Data Fan Manufacturer Cook Fan Model Number 120SQN17D081VF Fan Serial Number 041PK85090-00/0000701 Fan Type Backward Incline Fan Arrangement SWSI Fan Discharge Plenum Starter Data Installed Thermal Internal Test Data Total CFM Design 400 CFM Total CFM Actual 416 CFM Fan RPM Actual 1366(76%) RPM Motor Volts T1-T2 121 Volts Motor Amps 1 1.2 Amps SP In Actual -0.26 in. wc SP Out Actual 0.22 in. wc Total SP Actual 0.48 in. wc Motor Data Motor Manufacturer Vari-Flow Motor HP 1/4 HP Motor RPM 1725 RPM Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 3.2 Amps Sheave Data Motor Sheave Make Direct Drive System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Inlet-01 102 EG-1 24x12 150 113 154 75 103 Inlet-02 103 EG-1 24x12 150 155 156 103 104 Inlet-03 104 EG-2 8x8 100 298 106 298 106 Totals:---400 566 416 142 104 EF-01 Exhaust Inlet Summary L.H. Finn and Associates PreFinal Balance Report Page 9 of 19 Fan UnitPROJECT: LOCATION: Atlantic Aviation - Rifle Hangar 6 Rifle, CO DATE: CONTACT: AUTHOR: 7/29/2024 Emerson Moore Emerson Moore Tested By:Emerson Moore Date:7/16/2024 SYSTEM/UNIT: EF-02 Unit Data Fan Manufacturer Cook Fan Model Number 120SQN17D061VF Fan Serial Number 041PK85090-00/0002101 Fan Type Backward Incline Fan Arrangement SWSI Fan Discharge Plenum Starter Data Installed Thermal Internal Test Data Total CFM Design 125 CFM Total CFM Actual 131 CFM Fan RPM Actual 1061(58%) RPM Motor Volts T1-T2 121 Volts Motor Amps 1 0.8 Amps SP In Actual -0.18 in. wc SP Out Actual 0.22 in. wc Total SP Actual 0.40 in. wc Motor Data Motor Manufacturer Vari-Flow Motor HP 1/4 HP Motor RPM 1725 RPM Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 3.2 Amps Sheave Data Motor Sheave Make Direct Drive System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Inlet-01 101 EG-1 24x12 125 225 131 180 105 Totals:---125 225 131 180 105 EF-02 Exhaust Inlet Summary L.H. Finn and Associates PreFinal Balance Report Page 10 of 19 Fan UnitPROJECT: LOCATION: Atlantic Aviation - Rifle Hangar 6 Rifle, CO DATE: CONTACT: AUTHOR: 7/29/2024 Emerson Moore Emerson Moore Tested By:Emerson Moore Date:7/16/2024 SYSTEM/UNIT: EF-03 Unit Data Fan Manufacturer Cook Fan Model Number 165SQN17D VF Fan Serial Number 041SK85090-01/0000701 Fan Type Backward Incline Fan Arrangement SWSI Fan Discharge Plenum Starter Data Installed Thermal Internal Test Data Total CFM Design 1800 CFM Fan RPM Actual 1084(100%) RPM Motor Volts T1-T2 121 Volts Motor Amps 1 5.4 Amps SP In Actual -0.32 in. wc SP Out Actual 0.32 in. wc Total SP Actual 0.64 in. wc Motor Data Motor Manufacturer Vari-Flow Motor HP 1/2 HP Motor RPM 1087 RPM Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 6.4 Amps Sheave Data Motor Sheave Make Direct Drive System/Unit Area Served Outlet Type Size LxW / D AK Factor Maximum Design Prelim Reading Maximum Final % Prelim Deviation % Final Deviation Inlet-01 108 ER-1 18x10 450 246 448 55 100 Inlet-02 108 ER-1 18x10 450 289 456 64 101 Inlet-03 108 ER-1 18x10 450 602 449 134 100 Inlet-04 108 ER-1 18x10 450 686 461 152 102 Totals:---1800 1823 1814 101 101 EF-03 Exhaust Inlet Summary L.H. Finn and Associates PreFinal Balance Report Page 11 of 19 Hydronic PumpPROJECT: LOCATION: Atlantic Aviation - Rifle Hangar 6 Rifle, CO DATE: CONTACT: AUTHOR: 7/29/2024 Emerson Moore Emerson Moore Tested By:Emerson Moore Date:7/16/2024 SYSTEM/UNIT: P-01 Unit Data Pump Manufacturer Armstrong Pump Model Number IVS 4300-2x2x8-4P-5HP Pump Serial Number 1024124065 Pump Flowrate (GPM)96 GPM Starter Data Installed Thermal VFD Final Test Data Final GPM Design 98 GPM Motor Data Motor Manufacturer Armstrong Motor Frame 184TC Motor HP 5 HP Motor RPM 1755 RPM Motor Rated Volts 200/400 Volts Motor Phase 3 Motor Hertz 60 Hz Motor F.L. Amps 15.6/7.8 Amps Motor S.F.1.25 Power Factor 78 Efficiency 89.5 System/Unit Mfg.Model #Size Des. GPM Act. GPM Des. Valve D.P. Act. Valve D.P. Valve Pos. Zone-01 29 Zone-02 6 Zone-03A 19 Zone-03B 6 Zone-04 28 Zone-05 10 Totals:---98 0 --- P-01 Balance Valve Summary L.H. Finn and Associates PreFinal Balance Report Page 12 of 19 GENERAL LEGENDHVAC LEGEND P/T PRESSURE GAUGE WITH COCK THERMOMETER PRESSURE RELIEF VALVE TEE OFF TOP OF PIPE TEE OFF BOTTOM OF PIPE PRESSURE/TEMPERATURE TEST PLUG PIPE ELBOW UP PIPE ELBOW DOWN AIRFLOW - RETURN/EXHAUST AIRFLOW - SUPPLY MVD RETURN OR EXHAUST REGISTER OR GRILLE STANDARD RADIUS ELBOW FLEXIBLE DUCTWORK 45° TAKEOFF DUCT ELBOW WITH TURNING VANES RETURN/EXHAUST DUCT UP/ SUPPLY DUCT UP/SUPPLY DUCT DOWN MANUAL VOLUME DAMPER CONICAL SPIN-IN FITTING CONICAL SPIN-IN FITTING OFFSET DUCT UP / DOWN SQUARE TO ROUND TRANSITION DN UP BV CV AUTOMATIC AIR VENT MANUAL AIR VENT BALL VALVE BALANCING VALVE CONCENTRIC PIPE REDUCER ECCENTRIC PIPE REDUCER STRAINER WITH BLOWDOWN VALVE CHECK VALVE PIPE UNION STRAINER DIRECTION OF FLOW IN PIPE CONTROL WIRING F.P.C. A.F.F. N.I.C. M.C. E.C. ABBV. G.C. SYMBOL ELECTRICAL CONTRACTOR ABOVE FINISHED FLOOR MECHANICAL CONTRACTOR FIRE PROTECTION CONTRACTOR NOT IN CONTRACT GENERAL CONTRACTOR TCV MCD THERMOSTAT MOTORIZED CONTROL DAMPER (2 OR 3-WAY) TEMPERATURE CONTROL VALVE DESCRIPTIONABBV.SYMBOL DESCRIPTION GAUGE PIPE CAP ROUND DUCT UP / DOWN SMS SNOW MELT SUPPLYSMS SMR SNOW MELT RETURNSMR CEILING DIFFUSER B.F.F.BELOW FINISHED FLOOR CD RG/EG RETURN GRILLE WITH SOUND BOOT RL RS REFRIGERANT SUCTION REFRIGERANT LIQUIDRL RS T M WALL SWITCH$ RA EA OA SA RETURN AIR EXHAUST AIR OUTSIDE AIR SUPPLY AIR EWH P GRH ELECTRIC WALL HEATER GAS RADIANT HEATER PUMP CU B BOILER CONDENSING UNIT AS ET AIR SEPARATOR EXPANSION TANK FURNACEF EF EXHAUST FAN CD CEILING DIFFUSER RG RETURN GRILLE CF CEILING FAN WITH MANUAL VOLUME DAMPER WITHOUT MANUAL VOLUME DAMPER RETURN/EXHAUST DUCT DOWN IN DIRECTION OF ARROW (FOUR WAY THROW PATTERN) CEILING DIFFUSEREQUALSCD (TWO WAY THROW PATTERN AS INDICATED) 1. THE MECHANICAL CONTRACTOR SHALL INSPECT SITE TO BECOME FAMILIAR WITH THE SCOPE OF THE WORK. THESE DOCUMENTS DO NOT REFLECT AS-BUILT CONDITIONS. ANY DISCREPANCIES BETWEEN THESE DOCUMENTS AND THE ACTUAL CONDITIONS SHALL BE REPORTED TO THE ARCHITECT/ENGINEER FOR RESOLUTION PRIOR TO BID PRICING. NO EXTRAS WILL BE ALLOWED DUE TO LACK OF KNOWLEDGE OF THE EXISTING CONDITIONS. 2. THE MECHANICAL CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL ABOVE CEILING EQUIPMENT, DUCTWORK AND CEILING MOUNTED AIR DEVICES WITH ARCHITECTURAL, STRUCTURAL AND ELECTRICAL CONDITIONS. APPROXIMATE LOCATIONS OF NEW WORK ARE SHOWN AND SHOULD BE FOLLOWED AS CLOSELY AS CONDITIONS WILL ALLOW. 3. MECHANICAL WORK SHALL COMPLY WITH ALL APPLICABLE CODES. VERIFY ALL REQUIREMENTS PRIOR TO SUBMITTING BID OR COMMENCING WORK. 4. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ANY ADDITIONAL COORDINATION OR MODIFICATIONS THAT MAY BE REQUIRED DUE TO THE USE OR INSTALLATION OF EQUIPMENT OTHER THAN THAT OF THE BASIS OF DESIGN MANUFACTURERS LISTED ON THE DRAWINGS. 5. THE MECHANICAL SYSTEM SHOWN SHALL BE ROUTED AS HIGH AS POSSIBLE. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING REQUIREMENTS WITH ALL TRADES PRIOR TO CONSTRUCTION. 6. REFER TO THE ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF ALL CEILING AIR DEVICES AND ACCESS PANELS. OBTAIN CLARIFICATION FROM THE ARCHITECT, IF EXACT LOCATIONS ARE NOT SHOWN. 7. REFER TO THE ARCHITECTURAL DRAWINGS FOR ROOFING DETAILS SPECIFIC TO THE PROJECT. 8. THE MECHANICAL CONTRACTOR SHALL COORDINATE THERMOSTAT, SENSOR, AND SWITCH LOCATIONS WITH ARCHITECT/ENGINEER PRIOR TO INSTALLATION. ALL THERMOSTATS, SENSORS, AND SWITCHES SHALL BE LOCATED 48" A.F.F. UNLESS INDICATED OTHERWISE. 