HomeMy WebLinkAboutComm Check- Mechanical ComplianceCOMcheck Software Version COMcheckWeb
Mechanical Gompliance Gertificate
Project lnformation
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
Construction Site:
252 C.R. 167
GLENWOOD SPRINGS, Colorado
81601
202L IECC
23045 - Schafer and Company Warehouse
Glenwood Springs, Colorado
5b
Addition
Owner/Agent;
Bucky Schafer
Schafer & Company
303-819-9706
bucky@scmetals.com
Desi g n e r/Contractor:
Mark Sorensen
AEC
PO BOX 8489
Avon, Colorado 81620
970-748-8520
mark@aec-vail.com
Mechanical Systems List
QuantitySystem Type & Description
1 HP-1 (Unknown):
VRF Condensing Unit, Air Cooled Heat pump
Heating Mode: Capacity = :+ kBtu/h,
Proposed Efficiency = 12,00 HSpF, Required Efficiency = 7.70 HSpF
Cooling Moder Capacity : Zg kBtu/h,
Proposed Efficiency = 22.3O SEER, Required Efficiency = 13.00 SEER
Proposed Part Load Efficiency = 0,00 , Required part Load Efficiency : 0.00
Fan System: None
1 FC-1 (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 7 kBtu/h, Unknown Economizer
No mlnimum efficiency requirement applies
Fan System: Fc-1 | Kitchen/Living -- Compliance (Motor nameplate Hp and fan efficiency method) : passes
Fans:
- FAN l Supply, Single-Zone VAV,297 cFM, 0.1 motor nameplate hp, 1.00 fan energy index, fan exception: Singlefan < 1 HP or < 0.89 kW
1 FC-2 (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 5 kBtu/h, Unknown Economizer
No minimum efficiency requirement applies
Fan System: FC-2 & 3 | eedrbom 1 -- compliance (Motor nameplate Hp and fan efficiency method)
Fans:
- FAN 2 !uppty, Single-Zone vAv,237 cFM, 0.1 motor nameplate hp, 1.00 fan energy index, fan exception: Singlefan < 1 HP or < 0,89 kW
1 FC-3 (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity : 5 kBtu/h, Unknown Economizer
No minimum efficiency requirement applies
Fan System: Fc-2 & 3 | Bedroom 1 -- Compliance (Motor nameplate Hp and fan efficiency method)
Fans:
- FAN 2 Supply, Single-Zone vAv,231 cFM, 0,1 motor nameplate hp, 1.00 fan energy index, fan exception: Singlefan < 1 HP or < 0.89 kW
Passes
Passes
1 F-l (Single Zone)
Heating: 1 each -
Proposed Effici
Fan System: F-1
Central Furnace, Gas, Capacity: 120 kBtu/h
ency = 96.50% Et, Required Efficiency: 80.00 % Et or 80% AFUE
Office -- Compliance (Motor nameplate HP and fan efficien cy method) : Passes
Project Title: 23045 - Schafer and Company Warehouse
Data filename:
Report dale: O4lL2/24
Page I of 11
QuantitySystem Type & Description
Fans:
FAN 3 Supply, ConstantVolume, 2200 CFM, 1.0 motor nameplate hp, 1,00 fan energy index
1 CU-1 (Single Zone):
Cooling: 1 each_- Split System, Capacity = 57 kBtu/h, Air-Cooled Condenser, No Economizer, Economizer exceptionHeat Recovery System
Proposed Efficiency = 16,00 SEER2, Required Efficiency = 13.40 SEER2
Proposed Part Load Efficiency = 0.00 , Required Part Load Efficiency = 0.00
Fan Systeml F-1 | office -- Compliance (Motor nameplate HP and fan efficiency method) : passes
Fans:
FAN 3 Supply, ConstantVolume, 2200 CFM, 1,0 motor nameplate hp, 1,00 fan energy lndex
1 WH.1:
Gas Storage {ater Heater, Capacity: 50 gallons, lnput Rating: 100 kBtu/h w/ Circulation pump
Proposed Efficiency: 96,00 % Et, Required Efficiency: BO.O0 % Et
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document ls consistent with the building plans,specificatlons, and other calculations submitted with this permit application. The proposed mechanical systems nave"Obendesigned to meet the 2021 IECC requirements in CoMcheckVersion COMcheckWbb ind to comply with 5ny appf iiaOfe
--
mandatory requirements listed in the lnspection Checklist.