9. BALANCE AIR, HYDRONIC WATER SYSTEM AND DOMESTIC WATER SYSTEM TO THE QUANTITIES SHOWN AND SUBMIT BALANCE REPORT(S) TO THE ARCHITECT/ENGINEER FOR REVIEW. 10. ACCESS DOORS SHALL BE INSTALLED IN ORDER TO PROVIDE ACCESS TO MECHANICAL SYSTEMS LOCATED ABOVE INACCESSIBLE CEILINGS, WHETHER OR NOT SHOWN ON THE DRAWINGS. ACCESS DOORS SHALL BE FURNISHED BY THE MECHANICAL CONTRACTOR AND INSTALLED BY THE GENERAL CONTRACTOR. ACCESS DOOR LOCATIONS SHALL BE APPROVED BY THE ARCHITECT PRIOR TO INSTALLATION. PROVIDE 12"x12" ACCESS DOORS FOR HAND ACCESS AND 24"x24" ACCESS DOORS FOR HEAD AND SHOULDER ACCESS. MECHANICAL GENERAL NOTES 1. DUCTWORK DIMENSIONS LISTED ON THE DRAWINGS ARE CLEAR, INSIDE DIMENSIONS. 2. FLEXIBLE DUCTWORK SHALL BE INSULATED AND SHALL BE THE SAME SIZE AS THE NECK OF THE AIR DEVICE. FLEXIBLE DUCTWORK SHALL NOT EXCEED 8'-0" IN LENGTH. PROVIDE WRAPPED RIGID ROUND DUCTWORK FOR TAKEOFFS IN EXCESS OF 8'-0". 3. UNLESS SHOWN OTHERWISE, THE INLET DUCTWORK TO FURNACES SHALL BE THE FULL SIZE OF THE UNIT CONNECTION. 4. PROVIDE DUCT TRANSITIONS FROM EQUIPMENT CONNECTIONS TO DUCT SIZES AS SHOWN. 5. PROVIDE A FLEXIBLE CONNECTION TO THE INTAKE AND DISCHARGE OF ALL MECHANICAL EQUIPMENT HAVING ROTATING PARTS. FLEXIBLE CONNECTION SHALL COMPLY WITH ALL APPLICABLE CODES. 6. ALL DUCTWORK SHALL BE A MINIMUM 26 GAUGE SHEETMETAL, OR AS REQUIRED BY ALL APPLICABLE CODES. ALL DUCTWORK CROSSING RATED CORRIDORS SHALL BE A MINIMUM 24 GAUGE SHEETMETAL. MEET OR EXCEED SMACNA STANDARDS. 7. ALL SUPPLY, RETURN AND EXHAUST DUCTWORK SHALL BE SEALED AIRTIGHT WITH DUCT SEALANT (SMACNA SEAL CLASS "A") ALONG ALL SEAMS AND JOINTS. 8. ALL RECTANGULAR SUPPLY, RETURN AND TRANSFER DUCTWORK SHALL BE SHEETMETAL WITH DUCT LINER. REFER TO SPECIFICATION 233000 FOR REQUIREMENTS. 9. ALL EXHAUST DUCTWORK SHALL BE UNLINED SHEETMETAL, UNLESS NOTED OTHERWISE. 10. ALL CONCEALED SPIRAL ROUND DUCTWORK SHALL BE SHEETMETAL WITH EXTERNAL DUCT INSULATION. REFER TO SPECIFICATION 230700 FOR REQUIREMENTS. 11. MAINTAIN A MINIMUM 10'-0" SEPARATION FROM OUTSIDE AIR INTAKES TO EXHAUST TERMINATIONS AND FLUE OUTLETS. 12. MAINTAIN A MINIMUM OF 15'-0" FROM OUTSIDE AIR INTAKES TO PLUMBING VENTS. 13. MAINTAIN A MINIMUM 3'-0" SEPARATION FROM EXHAUST TERMINATIONS TO OPERABLE WINDOWS AND DOORS. 14. COORDINATE WALL CAP AND AIR DEVICE PLACEMENT WITH BRICK OR BLOCK COURSING WHERE APPLICABLE. 15. SPIN-IN FITTINGS SERVING GRILLES AND DIFFUSERS SHALL BE CONICAL WITH MANUAL VOLUME DAMPERS, UNLESS THE AIR DEVICE IS PROVIDED WITH AN OPPOSED BLADE DAMPER. 16. RECTANGULAR BRANCH DUCT TAKEOFFS SHALL HAVE 45° TAKEOFFS AND ROUND DUCT TAKEOFFS SHALL BE CONICAL. 17. ALL ELBOWS, BOTH HORIZONTAL AND VERTICAL, SHALL BE LONG RADIUS ELBOWS WHEREVER POSSIBLE OR SHALL HAVE TURNING VANES UNLESS SHOWN OTHERWISE. 18. 12"x12" ACCESS DOORS SHALL BE PROVIDED FOR ALL MANUAL VOLUME DAMPERS LOCATED ABOVE GYPSUM BOARD CEILINGS. ALL FINAL ACCESS DOOR LOCATIONS SHALL BE APPROVED BY ARCHITECT PRIOR TO INSTALLATION. 19. 24"x24" ACCESS DOORS SHALL BE PROVIDED FOR ALL EQUIPMENT LOCATED ABOVE GYPSUM BOARD CEILINGS. ALL FINAL ACCESS DOOR LOCATIONS SHALL BE APPROVED BY ARCHITECT PRIOR TO INSTALLATION. 20. ALL JOB SITE DUCTWORK PRIOR TO INSTALLATION SHALL BE COVERED AND PROTECTED FROM DIRT, DUST, AND DAMAGE PER SMACNA STANDARDS. 21. ALL ROOF MOUNTED EQUIPMENT SHALL BE LOCATED AT LEAST 10'-0" FROM THE EDGE OF THE ROOF. THE GENERAL AND MECHANICAL CONTRACTOR SHALL VERIFY AND CONFIRM THE ACTUAL INSTALLED LOCATIONS OF ALL ROOF MOUNTED EQUIPMENT. IF THIS EQUIPMENT IS INSTALLED WITHIN 10'-0" OF THE ROOF EDGE, THE GENERAL CONTRACTOR SHALL INSTALL AN OSHA APPROVED GUARD RAIL. 22. FLUES FOR BOILERS, WATER HEATER, FURNACES AND RADIANT HEATERS SHALL BE ENGINEERED BY THE FLUE MANUFACTURER, BASED ON ACTUAL EQUIPMENT, AND SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL. MECHANICAL HVAC NOTES 1. HEATING WATER PIPING AND INSULATION: REFER TO SPECIFICATION SECTIONS 23 2000 AND 23 0700 RESPECTIVELY FOR PIPING AND INSULATION REQUIREMENTS. 2. REFRIGERANT PIPING AND INSULATION: REFER TO SPECIFICATION SECTIONS 23 2000 AND 23 0700 RESPECTIVELY FOR PIPING AND INSULATION REQUIREMENTS. 3. THE AIR-COOLED CONDENSING UNIT SUPPLIER SHALL SUBMIT A MANUFACTURER APPROVED REFRIGERANT PIPING DIAGRAM SPECIFIC TO THIS PROJECT. CLEARLY IDENTIFY PIPING LENGTHS, DROPS, RISES, SIZES, VALVES, AND SPECIALTIES. 4. INSTALL ALL VALVES ABOVE ACCESSIBLE CEILINGS. PROVIDE 12"x12" ACCESS DOORS FOR ALL VALVES ABOVE GYPSUM CEILINGS. ALL FINAL ACCESS DOOR LOCATIONS SHALL BE APPROVED BY THE ARCHITECT DURING COORDINATED SHOP DRAWING REVIEW. 5. PROVIDE PIPING SLEEVES AT ALL WALL PENETRATIONS. REFER TO SPECIFICATION FOR EXACT REQUIREMENTS. MECHANICAL PIPING NOTES 1. FURNISH ALL LABOR, MATERIALS TRANSPORTATION, EQUIPMENT, AND SERVICES TO INSTALL A HYDRONIC RADIANT HEAT SYSTEM WHERE INDICATED ON THE DRAWINGS. 2. SHOP DRAWINGS, OR DESCRIPTIONS OF MATERIALS, AND DETAILS OF INSTALLATION SHALL BE SUBMITTED FOR APPROVAL. NO FABRICATION SHALL BE PERFORMED UNTIL APPROVAL IS OBTAINED. 3. TUBE SHALL CARRY A 25-YEAR NON-PRORATED WARRANTY AGAINST FAILURE DUE TO DEFECT IN MATERIAL AND/OR WORKMANSHIP. 4. TUBE SHALL BE CROSS-LINKED POLYETHYLENE WITH AN OXYGEN DIFFUSION BARRIER, RATED AT 180°F MAXIMUM WORKING TEMPERATURE, AND 100 PSI WORKING PRESSURE. THE TUBE SHALL BE MANUFACTURED IN ACCORDANCE WITH ASTM STANDARD SPECIFICATION F 876. 5. TUBING LAYOUT SHALL BE BY THE TUBING MANUFACTURER'S APPROVED REPRESENTATIVE. TUBING MANUFACTURER'S REPRESENTATIVE SHALL PROVIDE A WRITTEN STATEMENT THAT THE TUBING LAYOUT WILL OPERATE CORRECTLY WITH THE SPECIFIED PUMP AND CONTROL SYSTEM. IF THE TUBING LAYOUT DOES NOT WORK WITH THE SPECIFIED PUMP, THE MANUFACTURER'S REPRESENTATIVE SHALL SELECT AND SUBMIT ON THE CORRECT PUMP. SUBMIT TUBE FLOW AND PRESSURE DROP DATA FOR EACH ZONE FOR REVIEW. 6. THE MINIMUM BEND RADIUS FOR COLD BENDING OF THE TUBE SHALL NOT BE LESS THAN SIX TIMES THE OUTSIDE DIAMETER. BENDS WITH A RADIUS LESS THAN STATED SHALL REQUIRE THE USE OF A BEND SUPPORT AS SUPPLIED BY THE TUBE MANUFACTURER. 7. MANIFOLDS: MANIFOLDS SHALL BE COPPER. MANIFOLDS SHALL HAVE INTEGRAL CIRCUIT BALANCING VALVES. MANIFOLDS SHALL BE ABLE TO VENT AIR AND DRAIN WATER FROM THE SYSTEM. MANIFOLDS SHALL BE PROVIDED WITH SUPPORT BRACKETS AND TUBE BEND SUPPORT. MANIFOLDS SHALL BE ISOLATED FROM SUPPLY AND RETURN TUBING WITH VALVES THAT ARE SUITABLE FOR ISOLATION AND BALANCING. 8. FITTINGS SHALL BE MANUFACTURED OF STAINLESS STEEL. THESE FITTINGS MUST BE SUPPLIED BY THE TUBE MANUFACTURER. THE FITTINGS SHALL CONSIST OF A BARBED INSERT, A COMPRESSION RING, AND A COMPRESSION NUT. 9. INSTALL MANIFOLDS IN UPONOR WALL CABINETS. COORDINATE WALL CABINET LOCATIONS, SIZES AND FRAMING REQUIREMENTS WITH THE GENERAL CONTRACTOR. 10. UNLESS NOTED OTHERWISE, MOUNT WALL CABINETS FOR RADIANT HEAT MANIFOLDS WITH THE BOTTOM AT 18" A.F.F. 11. ACCEPTABLE SNOWMELT MANIFOLD AND TUBING MANUFACTURERS: UPONOR OR PRIOR APPROVED EQUAL. 12. PROVIDE CONTROLS AS REQUIRED TO CONTROL THE RADIANT HEAT SYSTEMS (BOILERS, PUMP, ZONE CONTROL VALVES, THERMOSTATS, SENSORS, ETC.). REFER TO DRAWINGS AND SPECIFICATIONS FOR CONTROLS SEQUENCES AND CONTROLLER REQUIREMENTS. SUBMIT ALL FINAL CONTROL SEQUENCES AND EQUIPMENT FOR APPROVAL. RADIANT HEAT (SNOWMELT) GENERAL NOTES 1. SYSTEM COMMISSIONING. PRIOR TO FINAL MECHANICAL AND PLUMBING INSPECTIONS, THE PROJECT COMMISSIONING AUTHORITY (CxA) SHALL PROVIDE EVIDENCE OF MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION IN ACCORDANCE WITH THIS SECTION. COPIES OF ALL DOCUMENTATION SHALL BE MADE AVAILABLE TO THE CODE OFFICIAL UPON REQUEST. A. NOTE THAT THE MECHANICAL ENGINEER OR MEMBERS OF THE DESIGN TEAM, ARE NOT THE ACTING CxA. THE CxA SHALL BE HIRED DIRECTLY BY THE OWNER. B. THE MECHANICAL CONTRACTOR(S) SHALL INCLUDE IN THEIR BID TIME NECESSARY FOR PARTICIPATION WITH THE CxA AS NEEDED FOR COMPLETION OF THE COMMISSIONING DOCUMENTATION. 