Mark $orensen EIT t4t<-/ laP-t-)*04t12t24
Name - Title 5 rgna tu re Date
23045 - Schafer and Company WarehouseProject Title:
Data filename
Report date: O4ll2l24
Page 2 of lL
COMcfi eck Software Version CoMcheckWeb
lnspection Checklist
Energy Code: 202L IECC
Requirements: 0,0% were addressed directly in the coMcheck software
Text in the "comments/Assumptions" column is provided by the user in the CoMcheck Requirements screen. For eachrequirement, the user certifies that a code requirement wili be met and how that is documented, or that an exceptionis being claimed, Where compliance is itemized in a separate table, a reference to thattable is provideO.
Additional Comments/Assumptions :
1 High lmpact (Tier 1)2 Medium lmpact (Tier 2)3 Low lmpact (Tier 3)
&.lD
Section
#Plan Review Complies?Comments/Assumptions
: Plans, specifications, and/or
,calculations provide all information
,with which compliance can be
,determined for the mechanical and,service water heating systems and
:document where exceptions to the
, standard are claimed. Load
, calculations per acceptable
: engineering standards and
; handbooks. Hot water system sized
plies
Not
per manufacturer's guide.
c103.2
lPR2ll
ENot Observable
!ruot Applicable
c405.6
lPR16l1
units have
meters.
, croup R-2 dwelling
; separate electrical
nNot Observable
Itrtot Applicable
Complies
Does Not
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the additional energy
:nDoes Not
I lNot Observable
;!t',tot Rpplicableckaefficienons.
pliesc406
lPR9l1
Project Title: 23045 - Schafer and Company Warehouse
Data filename:
Report date: O4/I2124
Page 3 of 11
Snow/ice melting system and freeze
protection systems have sensors and
controls configured to limit service for
pavement temperature above 50F and
outdoor temperature above 40F,
c403.13.3
IF0913
lDoes Not
plies
:ENot observable
:!Not applicable
Additional Comments/Assumptions:
1 High lmpact (Tier 1)2 Medium lmpact (Tier 2)3 Low lmpact (Tier 3)
23045 - Schafer and Company WarehouseProject Title:
Data filename:Report date: 04/12124
Page 4 of 11
Section
#
& Reo,lD
Plumblng Rough-ln lnspectlon Complles?Comments/Assumptlons
c404.5,
c404.5,1,
c404.5.2
lPL6l3
'Heated water supply piping conforms :[lComplies :
to pipe length and volume ;DOoes Not :
requirements. Refer to section details. j;ruot Observable ,
;ENot Applicable ,j,
c404.6.r,
c404.6.2
lPL3l1
Automatic time switches installed to
automatically switch off the
recirculating hot-water system or heat
trace.
:IComplies
j!Does tr,tot
:flNot Observable
;DNot Rpplicable
eumps that circulate water between a ;nComplies :
heater and storage tank have controls lnDoes Not :
that limit operation from startup to -f,,^! ^L :
<= 5 minutes after end oi-[".llno* !Not observable;
cycle. " L-lNot APPlicable :
c404,6,3
lPL7l3
c404.6.1,
c404.6.1.
1
lPL8l3
. Demand recirculation water systems'have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104'F.
,nComplies
Not
flNot Applicable
Observable
Additional Comments/Assumptions:
1 2Hhlmact (Tier Medium lmpact (Tier 2)3 Low lm ct (Tier 3)
Project Title: 23045 - Schafer and Company Warehouse
Data filename:
Report date: 041L2124
Page 5 of 11
Section
#
& Req.lD
Mechanical Rough-ln lnspectlon Complles?Comments/Assumptlons
Thermally ineffective panel surfaces of lComplies
sensible heating panels have nDoes Not
insulation >: R-3.5. [Not Observable
:nNot Applicable
c402.2.6
lME4113
nComplies
nDoes Not
nNot Observable
flNot Applicable
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
See the Mechanical Systems list for valuesc403.8.1
lME65l3
Fans have a fan energy index (FEl) >: lnComplies
1.00. Variable volume fans will have ,!Does Not
an FEI >= o'95' [Not observable
:nruot Rpplicable
c403,8.3
lME117l2
Motors for fans that are not less than
llI2 hp and less than t hp are
electronically commutated motors or
have a minimum motor efficiency of
70 percent. These motors have the
means to adjust motor speed,
,nComplies
lnooes Not
lflNot observable
:nNot Applicable
c403.8.4
lME14212
Each DX cooling system > 65 kBtu :nComplies
and chiller water/evaporative cooling :nDoes Not
system with fans > 1/4 hp are
designed to vary ffre inoJor ian airflow ENot observable
as alunction of load and comply with LlNot Applicable
detailed requirements of this section.