2.THE FOLLOWING COMMISSIONING ACTIVITIES SHALL BE COMPLETED: A. COMMISSIONING PLAN. A COMMISSIONING PLAN SHALL BE DEVELOPED BY THE CxA AND SHALL INCLUDE THE FOLLOWING ITEMS: 1. A NARRATIVE DESCRIPTION OF THE ACTIVITIES THAT WILL BE ACCOMPLISHED DURING EACH PHASE OF COMMISSIONING, INCLUDING PERSONNEL INTENDED TO ACCOMPLISH EACH OF THE ACTIVITIES. 2. A LISTING OF SPECIFIC EQUIPMENT OR SYSTEMS TO BE TESTED AND A DESCRIPTION OF THE TESTS TO BE PERFORMED. 3. FUNCTIONS TO BE TESTED INCLUDING, BUT NOT LIMITED TO, CALIBRATIONS. 4. CONDITIONS UNDER WHICH THE TEST WILL BE PERFORMED. TESTING SHALL AFFIRM WINTER AND SUMMER DESIGN CONDITIONS AND FULL OUTSIDE AIR CONDITIONS. 5. MEASURABLE CRITERIA FOR PERFORMANCE. B. SYSTEMS ADJUSTING AND BALANCING. HVAC SYSTEMS SHALL BE BALANCED IN ACCORDANCE WITH ACCEPTED INDUSTRY STANDARDS. REFER TO TEST AND BALANCING SPECIFICATION FOR ADDITIONAL PARAMETERS. C. FUNCTIONAL PERFORMANCE TESTING. 1. EQUIPMENT. EQUIPMENT FUNCTIONAL PERFORMANCE TESTING SHALL DEMONSTRATE THE INSTALLATION AND OPERATION OF COMPONENTS, SYSTEMS, AND SYSTEM-TO- SYSTEM INTERFACING RELATIONSHIPS IN ACCORDANCE WITH PLANS AND SPECIFICATIONS SUCH THAT OPERATION, FUNCTION, AND MAINTENANCE SERVICEABILITY FOR EACH OF THE COMMISSIONED SYSTEMS IS CONFIRMED. TESTING SHALL INCLUDE ALL MODES AND SEQUENCE OF OPERATION, INCLUDING UNDER FULL- LOAD, PART-LOAD, AND THE FOLLOWING EMERGENCY CONDITIONS AS APPLIES: A. ALL MODES DESCRIBED IN THE SEQUENCE OF OPERATION. B. REDUNDANT OR AUTOMATIC BACK-UP MODE. C. PERFORMANCE OF ALARMS. D. MODE OF OPERATION UPON A LOSS OF POWER AND RESTORATION OF POWER. 2. CONTROLS. HVAC AND SERVICE WATER HEATING CONTROL SYSTEMS SHALL BE TESTED TO DOCUMENT THAT CONTROL DEVICES, COMPONENTS, EQUIPMENT, AND SYSTEMS ARE CALIBRATED AND ADJUSTED AND OPERATE IN ACCORDANCE WITH PLANS AND SPECIFICATIONS. SEQUENCES OF OPERATION SHALL BE FUNCTIONALLY TESTED TO DOCUMENT THEY OPERATE IN ACCORDANCE WITH PLANS AND SPECIFICATIONS. 3. PRELIMINARY COMMISSIONING REPORT. A PRELIMINARY REPORT OF COMMISSIONING TEST PROCEDURES AND RESULTS SHALL BE COMPLETED AND CERTIFIED BY THE CxA. THE REPORT SHALL BE ORGANIZED WITH MECHANICAL AND SERVICE HOT WATER FINDINGS IN SEPARATE SECTIONS TO ALLOW INDEPENDENT REVIEW. THE REPORT SHALL BE IDENTIFIED AS 'PRELIMINARY COMMISSIONING REPORT' AND SHALL IDENTIFY: A. ITEMIZATION OF DEFICIENCIES FOUND DURING TESTING REQUIRED BY THIS SECTION THAT HAVE NOT BEEN CORRECTED AT THE TIME OF REPORT PREPARATION. B. DEFERRED TESTS THAT CANNOT BE PERFORMED AT THE TIME OF REPORT PREPARATION BECAUSE OF CLIMATIC CONDITIONS. C. CLIMATIC CONDITIONS REQUIRED FOR PERFORMANCE TESTS. D. RESULTS OF FUNCTIONAL PERFORMANCE TESTS. E. FUNCTIONAL PERFORMANCE TEST PROCEDURES USED DURING THE COMMISSIONING PROCESS, INCLUDING MEASURABLE CRITERIA FOR TEST ACCEPTANCE. D. ACCEPTANCE REPORT. BUILDINGS SHALL NOT BE CONSIDERED AS ACCEPTABLE FOR A FINAL INSPECTION UNTIL THE CODE OFFICIAL HAS RECEIVED THE PRELIMINARY COMMISSIONING REPORT FROM THE BUILDING OWNER OR OWNER'S AUTHORIZED AGENT. 1. THE CODE OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A COPY OF THE PRELIMINARY COMMISSIONING REPORT BE MADE AVAILABLE FOR REVIEW BY THE CODE OFFICIAL. E. DOCUMENTATION REQUIREMENTS. THE DOCUMENTS DESCRIBED IN THIS SECTION SHALL BE PROVIDED TO THE BUILDING OWNER OR OWNER'S AUTHORIZED AGENT WITHIN 90 DAYS OF THE DATE OF RECEIPT OF THE CERTIFICATE OF OCCUPANCY. 1. SYSTEM BALANCING REPORT. 2. FINAL COMMISSIONING REPORT. A REPORT OF TEST PROCEDURES AND RESULTS IDENTIFIED AS 'FINAL COMMISSIONING REPORT' SHALL BE DELIVERED TO THE BUILDING OWNER OR OWNER'S AUTHORIZED AGENT. THE REPORT SHALL BE ORGANIZED WITH MECHANICAL SYSTEM AND SERVICE HOT WATER SYSTEM FINDINGS IN SEPARATE SECTIONS TO ALLOW INDEPENDENT REVIEW. THE REPORT SHALL INCLUDE THE FOLLOWING: A. RESULTS OF FUNCTIONAL PERFORMANCE TESTS. B. DISPOSITION OF DEFICIENCIES FOUND DURING TESTING, INCLUDING DETAILS OF CORRECTIVE MEASURES USED OR PROPOSED. C. FUNCTIONAL PERFORMANCE TEST PROCEDURES USED DURING THE COMMISSIONING PROCESS INCLUDING MEASURABLE CRITERIA FOR TEST ACCEPTANCE, WITH THE EXCEPTION OF TESTS THAT CANNOT BE PERFORMED AT THE TIME OF REPORT PREPARATION DUE TO CLIMATIC CONDITIONS. MECHANICAL COMMISSIONING NOTES The Ballard Group, Inc. Mechanical Consulting Engineers 2525 S. Wadsworth Blvd, Suite 200 Lakewood, CO 80227 (303) 988-4514 Consultant Seal Project Title Project Description Revision Log Issue Date Tectonic Project Number Issue Title Sheet Title Sheet Number Approved By Revision Date Al l D r a w i n g s A n d W r i t t e n M a t e r i a l A p p e a r i n g H e r e i n C o n s t i t u t e O r i g i n a l A n d Un p u b l i s h e d W o r k O f T h e D e s i g n e r A n d M a y N o t B e D u p l i c a t e d , U s e d , O r Di s c l o s e d W i t h o u t W r i t t e n C o n s e n t F r o m T e c t o n i c M a n a g e m e n t G r o u p , I n c . Drawn By 1/ 2 0 / 2 0 2 3 8 : 3 4 : 0 7 A M C: \ U s e r s \ p f a i l l a \ D o c u m e n t s \ 2 2 0 7 9 _ H V A C _ R 2 1 _ P F a i l l a . r v t M0.00 Mechanical Cover Sheet 100% Construction Documents 202199 01/20/2023 AAS-RIL, Hgr 6 Rifle Garfield County Airport Rifle, CO At l a n t i c A v i a t i o n - Ri f l e H a n g a r 6 PWF JJG SHEET INDEX SHEET NUMBER MECHANICAL SHEET TITLE SHEET SCALE SHEET ISSUED M0.00 Mechanical Cover Sheet NONE X M2.00 First Floor HVAC Plan 1/8" = 1'-0"X M2.01 Mezzanine HVAC Plan & Sections 1/8" = 1'-0"X M5.00 HVAC Schedules NONE X M5.01 HVAC Schedules NONE X M6.00 HVAC Details & Piping Schematic NONE X M7.00 HVAC Outside Air Calcs & Sequence NONE X 1/20/2023 Page 13 of 19 Global 7500 HB HB HB CA CA CA FIRST FLOOR HVAC KEYNOTES: 1 HORIZONTAL FURNACE WITH ASSOCIATED COOLING COIL. SET UNIT ABOVE CEILING. ENSURE SPACE BELOW UNIT IS SUITABLE FOR CONDENSATE DRAIN CONNECTIONS. REFER TO SCHEDULES AND DETAILS. 2 VERTICAL FURNACE WITH ASSOCIATED COOLING COIL. REFER TO SCHEDULES AND DETAILS. 3 INLINE EXHAUST FAN SUPPORTED FROM STRUCTURE. REFER TO SCHEDULES AND DETAILS. 4 OUTSIDE AIR DUCTWORK UP. REFER TO MEZZANINE PLAN. 5 EXHAUST DUCTWORK OF SIZE INDICATED TO SIDEWALL TERMINATION. TERMINATE WITH MANUFACTURER'S APPROVED SIDEWALL CAP. 6 CPVC FLUE/COMBUSTION AIR OF SIZE INDICATED TO SIDEWALL CONCENTRIC VENT. TERMINATE PER MANUFACTURER'S REQUIREMENTS. 7 DUCTLESS FAN COIL MOUNTED ON WALL ABOVE DOOR AS INDICATED. REFER TO SCHEDULE. 8 GRADE MOUNTED CONDENSING UNIT MOUNTED ON 4" CONCRETE HOUSEKEEPING PAD. INSTALL PER MANUFACTURER'S INSTALLATION INSTRUCTIONS AND MAINTAINING MANUFACTURER'S CLEARANCE REQUIREMENTS. ROUTE MANUFACTURER'S REFRIGERANT LINESETS CONCEALED TO ASSOCIATED FURNACE/FAN COIL UNIT. REFER TO SCHEDULE. 9 ROUTE 4"ø SINGLE WALL GALVANIZED EXHAUST THROUGH WALL. TERMINATE IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS. 10 VENT PIPING EXPOSED WITHIN HANGAR TO BE WRAPPED WITH 1-1/2" THICK FIBERGLASS INSULATION WITH VAPOR JACKET. 11 INSTALL RADIANT HEATER WITH MANUFACTURER'S WIND CLIPS AND PER MANUFACTURER'S WINDY CONDITION INSTALLATION INSTRUCTIONS. REFER TO SECTION ON M2.01 FOR ELEVATIONS. 12 HVLS FAN CONTROLLER. 13 14 ZONE MANIFOLD MOUNTED LOW ON WALL. PROVIDE LOCKABLE SURFACE MOUNTED MANIFOLD CABINET. REFER TO DETAIL. BOILER EMERGENCY POWER OFF SWITCH. 15 APPROXIMATE LOCATION OF SLAB/MOISTURE SENSOR. 16 DIMENSION INDICATED BASED ON APPROXIMATE DISTANCE REQUIRED TO PROVIDE SNOWMELT UNDER THE DOOR TRACK SYSTEM. REFER TO DETAIL. 17 DIMENSION INDICATED BASED ON APPROXIMATE DISTANCE REQUIRED FROM THE EXTERIOR OF THE BUILDING FOR ALL RADIANT LOOPS TO ROUTE OVER TO LARGER SNOWMELT ZONE 18 GAS MONITORING CONTROL PANEL MOUNTED ON WALL. PROVIDE ARMSTRONG AMC-1AD OR EQUIVALENT. PROVIDE 120V POWER TO PANEL. PANEL SHALL RECEIVE INPUTS FROM CO/NO2 SENSOR AND OVERRIDE ASSOCIATED EXHAUST FAN TO FULL AIRFLOW IN PURGE MODE. 19 ADJUSTABLE SPIN TIMER MOUNTED ON WALL TO CONTROL INDICATED EXHAUST FAN. SPIN TIMER SHALL BE IN PARALLEL WITH GAS DETECTION CONTROL PANEL. 21 PROVIDE NEMA WATERPROOF ENCLOSURE FOR EQUIPMENT INDICATED. 22 TRANSFER AIR OPENING WITH FIRE DAMPER AS INDICATED. INSTALL WITH BOTTOM OF TRANSFER GRILL AT 29'-0" AFF. 20 COMBINATION CO/NO2 GAS SENSOR MOUNT ON WALL AS INDICATED. PROVIDE ARMSTRONG AMC-12222 OR EQUIVALENT. MOUNT SENSORS AT ELEVATION IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR THE SPECIFIC GAS DETECTION AND APPLICATION. INTERLOCK SENSORS TO GAS DETECTION CONTROL PANEL. 23 CPVC FLUE/COMBUSTION AIR OF SIZE INDICATED UP TO MEZZANINE. REFER TO MEZZANINE FLOOR PLAN FOR CONTINUATION. 24 PROVIDE EXPANSION LOOP IN HYDRONIC PIPING IN APPROXIMATE LOCATION INDICATED. 25 6"ø AL29-4C BOILER FLUE. TERMINATE WITH MANUFACTURER'S APPROVED SIDEWALL TERMINATION CAP AS INDICATED. ENSURE ALL MANUFACTURER'S MINIMUM CLEARANCE REQUIREMENTS ARE MAINTAINED. 26 6"ø GALVANIZED BOILER COMBUSTION AIR. INSULATE PER THE SPECIFICATIONS AND TERMINATE WITH DOWNWARD GOOSENECK AS INDICATED. 27 SNOWMELT SUPPLY AND RETURN PIPING ROUTED HIGH ACROSS MEZZANINE. REFER TO MEZZANINE FLOOR PLAN FOR CONTINUATION. 28 MANUFACTURER'S APPROVED SIDEWALL TERMINATION CAP. 29 COORDINATE EXACT SNOWMELT EXTENTS WITH ARCHITECTURAL AND CIVIL SITE PLANS AND CONTROL JOINT SPACING. 30 INSTALL RADIANT HEATER WITH MANUFACTURER'S WIND CLIPS AND PER MANUFACTURER'S WINDY CONDITION INSTALLATION INSTRUCTIONS. INSTALL WITH 45° REFLECTOR ANGLE ANGLED INTO GSE SPACE. REFER TO SECTION ON M2.01 FOR ELEVATION. 31 SNOWMELT SUPPLY AND RETURN PIPING RACKED ON WALL AND DOWN FROM MEZZANINE ABOVE. ROUTE INTO MECHANICAL ROOM AND TO ZONE MANIFOLDS AS INDICATED. CONNECT 2" PIPING TO ZM-4 AND 1-1/4" PIPING TO ZM-5 REFER TO DETAIL FOR MANIFOLD CONNECTION. 32 LINE VOLTAGE THERMOSTAT PROVIDED FOR EACH RADIANT HEATER. PROVIDE A THERMOSTAT WITH AN "OFF" POSITION TO ALLOW FOR EACH HEATER TO BE TURNED OFF, TYPICAL. 33 NOT USED. 34 ELECTRIC UNIT HEATER MOUNTED ON WALL FOR SUPPLEMENTAL HEAT AT WATER AND FIRE ENTRY LOCATION. DIRECT UNIT AT WATER AND FIRE ENTRY. LOCATE THE ASSOCIATED WALL MOUNTED THERMOSTAT PAST FURTHEST WATER ENTRY INTO BUILDING. BTN-1 BTN-1 T GRH-2 T GRH-6 TGRH-7 12 CF-1 11GRH-1 11GRH-2 11GRH-3 11GRH-4 GRH-511 GRH-611 GRH-711 GRH-811 9 9 4"ø FLUE 4"ø FLUE 10 10 EWH-1 13EPO F-11 RG-1 8"ø CD-1 175 CFM TYP. (4) 12x12 RA 12x12 SA 12 x 1 2 S A T Hangar 100 Suite A 105 Suite B 106 Toilet 102 Toilet 103 Jan/Storage 104 Mech 111 Hall 101 Suite C 107 GSE 108 GSE Office 110 IT 109 Boiler 112 EUH-2 T T DFC-17 4"ø FLUE 9 4"ø FLUE10 9 4"ø FLUE10 4"ø FLUE 9 4"ø FLUE10 4"ø FLUE 9 4"ø FLUE 10 4"ø FLUE 9 4"ø FLUE 10 4"ø FLUE 9 4"ø FLUE 10 4"ø FLUE 12CF-2 T GRH-3 1 M2.01 8DCU-1 F-21 RG-1 8"ø CD-1 175 CFM TYP. (4) 12x12 RA 12x12 SA 12 x 1 2 S A F-31 RG-1 8"ø CD-1 175 CFM TYP. (4) 12x12 RA 12x12 SA 12 x 1 2 S A EF-13 EF-23 2F-4 8"ø CD-1A 125 CFM 8"ø CD-1A 125 CFM 12 x 1 2 R A 12 x 1 2 S A 10 x 8 E A 22x8 EA 8x8 EG-2 75 CFM EG-1 150 CFM EG-1 150 CFM 8x8 SG-1 50 CFM 10 x 8 E A 8x 8 E A 5 10x8 EA 8x8 EA 5 62-1/2"ø FLUE & CA TYP. (3) 15 SNOWMELT ZONE 1 SNOWMELT ZONE 3A SNOWMELT ZONE 2 SNOWMELT ZONE 3B 20 ' - 0 " 70' - 0 1/32" 27' - 0" 12 ' - 0 " 20 ' - 0 " 5' - 6 " 5' - 6 " 16 17 30x24 TG-1 TYP.(2) 22 18 $ TO EF-3 Hangar 100 EF-33 9 10 4"ø FLUE 4"ø FLUE 4"ø FLUE 4"ø FLUE EUH-1 T 1921 CO/NO2 CO/NO2 20 20 18"ø EA 18 " ø E A 32x16 LVR-1 T T T EG-1 125 CFM RG-2 RG-2 8"ø CD-1 150 CFM 10"ø CD-1B 250 CFM REFER TO DETAILS FOR PIPING IN THIS ROOM. T 3'-0" MIN. GWH-1 RE: PLBG 232-1/2" CA 2-1/2" FLUE 23 23 23 3"ø CA 3"ø FLUE 6"ø OA UP 30' - 0" 81 ' - 6 " SNOWMELT ZONE 4 SNOWMELT ZONE 5 15 C M 1 12 2 3 4 6 9 10 11 D E F G H I J K LA 5 7 8 B B-1 24 132' - 6" ET-1 GF-1 P-1 AS-1 14ZM-5 14ZM-4 ZM-114 ZM-314 2" SMS 2" SMR 2 1/2" SMS 2 1/2" SMR 2" SMS 2" SMR TO ZM-4 & ZM-5 10' - 0" 25 ' - 6 " 5' - 4" 10' - 0" 25 26 6"ø FLUE 6"ø CA 27 28 18x10 ER-1 450 CFM TYP.(4) GRH-930 29 29 14ZM-2 2" SMR 1" SMS DN. 1" SMR DN. 2" SMR DN. 2" SMS DN. 2" SMS TO EUH-2 S S CF-1 CF-2 T GRH-1 T GRH-4 TGRH-8 T GRH-5 10' - 0" 12CF-3 CF-3 31 2 M2.01 8CU-4 8CU-3 8CU-2 8CU-1 34 32 32 32 32 32 $ 6"ø OA 6"ø OA UP 6"ø OA 6"ø OA UP 6"ø OA UP 4 4 4 4 BTN-1 BTN-1 BTN-1 BTN-1 BTN-1 The Ballard Group, Inc. Mechanical Consulting Engineers 2525 S. Wadsworth Blvd, Suite 200 Lakewood, CO 80227 (303) 988-4514 Consultant Seal Project Title Project Description Revision Log Issue Date Tectonic Project Number Issue Title Sheet Title Sheet Number Approved By Revision Date Al l D r a w i n g s A n d W r i t t e n M a t e r i a l A p p e a r i n g H e r e i n C o n s t i t u t e O r i g i n a l A n d Un p u b l i s h e d W o r k O f T h e D e s i g n e r A n d M a y N o t B e D u p l i c a t e d , U s e d , O r Di s c l o s e d W i t h o u t W r i t t e n C o n s e n t F r o m T e c t o n i c M a n a g e m e n t G r o u p , I n c . Drawn By 6/ 1 4 / 2 0 2 3 3 : 3 3 : 5 6 P M C: \ U s e r s \ p f a i l l a \ D o c u m e n t s \ 2 2 0 7 9 _ H V A C _ R 2 1 _ P F a i l l a . r v t M2.00 First Floor HVAC Plan 100% Construction Documents 202199 01/20/2023 AAS-RIL, Hgr 6 Rifle Garfield County Airport Rifle, CO At l a n t i c A v i a t i o n - Ri f l e H a n g a r 6 PWF JJG N SCALE: 1/8" = 1'-0" HVAC Floor Plan - Level 1 BTN-1 06-16-23 6/16/2023 Page 14 of 19 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 12 3 4 1 1 2 3 4 5 C 1 12 2 3 4 6 9 10 11 A 5 7 8 B REFER TO M2.00 FOR WORK IN THIS AREA. T ECUH-14 12 " ø S A 3"ø FLUE 3"ø CA 2" SMS 2" SMR 2" SMS 2" SMR 2" SMS 2" SMR 2-1/2" CA 2-1/2" FLUE 1 1 1 1 2 2 3 3 5 6x40 SA 24x18 TG-1 TYP.(2) 7 6 24x18 TA Mezzanine Storage 113 12x6 SG-2 125 CFM TYP.(4) 8 6"ø OA DN. M 8 M M 8 8 M 9 9 9 9 6"ø RA DN. 6"ø OA DN. 6"ø OA DN. BTN-1 BTN-1 BTN-1 BTN-1 MEZZANINE HVAC KEYNOTES: CPVC FLUE/COMBUSTION AIR OF SIZE INDICATED TO UP THROUGH ROOF. INSTALL AND TERMINATE PER MANUFACTURER'S RECOMMENDATIONS AND MAINTAINING MANUFACTURER'S REQUIRED CLEARANCES. ENSURE THE TERMINATIONS ARE A MINIMUM OF 24" ABOVE THE ROOF LEVEL. 1 ROUTE PIPING HIGH ACROSS MEZZANINE. RACK PIPING ON WALL NEAR FLUE AND COMBUSTION AIR AND DOWN. REFER TO M2.00 FOR CONTINUATION. 2 ELECTRIC CABINET UNIT HEATER MOUNTED ON MEZZANINE FLOOR. REFER TO SCHEDULE FOR SIZE AND CAPACITY. DUCT FROM CABINET UNIT HEATER DISCHARGE INTO PLENUM SPACE ABOVE OFFICES AND HVAC EQUIPMENT SERVING THE OFFICES AS INDICATED. 4 THERMOSTAT FOR ELECTRIC CABINET UNIT HEATER, ECUH-1, MOUNTED ABOVE OFFICE CEILING. MOUNT A MAXIMUM OF 2'-0" ABOVE THE CEILING SO IT IS ACCESSIBLE FROM THE CEILING BELOW. 5 ROUTE PIPING HIGH ACROSS MEZZANINE AND INTO HANGAR. REFER TO M2.00 FOR CONTINUATION.3 TRANSFER GRILLE OF SIZE INDICATED MOUNTED WITH BOTTOM AT 8'-0" AFF.6 TRANSFER DUCTWORK OF SIZE INDICATED OPEN ENDED INTO PLENUM SPACE. PROVIDE WITH 1/2" BIRDSCREEN OVER OPEN END. 7 ALUMINUM WALL CAP WITH BIRDSCREEN AND NO BACKDRAFT DAMPER. SET JUST ABOVE AWNING.8 120V MOTORIZED DAMPER. REFER TO SEQUENCE OF OPERATION FOR CONTROL. 