c403.8.6
lME143l2
nComplies
!Does Not
nNot Observable,
nNot Applicable :
Large diameter fans where installed
shall be tested and labeled in
accordance with AMCA 230.
c403.9
lMEr.44l2
HVAC equipment efficiency verified. ,nComplies :
nDoes Not
nNot Observable
nNot Applicable
see the Mechanical Systems list for valuesc403,3
IMEss],
nComplies l
lDoes Not :
INot Observable,
nruot npplicable :
Natural or mechanical ventilation is
provided in accordance with
lnternational Mechanical Code
Chapter 4. Mechanical ventilation has
capability to reduce outdoor air supply
to minimum per IMC Chapter 4,
c403.2.2
lME5911
, Demand control ventilation provided ,nComplies
,for spaces >500 ft2 and >15 ;lDoes Not
people/l000 ft2 occupant densitv and -., . ^,,ierved by systems wiih al;si;;-' - "
=lo:observableeconomiierl auto modulating outside LlNot Applicable
:air damper control, or design airflow ,
>3,000 cfm.
c403,7.1
lME59l1
Enclosed parking garage ventilation
has automatic contaminant detection
and capacity to stage or modulate
fans to 5OVo or less of design capacity
,nComplies
:!ooes tlot
:nNot Observable
nruot applicable
c403.7.2
IME 11513
HVAC systems serving guestrooms in
Group R-1 buildings with > 50
guestrooms: Each guestroom is
provided with controls that
automatically mana ge temperature
setpoint and ventilation (see sections
C403.7.6,1 and C403.7.6,2).
,nComplies
,flDoes Not
.nNot Observable
:nruot Rpplicable
c403.7.6
lM E 14113
1 (Tier 1)Hi ht 2 Medium (Tier 2)3 Low lmpact (Tier 3)
23045 - Schafer and Company WarehouseProject Title:
Data filename
Report date: 041L2124
Page 6 of 11
Section
#
& Req.lD
Mechanical Rough-ln lnspection Complies?Comments/Assumptions
C4O3,7.4 tExhaust air energy recovery on
lME57l1 .systems meeting Table C403.7,4(1)
:and C403.7.4(2).
:ncomplies
:nooes ltot
nNot Observable
nNot Applicable
Kitchen exhaust systems comply with :
replacement air and conditioned
supply air limitations, and satisfy hood
rating requirements and maximum .
exhaust rate criteria. :
nComplies
nDoes Not
nNot Observable
nNot Applicable
c403.7.5
lMEL 1613
Closed-circuitcoolingtowerwithin ;!Complies
heat pump loop have either automatic lnDoes Not
bypass valve or lower leakaqe positive
ciosure dampers. op"n-.iii,iit ioii;; -
,L-JNot observable
within heat dump loop have automal;. LJNot Applicable
valve to bypass all heat pump water
flow around the tower. Open- or
closed-circuit cooling towers used in
conjunction with a separate heat
exchanger have heat loss by shutting
down the circulation pump on the
cooling tower loop. Open- or closed
circuit cooling towers have a separate
heat exchanger to isolate the cooling
tower from the heat pump loop, and
heat loss is controlled by shutting
down the circulation pump on the
cooling tower loop.
c403.4.3.
3.2
lME12113
Heating for vestibules and air curtains
with integral heating include
automatic controls that shut off the
heating system when outdoor air
temperatures > 45F. Vestibule
heating and cooling systems
controlled by a thermostat in the
vestibule with heating setpoint <:
60F and cooling setpoint >= BOF.
nComplies
lDoes Not
INot Observable
nruot Rpplicable
c403.4.1
4
lME6312
:DComplies
:nDoes Not
,nNot Observable
i!ruot Rpplicable
c403.3,3
lME35l1
Hot gas bypass limited to: <:240
kBtu/h - 5OVo >240 kBtu/h - 25%
>: 92 Et. Where multiple pieces of
water-heating equipment serve the
building with combined rating >:
1,000 kBtu/h, the combined input-
capacity-weighted-average thermal
efficiency >= 90 Et. Exclude input
rating of equipment in individual
dwelling units and equipment <: 100
kBtu/h.