9 BTN-1 Floor Plan 100' -0" Eave Height 138' -0" T.O. Hangar Door Joint 130' -0" Mezzanine 112' -0" Low Eave 136' -9 1/16" Ridge 142' -5 1/16" B.O. Hangar Door Opening 128' -6" MDEFGHIJKL GRH-1 CF-1 GRH-2 GRH-3 CF-2 GRH-4 31 ' - 0 " 32 ' - 6 " 31 ' - 0 " 31 ' - 0 " 32 ' - 6 " 31 ' - 0 " Hangar 100 Floor Plan 100' -0" Eave Height 138' -0" T.O. Hangar Door Joint 130' -0" Mezzanine 112' -0" Low Eave 136' -9 1/16" Ridge 142' -5 1/16" B.O. Hangar Door Opening 128' -6" CAB CF-3 18"ø EA GRH-9 18x10 ER-1 450 CFM TYP.(4) 28 ' - 0 " 28 ' - 0 " GSE 108 The Ballard Group, Inc. Mechanical Consulting Engineers 2525 S. Wadsworth Blvd, Suite 200 Lakewood, CO 80227 (303) 988-4514 Consultant Seal Project Title Project Description Revision Log Issue Date Tectonic Project Number Issue Title Sheet Title Sheet Number Approved By Revision Date Al l D r a w i n g s A n d W r i t t e n M a t e r i a l A p p e a r i n g H e r e i n C o n s t i t u t e O r i g i n a l A n d Un p u b l i s h e d W o r k O f T h e D e s i g n e r A n d M a y N o t B e D u p l i c a t e d , U s e d , O r Di s c l o s e d W i t h o u t W r i t t e n C o n s e n t F r o m T e c t o n i c M a n a g e m e n t G r o u p , I n c . Drawn By 6/ 1 4 / 2 0 2 3 3 : 3 3 : 5 8 P M C: \ U s e r s \ p f a i l l a \ D o c u m e n t s \ 2 2 0 7 9 _ H V A C _ R 2 1 _ P F a i l l a . r v t M2.01 Mezzanine HVAC Plan & Sections 100% Construction Documents 202199 01/20/2023 AAS-RIL, Hgr 6 Rifle Garfield County Airport Rifle, CO At l a n t i c A v i a t i o n - Ri f l e H a n g a r 6 PWF JJG BTN-1 06-16-23 SCALE: 1/8" = 1'-0" HVAC Floor Plan - Mezzanine SCALE: 1/8" = 1'-0"M2.01 1 HANGAR SECTION N SCALE: 1/8" = 1'-0"M2.01 2 GSE SECTION 6/16/2023 Page 15 of 19 CONDENSING UNIT SCHEDULE PLAN MANUFACTURER NOM AMBIENT ELECTRICAL DIMENSIONS OPER. CODE & MODEL NO. TONS SEER TEMP VOLT Ø MCA MOCP H L W WEIGHT REMARKS CU-1 CARRIER 24AAA524 2.0 15.0 95 208/230 1 14.1 20.0 33'' 26'' 24'' 175 NOTES: 1,2,3 CU-2 CARRIER 24AAA524 2.0 15.0 95 208/230 1 14.1 20.0 33'' 26'' 24'' 175 NOTES: 1,2,3 CU-3 CARRIER 24AAA524 2.0 15.0 95 208/230 1 14.1 20.0 33'' 26'' 24'' 175 NOTES: 1,2,3 CU-4 CARRIER 24AAA524 2.0 15.0 95 208/230 1 14.1 20.0 33'' 26'' 24'' 175 NOTES: 1,2,3 NOTES: 1. UNIT MOUNTED ON MINIMUM 4" THICK CONCRETE HOUSEKEEPING PAD. 2. PROVIDE WITH HAIL GUARDS. 3. PROVIDE WITH LOCKING REFRIGERANT CAPS. DUCTLESS CONDENSING UNIT SCHEDULE PLAN MANUFACTURER NOM AMBIENT ELECTRICAL DIMENSIONS OPER. CODE & MODEL NO. TONS SEER TEMP REFRIG. VOLT PHASE MCA MOCP W D H WEIGHT REMARKS DCU-1 CARRIER 38MPRAQ24 2 23.5 100 R-410A 208 1 20.0 30.0 38'' 17'' 31'' 175 NOTE: 1,2,3 NOTES: 1. PROVIDE WITH LOW AMBIENT COOLING KIT TO -20°F. 2. PROVIDE WITH WIND BAFFLES AND HAIL GUARDS. 3. UNIT MOUNTED ON MINIMUM 3" THICK CONCRETE HOUSEKEEPING PAD. DUCTLESS FAN COIL UNIT SCHEDULE NOM SIZE (INCHES) OPER. PLAN MANUFACTURER & CAP VOLTS/ MCA/ WT. CODE MODEL NUMBER MOUNTING (MBH) CFM PHASE MOCP W H D (LBS) REMARKS DFC-1 CARRIER 40MPHAQ24 WALL 24 700 - - 50'' 15'' 12'' 50 NOTE: 1,2 NOTES: 1. UNIT POWERED THROUGH OUTDOOR UNIT VIA 208/1 WIRING. 2. PROVIDE WITH HARD WIRED THERMOSTAT AND DRAIN PAN LEVEL SENSOR. FAN SCHEDULE PLAN MANUFACTURER CFM ESP RPM MOTOR WT DAMPER CODE & MODEL NO. TYPE SONES (5,300 FT) (5,300 FT) HP (FLA) V/Ø (LBS) CONTROL TYPE REMARKS EF-1 GREENHECK SQ-98-VG INLINE 12.8 375 0.75'' 1,717 1/4 120/1 75 NOTE: A GRAVITY NOTE: 1 EF-2 GREENHECK SQ-97-VG INLINE 12.5 125 0.75'' 1,696 1/4 120/1 75 NOTE: C GRAVITY NOTE: 1 EF-3 GREENHECK SQ-160-VG INLINE 7.9 1,800 0.50'' 955 3/4 120/1 175 NOTE: D GRAVITY NOTE: 1 CF-1 MACRO AIR AV18 HVLS - - - 70 1.0 (4.3) 480/3 250 NOTE: B - NOTE: 2,3,4 CF-2 MACRO AIR AV18 HVLS - - - 70 1.0 (4.3) 480/3 250 NOTE: B - NOTE: 2,3,4 CF-3 MACRO AIR AVD06 HVLS - - - 164 3/4 (3.7) 120/1 100 NOTE: B - NOTE: 3,4,5 NOTES: 1. PROVIDE WITH SPEED CONTROLLER MOUNTED AT FAN FOR BALANCING.A. TIME CLOCK BY ELECTRICAL. 2. 18 FT DIAMETER.B. MANUFACTURER DIGITAL WALL CONTROLLER WITH ON/OFF OVERRIDE AND SPEED CONTROL. 3. PROVIDE WITH VFD AND DISCONNECT.C. WALL SWITCH WITH SPIN TIMER. 4. PROVIDE WITH REMOTE FIRE ALARM SHUTDOWN.D. CO/NO2 GAS DETECTION CONTROL PANEL AND WALL SWITCH WITH SPIN TIMER. 5. 6 FT DIAMETER. ELECTRIC HEATER SCHEDULE PLAN ELECTRICAL GRILLE DIMENSIONS CODE MANUFACTURER & MODEL NO. VOLTS Ø WATTS CFM GAUGE MOUNTING TYPE H L W REMARKS EWH-1 MARKEL F30522TDWB 208 1 1,000 100 18 RECESSED SURFACE 13'' 10'' 4'' NOTE: 1,2 EUH-1 MARKEL P3PUH05 480 3 5,000 400 18 HORIZ 13'' 20'' 11'' NOTE: 2,3,4 EUH-2 MARKEL P3PUH05 480 3 3,300 400 18 HORIZ 13'' 20'' 11'' NOTE: 2,3,4 ECUH-1 MARKEL 6333 480 3 10,000 500 18 VERTICAL 25'' 46'' 9''NOTE: 2,4,5,6,7 NOTES: 1. WITH INTEGRAL THERMOSTAT. 2. WITH UNIT MOUNTED DISCONNECT. 3. PROVIDE WITH WALL/CEILING BRACKET. 4. PROVIDE WITH 24V WALL THERMOSTAT AND TRANSFORMER FOR 24V REMOTE THERMOSTAT. 5. PROVIDE UNIT AS FRONT INLET AND TOP DISCHARGE CONFIGURATION. PROVIDE STAMPED FRONT INLET GRILLE AND DUCT COLLAR ON THE TOP DISCHARGE. 6. PROVIDE UNIT WITH SUMMER FAN SWITCH. 7. DISABLE UNITS SECOND STAGE HEATING. LIMIT UNIT TO FIRST STAGE OF HEATING AT 6,000 W. FURNACE AND SPLIT SYSTEM COOLING COIL SCHEDULE FURNACE COOLING COIL MATCHING MIN HEATING CAPACITY SUPPLY FAN COOLING COIL ELECTRICAL FILTER DIMENSIONS WITHOUT COIL PLAN MANUFACT. MANUFACT. SERVICE A.C. CFM ESP O.A. EAT LAT MBH MBH HP RPM TYPE REFRIG. COIL TOT. SENS. EAT LAT DAT V/ø/HZ AMP. MOCP EFF. W L H SA RA FLUE/ WT. CODE & MODEL NO.UNIT (IN) CFM INPUT OUTPUT TON (MBH) (MBH) DB WB DB WB DB (IN) (IN) (IN) (IN) (IN) CA (LBS) REMARKS (SL) (5,300') F-1 CARRIER 59SP5A040-10 CARRIER SUITE C CU-1 700 0.90 75 60.0 110.9 40.0 31.7 1/2 - DIRECT R-410 2.5 17.0 16.4 80.3 59.5 54.1 49.8 55.0 120/1/60 11.0 15.0 30% 30'' 36'' 15'' 20"x20" 22"x20" 2-1/2" 225 NOTES: 1,2,3,4,5,6,7,8,9,10,12 F-2 CARRIER 59SP5A040-10 CARRIER SUITE B CU-2 700 0.90 75 60.0 110.9 40.0 31.7 1/2 - DIRECT R-410 2.5 17.0 16.4 80.3 59.5 54.1 49.8 55.0 120/1/60 11.0 15.0 30% 30'' 36'' 15'' 20"x20" 22"x20" 2-1/2" 225 NOTES: 1,2,3,4,5,6,7,8,9,10,12 F-3 CARRIER 59SP5A040-10 CARRIER SUITE A CU-3 700 0.90 75 60.0 110.9 40.0 31.7 1/2 - DIRECT R-410 2.5 17.0 16.4 80.3 59.5 54.1 49.8 55.0 120/1/60 11.0 15.0 30% 30'' 36'' 15'' 20"x20" 22"x20" 2-1/2" 225 NOTES: 1,2,3,4,5,6,7,8,9,10,12 F-4 CARRIER 59SP5A040-10 CARRIER OFFICE 110 CU-4 700 0.90 75 60.0 110.9 40.0 31.7 1/2 - DIRECT R-410 2.5 17.0 16.4 80.3 59.5 54.1 49.8 55.0 120/1/60 11.0 15.0 30% 15'' 30'' 36'' 20"x20" 22"x20" 2-1/2" 225 NOTES: 1,2,3,4,5,6,8,9,10,11,12 NOTES: 1. PROVIDE COIL WITH THERMOSTATIC EXPANSION VALVE.6. PROVIDE WITH CONDENSATE NEUTRALIZATION KIT.11. PROVIDE IN VERTICAL CONFIGURATION FOR FLOOR MOUNTING. 2. PROVIDE WITH HIGH ALTITUDE KIT.7. PROVIDE IN HORIZONTAL CONFIGURATION FOR ABOVE CEILING MOUNTING.12. PROVIDE WITH SECONDARY DRAIN OVERFLOW SWITCH 3. PROVIDE FLEXIBLE DUCT CONNECTIONS AT UNIT INLET AND OUTLET.8. MINIMUM NATURAL GAS INLET PRESSURE 4.5" WC, MAXIMUM 13.6" WC. 4. PROVIDE FILTER RACK IN RETURN AIR DUCT.9. PROVIDE WITH ECM MULTIPLE-SPEED BLOWER MOTOR. 5. LISTED ESP ASSUMES FILTER PRESSURE LOSS AND DX COOLING COIL EXTERNAL TO THE FURNACE.10. PROVIDE WITH 7-DAY, AUTO CHANGEOVER, PROGRAMMABLE THERMOSTAT. GRILLES, REGISTERS & DIFFUSERS SCHEDULE NECK FACE VOLUME PLAN MANUFACTURER TYPE & SIZE SIZE DAMPER MOUNTING CODE & MODEL NO. SERVICE (IN) (IN) (OBD) MATERIAL TYPE FINISH REMARKS CD-1 PRICE SMDA SUPPLY AS NOTED 24"x24" NO STEEL LAY-IN WHITE NOTE: 1,2 CD-1A PRICE SMDA SUPPLY AS NOTED 24"x24" NO STEEL LAY-IN WHITE NOTE: 1,2,3 CD-1B PRICE SMDA SUPPLY AS NOTED 24"x24" NO STEEL LAY-IN WHITE NOTE: 1,2,4 SG-1 PRICE 520 SUPPLY AS NOTED NECK + 1.75" NO STEEL SURFACE BY ARCH. SG-2 PRICE HCD1 SUPPLY AS NOTED NECK + 2.375" NO STEEL SPIRAL DUCT BY ARCH. NOTE: 5 TG-1 PRICE 530 TRANSFER AS NOTED NECK + 1.75" NO STEEL SURFACE BY ARCH. EG-1 PRCE PDDR EXHAUST 10"x22" 12"x24" NO STEEL LAY-IN WHITE EG-2 PRICE 530 EXHAUST AS NOTED NECK + 1.75" NO STEEL SURFACE BY ARCH. ER-1 PRICE HCD1 EXHAUST AS NOTED NECK + 2.375" YES STEEL SPIRAL DUCT BY ARCH. NOTE: 5 RG-1 PRCE PDDR RETURN 22"x22" 24"x24" NO STEEL LAY-IN WHITE RG-2 PRCE PDDR RETURN 10"x22" 12"x24" NO STEEL LAY-IN WHITE NOTES: 1. ADJUSTABLE. 2. PROVIDE WITH 18"x18" LOUVERED FACE. 3. PROVIDE WITH TWO WAY CORNER THROW AS INDICATED ON DRAWINGS. 4. PROVIDE WITH TWO WAY OPPOSITE THROW AS INDICATED ON DRAWINGS. 5. PROVIDE WITH SPIRAL DUCT FRAME MOUNTING KIT. RADIANT TUBE HEATER SCHEDULE ELECTRICAL PLAN MANUFACTURER. & MBH INPUT U-TUBE WEIGHT CODE MODEL NO. @ 5,300 FT LENGTH LB REFLECTOR VOLTS/Ø FLA REMARKS GRH-1 SOLARONICS STU175-60CN 175 33'-4" 450 ALUM 120/1 1.3 NOTE: 1,2,3,4,5,6 GRH-2 SOLARONICS STU175-60CN 175 33'-4" 450 ALUM 120/1 1.3 NOTE: 1,2,3,4,5,6 GRH-3 SOLARONICS STU175-60CN 175 33'-4" 450 ALUM 120/1 1.3 NOTE: 1,2,3,4,5,6 GRH-4 SOLARONICS STU175-60CN 175 33'-4" 450 ALUM 120/1 1.3 NOTE: 1,2,3,4,5,6 GRH-5 SOLARONICS STU175-60CN 175 33'-4" 450 ALUM 120/1 1.3 NOTE: 1,2,3,4,5,6 GRH-6 SOLARONICS STU175-60CN 175 33'-4" 450 ALUM 120/1 1.3 NOTE: 1,2,3,4,5,6 GRH-7 SOLARONICS STU175-60CN 175 33'-4" 450 ALUM 120/1 1.3 NOTE: 1,2,3,4,5,6 GRH-8 SOLARONICS STU175-60CN 175 33'-4" 450 ALUM 120/1 1.3 NOTE: 1,2,3,4,5,6 GRH-9 SOLARONICS STU150-70CN 150 38'-4" 500 ALUM 120/1 1.3 NOTE: 1,2,3,4,5,6,7 NOTES: 1. MINIMUM NATURAL GAS INLET PRESSURE 7" WC. MAXIMUM INLET PRESSURE 14" WC. 2. SINGLE STAGE HEATING. 3. PROVIDE WITH HORIZONTAL WALL VENT KIT TERMINATION. 4. PROVIDE WITH 120 VOLT WALL THERMOSTAT WITH "OFF" POSITION TO ALLOW HEATER TO BE DISABLED. 5. PROVIDE WITH MANUFACTURER'S WIND CLIPS AND INSTALL PER MANUFACTURER'S WINDY CONDITIONS INSTRUCTIONS. 6. PROVIDE WITH MANUFACTURER'S HIGH ALTITUDE KIT. 7. PROVIDE WITH MANUFACTURER'S 45° REFLECTOR ANGLE. LOUVER SCHEDULE PLAN MANUFACTURER SERVICE FREE CFM VEL. A.P.D. MATERIALS SIZE REMARKS CODE & MODEL NO. AREA (FPM) (IN. W.C.) (INCHES) (SQ. FT.)W H D LVR-1 RUSKIN ELF 375 DX EF-3 EXHAUST 1.9 1,800 938 0.19 NOTE: 1 32'' 16'' 4'' NOTE: 2 NOTES: 1. PROVIDE LOUVER WITH 70% PVDF FINISH. COLOR SELECTION BY ARCHITECT. 2. PROVIDE LOUVER WITH 1/2" BIRDSCREEN. The Ballard Group, Inc. Mechanical Consulting Engineers 2525 S. Wadsworth Blvd, Suite 200 Lakewood, CO 80227 (303) 988-4514 Consultant Seal Project Title Project Description Revision Log Issue Date Tectonic Project Number Issue Title Sheet Title Sheet Number Approved By Revision Date Al l D r a w i n g s A n d W r i t t e n M a t e r i a l A p p e a r i n g H e r e i n Co n s t i t u t e O r i g i n a l A n d Un p u b l i s h e d W o r k O f T h e D e s i g n e r A n d M a y N o t B e D u p li c a t e d , U s e d , O r Di s c l o s e d W i t h o u t W r i t t e n C o n s e n t F r o m T e c t o n i c M a n ag e m e n t G r o u p , I n c . Drawn By 1/ 2 0 / 2 0 2 3 8 : 3 4 : 1 1 A M C: \ U s e r s \ p f a i l l a \ D o c u m e n t s \ 2 2 0 7 9 _ H V A C _ R 2 1 _ P F a i l l a . r vt M5.00 HVAC Schedules 100% Construction Documents 202199 01/20/2023 AAS-RIL, Hgr 6 Rifle Garfield County Airport Rifle, CO At l a n t i c A v i a t i o n - Ri f l e H a n g a r 6 PWF JJG 1/20/2023 Page 16 of 19 AIR/DIRT/HYDRAULIC SEPARATOR SCHEDULE PLAN MANUFACTURER SYSTEM GPM WPD STRAINER PIPE DIMENSIONS (NOTE: 2) WEIGHT REMARKS CODE & MODEL NO. (FT) CONN. SIZE HEIGHT DIA. LENGTH (LBS) AS-1 SPIROTHERM VDN300 SNOWMELT 96.0 5.0 YES 3.0'' 32'' 9''21'' 250 NOTE: 1,2,3 NOTES: 1. SYSTEM UTILIZES 50% PROPLYENE GLYCOL. 2. LENGTH DIMENSION IS FLANGE TO FLANGE CONNECTION DISTANCE. 3. PROVIDE WITH REMOVABLE LOWER HEAD FOR CLEANING. 96.01,150 15:1 110.0 140.0 CONDENSING WATER BOILER SCHEDULE MBH HEATNG WATER ASME WATER SIZE (IN) OPER PLAN MANUFACT. SERVICE INPUT OUTPUT TURN VOLUME (PSIG) OPER VOLT/ FLA EWT LWT FLOW % WPD L W H FLUE/CA WT. REMARKS CODE & MODEL NO. S.L. (5,300') DOWN (GAL) RATING PSIG ø/HZ (°F) (°F) (GPM) P.G. (FT) (ø) (LBS) B-1 RIELLO ARRAY 1500 HEATING 1,500 18 75.0 50.0 120/1/60 23.3 50 5.0 61'' 34'' 68'' 6" / 6" 1,600 NOTES: 1,2,3,4,5,6 NOTES: 1. BOILER SHALL BE MODULATED BY FACTORY SUPPLIED BOILER PLANT CONTROL PANEL. 5. MOUNT BOILER ON MASON INDUSTRIES SUPER W WAFFLE PAD. REFER TO DETAIL. 2. FM GAS TRAIN RATED FOR 3.5" TO 13.5" GAS INLET PRESSURE. 6. PROVIDE BOILER WITH HIGH ALLTITUDE KIT. 3. PROVIDE CONDENSING BOILER WITH FACTORY CONDENSATE NEUTRALIZATION KIT. 4. PROVIDE WITH 50 PSI RELIEF VALVE MOUNTED ON HEATING WATER RETURN PIPING. EXPANSION TANK SCHEDULE PLAN MANUFACTURER SERVICE TANK ACCEPT. SYSTEM MAX. AVERAGE MIN. OPER. MAX. OPER. TANK SIZE OPER. CODE & MODEL NO. VOLUME VOLUME VOLUME EWT TEMPERATURE PRESSURE PRESSURE DIA. HT. WEIGHT REMARKS ET-1 ARMSTRONG A300-L SNOWMELT 80.0 80.0 500.0 40.0 140.0 18.0 45.0 24'' 53'' 1,000 NOTE: 1,2,3 NOTES: 1.SNOWMELT SYSTEMS CONTAINS 50% PROPLYENE GLYCOL.3.ASME PRESSURE RATING EQUALS 125 PSI. 2.SYSTEM VOLUME IS TOTAL VOLUME. GLYCOL FEEDER SCHEDULE SYSTEM PUMP TANK UNIT "ON" UNIT "OFF" SYSTEM TANK OPER. PLAN MANUF. & FLOW HEAD MOTOR SIZE PRESSURE PRESSURE ELECTRICAL P.G. UNIT SIZE WT. CODE MODEL NO. SERVICE (GPM) (PSI) WATTS (GAL) (PSI) (PSI) REQUIREMENTS (%) L W H (LBS) REMARKS GF-1 AXIOM MF-200 SNOWMELT 0.7 25.0 50 W 6.6 10.0 25.0 NOTE: 1 50.0 12'' 12'' 16" 160 NOTE: 2,3,4,5 NOTES: 1. PROVIDE A DEDICATED 120/1/60 20 AMP CIRCUIT WITH A GFI RECEPTACLE LOCATED 3. SYSTEM PUMP SHALL BE BRONZE ROTARY GEAR TYPE. WITHIN 3 FEET OF AND BEHIND UNIT. 4. PROVIDE FLOAT SWITCH FOR LOW LEVEL PUMP SHUTOFF AND AUDIBLE ALARM. 2. TANK SHALL BE POLYETHYLENE MOUNTED IN A STEEL FRAME. 5. PROVIDE NEMA 4X UNIT CONTROL PANEL. PUMP SCHEDULE ELECTRICAL PLAN MANUFACTURER HP WEIGHT CODE & MODEL NO. TYPE SERVICE GPM HEAD (BHP) VOLTS Ø RPM CONTROL (LBS) REMARKS P-1 ARMSTRONG 4300 - 2x2x8 INLINE SNOWMELT 96.0 60.0 5.0 (2.4) 208 3 1,800 NOTE: 1 300 NOTE: 2 NOTES: 1. PUMP SHALL BE STARTED THROUGH THE SNOWMELT CONTROLLER. REFER TO SEQUENCE. 2. VFD PROVIDED FOR BALANCING AND SOFT START ONLY. PUMP SHALL RUN AT CONSTANT SPEED. SNOWMELT SYSTEM HEATING SCHEDULE TOTAL HTG OUTPUT HTG OUTPUT TUBING TUBE LEADER AVG. TUBE FLOW/ TOTAL MAX PRESSURE ZONE NAME AREA AREA HTG OUTPUT TOTAL UPWARD SIZE SPACING LENGTH NUMBER OF LENGTH/LOOP LOOP ZONE FLOW LOSS W/MANIFOLD (ZONE MANIFOLD) SERVED (SF) (BTUH/SF) (BTUH) (BTUH) (IN) (IN) (FT) LOOPS (FT) (GPM) (GPM) (FT HEAD) REMARKS ZONE 1 (ZM-1) SNOWMELT 2,610 137 388,800 357,800 3/4 9 10 11 331 2.6 29.0 30.0 NOTE: 1,2,3 ZONE 2 (ZM-2) SNOWMELT 510 137 75,500 69,700 3/4 9 10 4 195 1.5 6.0 30.0 NOTE: 1,2,4 ZONE 3A (ZM-3) SNOWMELT 1,670 137 249,300 229,300 3/4 9 10 7 340 2.7 19.0 30.0 NOTE: 1,2,3 ZONE 3B (ZM-3) SNOWMELT 510 136 75,300 69,500 9 10 4 200 1.5 6.0 ZONE 4 (ZM-4) SNOWMELT 2,445 137 365,000 335,600 3/4 9 10 11 320 2.5 28.0 30.0 NOTE: 1,2,3 ZONE 5 (ZM-5) SNOWMELT 820 137 121,812 112,000 3/4 9 10 4 270 2.5 10.0 30.0 NOTE: 1,2,4 NOTES: 1. HEAT OUTPUT BASED ON 140°F EWT, 110°F LWT, 50% PROPYLENE GLYCOL. 0°F AMBIENT, 10 MPH WIND SPEED, 36°F SLAB TEMPERATURE. 4. MANIFOLD TO BE UPONOR TRUFLOW CLASSIC WITH BALL AND BALANCING VALVES OR PRIOR APPROVED EQUAL. 