Gas-firedwater-heatingequipment inComplies
installed in new buildings: where a :nDoes Not
singular piece of water-heatinq
equ-ipmeirt >: 1,000 rcetuTh sErves LlNot observable
thb entire building, thermal efficiency LlNot Applicable
c404.2.1
lM E11112
Air outlets and zone terminal devices
have means for air balancing.:nooes titot
INot Observable
inruot npplicable
c408.2.2
1
lME53l3
lies
1 Hi (Tier 1)2 Medium lmpact (Tier 2)3 Low lm (Tier 3)
Project Title: 23045 - Schafer and Company Warehouse
Data filename:
Report date
Page
04lL2l24
7of LL
remote compressors and remote
condensers not located in a
condensing unit, have fan-powered
condensers that comply with Sections
C403.1 1.3.1 and refrigeration
compressor systems that comply with
c403.11.3.2..
1!Not Observable
;ENot Applicable
.3 ; Refrigerated display cases, walk-in
lcoolers or walk-in freezers served by
Complies
Does Not
Additional Comments/Assumptions:
1 Hi (Tier 1)Medium lm ct (Tier 2)ct (Tier 3)Low
Project Title: 23045 - Schafer and Company Warehouse
Data filename:
Report date: Q4ll2l24
Page 8 of 11
Complles?Comments/Assumptlons
Sectlon
#
& Req.lD
Rough-ln Electrlcal lnspectlon
Low-voltage dry-type distribution
electric transformers meet the
minimum efficiency requirements of
Table C405.6.
EComplies
nDoes Not
!Not Observable
lwot Applicable
c405.7
lEL26l'
Electric motors meet the minimum
efficiency requirements of Tables
C40s.7(1) through C405.7(4). I
Efficiency verified through certification l
under an approved certification l
program or the equipment efficiency :
ratings shall be provided by motor ;
manufacturer(wherecertification l
proqrams do not exist).
ncomplies
nDoes Not
nNot Observable
flruot Applicable
c405,8
[EL2712
Escalators and moving walks comply
with ASME A17,I/CSA 844 and have
automatic controls configured to
reduce speed to the minimum
permitted speed in accordance with
ASME A17.I/CSA 844 or applicable
local code when not conveying
nComplies
nDoes Not
INot Observable
INot Applicable
n ers
c405.9.1,
c405.9.2
lEL28l2
Total voltage drop across the
combination of feeders and branch
circuits <= SVo,
nruot licable ,
ENot Observable,
c405.10
lEL29l2
nComplies
nDoes Not
,At least 90Y" of dwelling unit
permanently installed lighting shall
have lamp efficacy >= 65 lm/W or
luminaires with efficacy >= 45 lm/W
nComplies
nDoes Not
ENot Observable,
nruot Rpplicable :or with C405.2.4 or C405.3
c405.1.1
lEL3ol2
C405.11, 50% of 15/20 amp receptacles
C405,11.1 installed in enclosed offices,
[EL31]2 conference rooms, copy rooms, break
rooms, classrooms and workstations
:and > 25yo of branch circuit feeders
for modular furniture will have
automatic receptacle control in
accordance with C405.11.1,
nComplies
nDoes Not
nNot Observable
!Not Applicable
Additional Comments/Assumptions:
1 ct (Tier 1)Hi ht 2 Medium ct (Tier 2)3 Low lm act (Tier 3)
23045 - Schafer and Company WarehouseProject Title:
Data filename
Report date: O4lI2l24
Page I of 11
Section
#
& Req.lD
Final lnspectlon Complles?Comments/Assumptlons
c303.3,
c408.2.s
3
lFt8l3
Furnished O&M manuals for HVAC
systems within 90 days of system
acceptance.
:nComplies
;nDoes Not
inNot observable
;nNot Applicable
HVAC systems and equipment
capacity does not exceed calculated
loads.