2. RIGID INSULATION UNDER AND AT PERIMETER OF HEATED SLAB (MINIMUM R-10) BY GC. 3. MANIFOLD TO BE UPONOR 2" COPPER PROPEX WITH BALL AND BALANCING VALVES OR PRIOR APPROVED EQUAL. BTN-1 The Ballard Group, Inc. Mechanical Consulting Engineers 2525 S. Wadsworth Blvd, Suite 200 Lakewood, CO 80227 (303) 988-4514 Consultant Seal Project Title Project Description Revision Log Issue Date Tectonic Project Number Issue Title Sheet Title Sheet Number Approved By Revision Date Al l D r a w i n g s A n d W r i t t e n M a t e r i a l A p p e a r i n g H e r e i n Co n s t i t u t e O r i g i n a l A n d Un p u b l i s h e d W o r k O f T h e D e s i g n e r A n d M a y N o t B e D u p li c a t e d , U s e d , O r Di s c l o s e d W i t h o u t W r i t t e n C o n s e n t F r o m T e c t o n i c M a n ag e m e n t G r o u p , I n c . Drawn By 6/ 1 4 / 2 0 2 3 3 : 3 3 : 5 8 P M C: \ U s e r s \ p f a i l l a \ D o c u m e n t s \ 2 2 0 7 9 _ H V A C _ R 2 1 _ P F a i l l a . r vt M5.01 HVAC Schedules 100% Construction Documents 202199 01/20/2023 AAS-RIL, Hgr 6 Rifle Garfield County Airport Rifle, CO At l a n t i c A v i a t i o n - Ri f l e H a n g a r 6 PWF JJG BTN-1 06-16-23 6/16/2023 Page 17 of 19 FIRE DAMPER DETAILTYPICAL PIPE HANGER DETAIL DUCT STRAP HANGER DETAIL SNOWMELT MANIFOLD DETAILIN-LINE PUMP DETAIL BRANCH DUCT TAKE-OFF DETAIL RADIANT TUBING DETAIL RADIANT TUBING AT JOINTS UPFLOW FURNACE DETAIL HORIZONTAL FURNACE DETAILDX COIL PIPING DETAIL RADIANT TUBING UNDER DOOR TRACK DETAIL IN-LINE CENTRIFUGAL FAN DETAIL EXPANSION TANK AND AIR/DIRT/HYDRAULIC SEPARATOR PIPING DETAIL CHEMICAL POT FEEDER DETAIL GLYCOL FEEDER DETAIL PIPING DETAIL - CONDENSING BOILER 60" 48" 36" 8'-0" 8'-0" 8'-0" 8'-0"1-1/2"x1-1/2"x1/8"1/4" ROUND ROD 2"x2"x1/8" 2"x2"x1/8" 2"x2"x1/8" 5/16" ROUND ROD 1" HANGER STRAPS NO POP RIVETS ALLOWED TOP CORD OF TRUSS 1/4"∅x1-1/4" HEX HEAD LAG BOLT HANGER SIZES FOR RECTANGULAR DUCT MAX. SIZE HANGER HORIZONTAL SUPPORT ANGLE MAXIMUM SPACING 30" 1"x18" GAGE STRAP SELF TAPPING CADMIUM PLATED HEX HEAD SHEET METAL SCREW STRAPS TO BE TIGHT AGANIST THE DUCT. NONE REQUIRED 10'-0" 84" 1/4" ROUND ROD 3/8" ROUND ROD HOSE END DRAIN VALVE WITH MANUAL AIR VENT END CAP REFER TO SNOWMELT MANIFOLD ZM-_: SYSTEM HEATING SMS BALL VALVE (TYP.) SMR SCHEDULE FOR NUMBER OF LOOPS hePEX TUBING SEE SCHEDULE FOR SIZE PRESSURE GAUGE FULL SIZE OF P&T (TYP.) CHECK VALVE PRESSURE GAUGE BALANCE VALVE WITH INLINE PUMP. REFER NOTES: 1. ON BOTH SIDES OF PUMP, INSTALL PIPE HANGER. 2. PROVIDE UNIONS ON BOTH SIDES OF PUMP WHERE MANUFACTURER DOES NOT PROVIDE FLANGE. (TYP.) BALL VALVE STRAINER WITH HOSE END DRAIN TO SCHEDULE FOR SIZE AND CAPACITIES. SRING ISOLATION HANGER, TYP SEE PLANS & SERVICES FOR PIPE SIZES FLOW METER FITTING, REFER TO SPEC.REQUIRED (TYP.) ECCENTIC REDUCER/ INCREASER AS 3/4" 3. WET ROTOR TYPE PUMPS MUST HAVE MOTOR SHAFT ORIENTED HORIZONTALLY. REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS. L W 45° L=1/4 W (4" MIN.) NOTE: NEAR CONCRETE JOINTS. INFORMATION FOR INSTALLATION NOTE: REFER TO RADIANT TUBING AT JOINTS DETAIL FOR ADDITIONAL SUB SOIL PEX TUBING WIRE MESH OR REBAR BY G.C. CONCRETE SLAB 6" DEEP GRAVEL BASE VERTICAL RIGID EDGE INSULATION MIN. R-10 BY G.C. CONTROL JOINT CONTROL JOINT SECURE TUBING TO MESH/REBAR AT 6" ON EACH SIDE OF CONTROL JOINT EXPANSION JOINT WRAP TUBING WITH PIPE INSULATION. EXTEND PIPE INSULATION MIN. 6" ON EACH SIDE OF EXPANSION JOINT. CONSTRUCTION JOINT ROUTE TUBING BELOW SLAB INTO THE SUBSOIL AT CONSTRUCTION JOINT CONSTRUCTION JOINT EXPANSION JOINT BALANCING VALVE, TYP FURNACE DX COIL RETURN DUCT. REFER TO PLANS SUPPLY DUCT. REFER TO PLANS FOR SIZE. CPVC INTAKE AND VENT PIPING. REFER TO FURNACE SCHEDULE FOR SIZES. 3/4" PVC DRAIN PIPING TO DRAIN REFER TO PLUMBING DRAWINGS. FLEXIBLE DUCT CONNECTOR, FOR SIZE. ROUTE REFRIGERANT PIPING TO CONDENSING UNIT. TYPICAL ANGLED FILTER IN RACK FLOOR SIZE IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. FURNACE DX COIL RETURN DUCT. REFER TO PLANS SUPPLY DUCT. REFER TO PLANS FOR SIZE. CPVC INTAKE AND VENT PIPING. REFER TO FURNACE SCHEDULE FOR SIZES. POLY TUBING FLEXIBLE DUCT CONNECTOR, FOR SIZE. ROUTE REFRIGERANT PIPING TO CONDENSING UNIT. SIZE IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. TYPICAL CEILING 3/4" PVC DRAIN PIPING TO DRAIN REFER TO PLUMBING DRAWINGS. CONDENSATE NEUTRALIZATION KIT POLY TUBING TO FLOOR DRAIN OUTSIDE AIR DUCT. REFER TO PLANS FOR SIZE. FILTER IN FILTER RACK45° SUCTION LINE SIGHT GLASS FILTER DRIER STRAINER EXPANSION VALVE SOLENOID VALVE (TYP.)LIQUID LINE REFRIGERATION STOP VALVES 1. SHALL BE SUBMITTED FOR APPROVAL PRIOR TO STARTING WORK. REFRIGERANT PIPING LAYOUT, INCLUDING SIZES, ROUTING, SPECIALTIES, ETC. NOTES: DX COOLING COIL (TYP.) TO CONDENSING UNIT RE: MFG FOR NUMBER OF COIL CONNECTIONS POSSIBLE TO COIL OUTLET. BOTTOM OF PIPE AS CLOSE AS THERMAL BULB, LOCATE 45° ABOVE EQUALIZER LINE TEV CONTROL 2. BOARD. INSTALL PER CONDENSING UNIT & VALVE MANUFACTURER'S INSTALLATION GUIDES. PROVIDE ELECTRONIC HOT GAS BYPASS (SPORLAN SDR) VALVE AND TEMP. CONTROL RS RL SPRING ISOLATION HANGER (TYP.) THREADED STEEL HANGER ROD (TYP.) (BY M.C.) (BY M.C.) LOCKABLE SURFACE MOUNTED MANIFOLD CABINET BY MECHANICAL EXPANSION JOINT AND SEALANT REFER TO ARCHITECTURAL PLANS. CONCRETE SLAB ON GRADE STEEL RAIL BY HANGER DOOR MANUFACTURER. REFER TO CONCRETE TOPPING SLAB CONCRETE SLAB ON GRADE 3/4" PEX TUBING (TYP.) HANGER DOOR. REFER TO ARCHITECTURAL PLANS. UNDER DOOR TRACKS1-1/2" MIN. ARCHITECTURAL PLANS. (TYP.) REBAR, REBAR, BY OTHERS BY OTHERS 6"6" TIE PEX TUBING TO REBAR AT END OF STRUCTURE. TIE PEX TUBING TO REBAR AT END OF STRUCTURE. LOOP #1 LOOP #2 LOOP #3 LOOP #4 NOTES: 1. REFER TO SCHEDULES FOR 2. REFER TO ARCHITECTURAL 3. FINAL TUBING SIZE AND TUBING SIZES, NUMBER OF LOOPS, LOOP LENGTH, ETC. AND STRUCTURAL DRAWINGS FOR SPECIFIC DOOR TRACK AND CONCRETE INSTALLATION LAYOUT TO BE CONFIRMED WITH APPROVED SHOP DRAWINGS PRIOR TO INSTALLATION. 4. REFER TO FLOOR PLANS FOR ZONE LOCATIONS. DETAILS. ASSEMBLY 90° AND PROVIDE WITH SPRING NEGATOR EXTENSION. VERTICAL TYPE FIRE DAMPER SHOWN. FOR HORIZONTAL TYPE TURN NOTE: LOCAL CODE GAUGE PER STEEL SHEET ACCESS DOOR TYPE "B" DAMPER SLEEVE. BOTH SIDES OF BREAKWAY JOINT, INSTRUCTIONS. ACCORDANCE WITH MFR. MAINTAIN CLEARANCE IN WALL. AROUND BOTH SIDES OF RETAINING ANGLES ALL 1-1/2"x1-1/2"x1/8" FIRE DAMPER FLOW AIR IN-LINE FAN, REFEROUTLET DUCTWORK, RE: FLOOR PLAN FOR SIZE AND CONTINUATION SPRING ISOLATION HANGER (TYP.) THREADED STEEL HANGER ROD (TYP.) (BY M.C.) (BY M.C.) FLOW AIR TO SCHEDULE DIRECT DIRVE FAN MOTOR FLEXIBLE CONNECTION, TYP. INLET GUARD PROVIDE SADDLE SPECIFIED (TYP.) ON DRAWINGS (TYP.) TYPE AS INDICATED PIPING OF SIZE AND OR INSERT AS CLEVIS TYPE HANGER MSS STANDARD (TYP.) THREADED HANGER RODS. SIZE PER STANDARD (TYP.) UNISTRUT. SIZE PER MSS STEEL ANGLE HANGER OR LOCK NUT AND WASHER ON BOTTOM (TYP.) NUT AND WASHER REFER TO SPECIFICATIONS FOR CLAMP SPACING ON TOP (TYP.) INSULATION AS SPECIFIED (TYP.) (TYP.) BOILER CONDENSING DIRECT VENT THERMOMETER (TYP.) GALVANIZED, INSULATED COMBUSTION AIR DUCT PER MANUFACTURER'S BOILER DRAIN. PIPE FULL SIZE TO FLOOR DRAIN. FLOOR REQUIREMENTS. FLUE CONDENSATE DRAIN. PIPE 1-1/2" PVC DRAIN FROM NEUTRALIZER TO FLOOR DRAIN. AL29-4C FLUE. INSTALL PER MANUFACTURER'S REQUIREMENTS. FLANGE CONN. (TYP.) BUTTERFLY SHUT-OFF VALVE TYP. 50 PSI PRESSURE RELIEF VALVE. PIPE FULL SIZE TO FLOOR DRAIN. NOTE: ANY HORIZONTAL DRAIN PIPING SHALL BE ANCHORED TO THE FLOOR. STRAINER. HWS HW R CONDENSATE TRAP MOUNTED 6" AFF, SUPPORT FROM FLOOR CONDENSATE TANK W/ UNIONS ANCHOR BOILER TO CONCRETE HOUSEKEEPING PAD, REAR OF BOILER SHALL BE FLUSH TO PAD. ROUTE DRAIN PIPING AS REQUIRED TO AVOID A TRIPPING HAZARD. BOTTOM OF SYSTEM MAIN PIPE EXPANSION LINE OFF AIR/DIRT/HYDRAULIC SEPARATOR OR UNION (TYP.) FLANGED CONNECTION STRUCTURE SUPPORT FROM 3"ø HWS HANGER/SUPPORT ROD (TYP.) PRESSURE GAUGE WITH FLOOR DRAIN FULL SIZE TO PIPE AIR VENT