,flcomplies
,nOoes trtot
'flNot Observable
:nNot Applicable
c403.3.1
lFl27 j3
Heating and cooling to each zone is lncomplies
controlled by a thermostat control. ,nDoes Not
Minimum one humidity control device nNot Observableper installed
humidification/dehumidification lflNot Applicable
system.
c403.4.1
lFt4713
c403.4.1
1
lFt42l3
Heat pump controls prevent ;nComplies :
supplemental electric resistance heat ,lpess t!e1
from coming on when not needed. ,nNot observable,
nruot Rpplicable
c403.4.1
2
lFt38 j3
incomplies :
llOoes trtot l
:Itrtot observable :
;nNot Applicable .
Thermostatic controls have a 5 'F
deadband.
c403.4.1
3
IFt2o]3
Temperature controls have setpoint
overlap restrictions.
:INot
L lNot
IComplies
!Does Not
Observa bl e
Applicable .
Each zone equipped with setback ,nComplies
controls using automatic time clock or ;lOoes Not
programmable control system. :nNot Observable
.nruot applicable
c443.4.2
lFt39l3
Automatlc Controls: Setback to 55'F .nComplies
(heat) and 85"F (cool); 7-day clock, 2- :Iooes Not
hour occupant override, 10-hour lnNot ObservablebackuP Erirot nppricanru
c403.4.2
1,
c403.4.2
2
lFt40l3
.!Complies
:nDoes Not
.!Not Observable
.!Not Applicable
c403.4.2
3
lFt4113
Systems include optimum start
controls.
,flcomplies
.flDoes Not
:nNot Observable
lnruot applicabte
Heat traps installed on supply and
discharge piping of non-circulating
systems.
c404.3
lFt11j3
All piping insulated in accordance with ,nComplies
section details and Table C403.12.3. ;nDoes Not
rnNot Observable
lnNot appllcable
c404.4
lFt2512
Complies
Does Not
Not Observable
Not Applicable
Controls are installed that limit the
operation of a recirculation pump
installed to maintain temperature of a
storage tank. System return pipe is a
dedlcated return pipe or a cold water
supply pipe.
c404.6.1
lFl 1 213
i!
,tr
1 High lmpact (Tier 1)2 Medium lmpact (Tier 2)3 Low lmpact (Tier 3)
Project Title: 23045 - Schafer and Company Warehouse
Data filename:
Report date: O4ll2l24
Page 10 of 11
Com rneilts/Ass um ptlonsSection
#
& Reo.lD
Flnal lnspectlon complles?
nComplies
rlDoes Not
,!Not Observable
.flruot applicable
Building operations and maintenance
documents will be provided to the
owner. Documents will cover
manufacturers' information,
specifications, programming
procedures and means of illustrating
to owner how building, equipment and
systems are intended to be installed,
maintained, and operated.
c408,1,1
lFt57l1
ncomplies
nDoes Not
nNot Observable
lNot Applicable
Commissioning plan developed by
registered design professional or
approved agency,
c408.2.1
lFt28l1
c408.2.3
1
lFt 3 111
ilcomplies :
]nDoes tlot i
l!ruot observable'
;nNot Applicable ,
,HVAC equipment, systems and
i system-to-system relationships have
:been tested to ensure proper
operation
c408.2.3
2
I Fr 10]1
:ncomplies
,!Ooes ttot
inruot observable
;[ruot applicable
HVAC and service water heating
control systems have been tested to
ensure proper operation, calibration
and adjustment of controls.
flcomplies .
nooes Not I
inruot observaole I
;nruot npplicable ,
Preliminary commissioning report
completed and certified by registered
design professional or approved
agency.
c408.2.4
lFt29l1
,flcomplies
lflooes trtot
tflruot Observable
tlt',tot Rpplicable
Furnished HVAC as-built drawings
submitted within 90 days of system
accepta nce.
c408.2.5
IFt7]3
c408.2.5
1
lFl43l1
lAn air and/or hydronic system ;nComplies
lbalancing report is provided for HVAC lnDoes trtots'stems
:=il3l:ffi::l?:"
:nDoes Not
,nNot Observable
.nllot Rppllcabte
c408.2,5.
2
lFt30ll
ibuilding owner within 90 days of
: receipt of certificate of occupancy
esFinal commissioning report due to
Additional Comments/Assumptions:
2 Medium (Tier 2)3 Low lm act (Tier 3)1 High lm ct (Tier 1)
Project Title: 23045 - Schafer and Company Warehouse
Data filename:
Report date: 04112124