BALL VALVE (TYP.) BALL VALVE (TYP.) 3"ø HWR MANUAL AIR VENT TO FLOOR DRAIN. AIR VENT. PIPE FULL SIZE REFER TO SCHEDULE FOR PRESSURIZED BLADDER TYPE EXPANSION TANK SIZE (TYP.) AND QUANTITY. FLOOR AIR CHARGING VALVE (TYP.) VALVE WITH BALL DRAIN HOUSEKEEPING PAD 4" CONCRETE SHUT OFF VALVE. REFER TO NOTE 1 BELOW. NOTES: 1. REFER TO SPECIFICATIONS FOR TYPE OF VALVE (BALL OR BUTTERFLY) BASED ON PIPE SIZE. HOSE END FITTING (TYP.) 3"ø HWR TO BOILER INLET FROM BOILER DISCHARGE SYSTEM SUPPLY, 3"ø HWS SYSTEM RETURN TO PUMP SUCTION (REFER TO PLUMBING DRAWINGS 1" SYSTEM MAKE UP (DCW) FOR CONTINUATION) THERMOMETER, TYP. 50 PSI PRESSURE RELIEF VALVE SIZED FOR FULL SYSTEM CAPACITY. PIPE FULL SIZE TO FLOOR DRAIN. DRAIN PLUG NOTE: MOUNT POT FEEDER PIPING AND SIDE STREAM FILTER TO MECHANICAL ROOM WALL IN A NEAT WORKMANSHIP MANNER AND IN AN ACCESSIBLE LOCATION. PUMP DISCHARGE 3/4" 3/4" HOSE END DRAIN VALVE (TYP.) 5 GAL. CAP. 4" CONCRETE TOP FEED MOUNT FEEDER ON CONCRETE PAD OR RIGIDLY MOUNT TO MECHANICAL ROOM WITH WIDE MOUTH PAD WALL. BALL VALVE (TYP.) CHECK VALVE UNION (TYP.) 3/4" SYSTEM PUMP SHOT FEEDER, REFER TO PLANS FOR SIZES. PUMP SUCTION HEADER. SYSTEM MAKE UP STATION. GLYCOL FEED 1" COLD WATER 1" FLOOR TIE INTO SYSTEM AT EXPANSION TANK LOOP SNOWMELT HIGH CAPACITY AUTOMATIC AIR VENT AIR SEPARATOR DRAIN WITH HOSE END CONNECTION CONTRACTOR. FLASHING OVER EDGE OF VERTICAL EDGE INSULATION FOR PROTECTION. FLEXIBLE EPS FOAM UNDERSLAB INSULATION. INSULATION ASSEMBLY SHALL BE A MIN. R-10 BY G.C. AT CONTRACTORS OPTION, RIGID HIGH DENSITY UNDERSLAB INSULATION MIN. R-10 BY G.C. IS ALLOWABLE. SCALE: NONE 6 M6.00 SCALE: NONESCALE: NONE 14 M6.00 13 M6.00 SCALE: NONE 5 M6.00 SCALE: NONE 17 M6.00 SCALE: NONE 15 M6.00 SCALE: NONE 2 M6.00 SCALE: NONE 1 M6.00SCALE: NONE 3 M6.00 SCALE: NONE 16 M6.00 SCALE: NONE 7 M6.00 4 M6.00 SCALE: NONE 8 SCALE: NONE NOTE: TOTAL COMBINED OPERATING WEIGHT OF PIPING ON TRAPEZE HANGERS TO BE < 10LB/LF M6.00SCALE: NONE 9 M6.00SCALE: NONE 10 M6.00 SCALE: NONE 12 M6.00 SCALE: NONE 11 M6.00 SCALE: NONE HEATING WATER PLANT - PIPING SCHEMATIC AND CONTROL DIAGRAM SMR SMS BOILER CONTROLLER SM R INTERNAL BOILER CIRC PUMP (TYP. 3) ET-1 GF-1 3" SMS BUTTERFLY VALVE TYP. P-1 FLANGE TYP. AIR/DIRT/HYDRAULIC SEPARATOR AS-1 2" 2" SMS TO ZM-4 2" SMS TO ZM-3 3" 2-1/2" 2" SMS FROM ZM-3 3" SMR SMS B -1 SMR SMS TEKMAR SNOW/ICE SENSORS TYP. (2) SEE PLANS FOR LOCATIONS TEKMAR 680 SNOWMELT CONTROLLER OUTDOOR AIR TEMP. SENSOR 3" BALL VALVE TYP. BOILER ROOM HARD WIRE INTERFACE TO BOILER SAFETY CIRCUIT EPO SMS-T TO BOILER CONTROLLER 1-1/4" SMS TO ZM-5 2" SMS TO ZM-1 1" SMS TO ZM-2 2" 2" SMR FROM ZM-4 1-1/4" SMR FROM ZM-5 2" SMR FROM ZM-1 1" SMR FROM ZM-2 The Ballard Group, Inc. Mechanical Consulting Engineers 2525 S. Wadsworth Blvd, Suite 200 Lakewood, CO 80227 (303) 988-4514 Consultant Seal Project Title Project Description Revision Log Issue Date Tectonic Project Number Issue Title Sheet Title Sheet Number Approved By Revision Date Al l D r a w i n g s A n d W r i t t e n M a t e r i a l A p p e a r i n g H e r e i n Co n s t i t u t e O r i g i n a l A n d Un p u b l i s h e d W o r k O f T h e D e s i g n e r A n d M a y N o t B e D u p li c a t e d , U s e d , O r Di s c l o s e d W i t h o u t W r i t t e n C o n s e n t F r o m T e c t o n i c M a n ag e m e n t G r o u p , I n c . Drawn By 1/ 2 0 / 2 0 2 3 8 : 3 4 : 1 3 A M C: \ U s e r s \ p f a i l l a \ D o c u m e n t s \ 2 2 0 7 9 _ H V A C _ R 2 1 _ P F a i l l a . r vt M6.00 HVAC Details & Piping Schematic 100% Construction Documents 202199 01/20/2023 AAS-RIL, Hgr 6 Rifle Garfield County Airport Rifle, CO At l a n t i c A v i a t i o n - Ri f l e H a n g a r 6 PWF JJG 1/20/2023 Page 18 of 19 2015 INTERNATIONAL MECHANICAL CODE - CHAPTER 4 NATURAL VENTILATION ROOM OPENING NET FLOOR OPENABLE PERCENT REMARKS NAME TYPE AREA WINDOW/DOOR AREA OPENABLE TO (SF) (SF) FLOOR AREA HANGAR 100 29,278 HANGAR DOOR 4,200 GARAGE DOOR 100 GARAGE DOOR 100 SWING DOOR 21 SWING DOOR 21 SWING DOOR 21 SWING DOOR 21 TOTAL 29,278 4,484 15.3%COMPLIES GSE 108 1,210 GARAGE DOOR 384 SWING DOOR 21 TOTAL 1,210 405 33.5%COMPLIES NOTE: THE MINIMUM OPENABLE AREA TO THE OUTDOORS SHALL BE 4 PERCENT OF THE FLOOR AREA BEING VENTILATED PER 2015 IMC 402.2. 2015 IMC MINIMUM OUTDOOR AIR REQUIREMENTS - SINGLE ZONE Project:ATLANTIC AVIATION - RIFLE HANGER 6 Project #:22079 SYSTEM:F-1 OPERATING MODE: HEATING ROOM ROOM ZONE OCCUPANCY FLOOR DESIGN OA/ OA/AIR ZONE AIR REQUIRED SA NAME NO. TAG CATEGORY AREA POP. PERSON SF DISTRIBUTION DISTRIBUTION OA TO ZONE TO ZONE (SF)TYPE EFFECTIVENESS (CFM) (CFM) (Rp) (Ra) (Ez) (Voz) SUITE C 107 F-1 Office space 505 3 5.0 0.06 CSCRH 0.8 53.7 700 TOTAL REQUIRED OUTDOOR AIR INTAKE FLOW RATE (Vot)54 CFM TOTAL OUTDOOR AIR PROVIDED 75 CFM 2015 IMC MINIMUM OUTDOOR AIR REQUIREMENTS - SINGLE ZONE Project:ATLANTIC AVIATION - RIFLE HANGER 6 Project #:22079 SYSTEM:F-2 OPERATING MODE: HEATING ROOM ROOM ZONE OCCUPANCY FLOOR DESIGN OA/ OA/AIR ZONE AIR REQUIRED SA NAME NO. TAG CATEGORY AREA POP. PERSON SF DISTRIBUTION DISTRIBUTION OA TO ZONE TO ZONE (SF)TYPE EFFECTIVENESS (CFM) (CFM) (Rp) (Ra) (Ez) (Voz) SUITE B 106 F-2 Office space 495 2 5.0 0.06 CSCRH 0.8 52.6 700 TOTAL REQUIRED OUTDOOR AIR INTAKE FLOW RATE (Vot)53 CFM TOTAL OUTDOOR AIR PROVIDED 75 CFM 2015 IMC MINIMUM OUTDOOR AIR REQUIREMENTS - SINGLE ZONE Project:ATLANTIC AVIATION - RIFLE HANGER 6 Project #:22079 SYSTEM: F-3 OPERATING MODE: HEATING ROOM ROOM ZONE OCCUPANCY FLOOR DESIGN OA/ OA/AIR ZONE AIR REQUIRED SA NAME NO. TAG CATEGORY AREA POP. PERSON SF DISTRIBUTION DISTRIBUTION OA TO ZONE TO ZONE (SF)TYPE EFFECTIVENESS (CFM) (CFM) (Rp) (Ra) (Ez) (Voz) SUITE A 105 F-3 Office space 500 3 5.0 0.06 CSCRH 0.8 53.1 700 TOTAL REQUIRED OUTDOOR AIR INTAKE FLOW RATE (Vot)53 CFM TOTAL OUTDOOR AIR PROVIDED 75 CFM 2015 IMC MINIMUM OUTDOOR AIR REQUIREMENTS - SINGLE ZONE Project:ATLANTIC AVIATION - RIFLE HANGER 6 Project #:22079 SYSTEM:F-4 OPERATING MODE: HEATING ROOM ROOM ZONE OCCUPANCY FLOOR DESIGN OA/ OA/AIR ZONE AIR REQUIRED SA NAME NO. TAG CATEGORY AREA POP. PERSON SF DISTRIBUTION DISTRIBUTION OA TO ZONE TO ZONE (SF)TYPE EFFECTIVENESS (CFM) (CFM) (Rp) (Ra) (Ez) (Voz) TOILET 102 F-4 Corridors 150 0 0.0 0.06 CSCRH 0.8 11.3 125 TOILET 103 F-4 Corridors 150 0 0.0 0.06 CSCRH 0.8 11.3 125 JAN/STORAGE 104 F-4 Corridors 75 0 0.0 0.06 CSCRH 0.8 5.6 50 HALL 101 F-4 Corridors 215 0 0.0 0.06 CSCRH 0.8 16.1 250 GSE OFFICE 110 F-4 Office space 115 1 5.0 0.06 CSCRH 0.8 12.2 150 TOTAL REQUIRED OUTDOOR AIR INTAKE FLOW RATE (Vot)56 CFM TOTAL OUTDOOR AIR PROVIDED 75 CFM The Ballard Group, Inc. Mechanical Consulting Engineers 2525 S. Wadsworth Blvd, Suite 200 Lakewood, CO 80227 (303) 988-4514 Consultant Seal Project Title Project Description Revision Log Issue Date Tectonic Project Number Issue Title Sheet Title Sheet Number Approved By Revision Date Al l D r a w i n g s A n d W r i t t e n M a t e r i a l A p p e a r i n g H e r e i n Co n s t i t u t e O r i g i n a l A n d Un p u b l i s h e d W o r k O f T h e D e s i g n e r A n d M a y N o t B e D u p li c a t e d , U s e d , O r Di s c l o s e d W i t h o u t W r i t t e n C o n s e n t F r o m T e c t o n i c M a n ag e m e n t G r o u p , I n c . Drawn By 1/ 2 0 / 2 0 2 3 8 : 3 4 : 1 3 A M C: \ U s e r s \ p f a i l l a \ D o c u m e n t s \ 2 2 0 7 9 _ H V A C _ R 2 1 _ P F a i l l a . r vt M7.00 HVAC Outside Air Calcs & Sequence 100% Construction Documents 202199 01/20/2023 AAS-RIL, Hgr 6 Rifle Garfield County Airport Rifle, CO At l a n t i c A v i a t i o n - Ri f l e H a n g a r 6 PWF JJG 1/20/2023 Page 19 of 19