HomeMy WebLinkAboutEngineer's Concrete Installation ReportsSOG bound by GL C.0-H.0/6.5-11.0Placement Location:
Mays ConcreteConcrete Contractor:Performed by:John Riley
Placement Method:Laser Screeded|Pumped
Weather:Sunny
Finish Method:Hand Finished|Trowel Finished|Machine
Finished
Total Quantity Placed:190 yd³
Sample No.Location Sampled From Quantity
(yd³)
Truck
No.
Ticket
No.
Batch
Time
Test
Time
Air
Temp.
(ºF)
Water
Added
(gal)
17 C.25/10.5 (See Location 1) Point of Delivery 10 56607 3307930 6:53 AM 8:05 AM 29 15
18 C.75/9.75 (See Location 2) Point of Delivery 60 999060 3307936 9:01 AM 9:46 AM 36 0
19 E.5/9.0 (See Location 3) Point of Delivery 110 999770 3307941 10:16 AM 10:56 AM 41 0
20 F.5/7.5 (See Location 4) Point of Delivery 160 56611 3307946 11:04 AM 12:02 PM 49 0
Sampling (ASTM C172 / AASHTO R60 / CDOT CP61)
Field Tests (ASTM C138, C143, C231, and C1064 / AASHTO T119, T121, and T152)
Sample No.Concrete Temp. (ºF)Slump (in)Air Cont. (%)Meas. Vol. (ft³)Empty Meas. (lb)Full Meas. (lb)Unit Wt. (pcf)Lab Samples Cast
17 67 5 1.5 0.250 7.39 43.29 143.6 Yes
18 67 6 2.0 0.250 7.39 44.29 147.6
19 67 6 1.8 0.250 7.39 44.02 146.5 Yes
20 68 6 2.2 0.250 7.39 44.32 147.7
Test Specified
Air Content (%) NP to NP
Slump (in)2 to 6
Unit Weight (pcf)-
Comp. Strength (psi) 4000
Mix Design
-
-
-
-
On-Site Notification(s)
Dwayne Felker with Tectonic Management
Group, Inc.
Nicholas Marquez with Tectonic Management
Group, Inc.
Item / Structure Type
Interior SOG
Mix Placed
United Companies 4000
Interior Spec w/ non Chloride
Accelerator 1
On-site Notifications, Specification, and Mix Information
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0016; ver: 3Apr 17, 2024
Reviewed by:Work Order Date:Mar 20, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 1 of 3
ClienI:Nicholas Marquez
Tectonic Management Group, lnc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033EROTfIfD
ENGINEERING
Repod Date: Sep 8, 2023
Wark Order Date: Sep 7, 2023
Atlantic Aviation Hangar 6
Work Order No.: 23-6522.Concrete.0002; ver: 1
Reviewed by: Chris Hutto
Concrete
Concrete Contractor: MaysConcrete
PlaeementMethod: Pumped
Total Quatttity Placed; 65 yd3
Placement Location: Footings, Bound by Gridlines l-Ml1-12 (see attached)
On-site Notifications, Specification, and Mix lnformation
On-Srte Notification{s) lten / Structure Type
Nicholas Marquez with Tectonic Management Footings
Group, lnc.
Mix Placed
United 35010705
Samplins (ASTM CIT2lAASHTO R60 / CDOT CP61)
Sample No. Location Sampled From
4 Test 1, GL M/2.5 (see attached) Point of Delivery
5 Test 2, GL J/11.5 (see attached) Point of Delivery
Performed by:
Finish Method:
Weather:
Jeff Haney
Float FinishedlHand FinishedlTrowel
Finished lVibrated- lnternally
CalmlClearlSunny
Iesf
Air Content (%)
Slump (in)
Unit Weight (pcf)
Comp. Strength (psi)
SpecrTred
NR to NR
3 to7
3000
Mix Design
Quantity
(vd1
10
60
Truck
No.
56608
56620
Ticket
No.
3306733
3306738
Air
Temp.
fF)
78
80
Water
Added
(sat)
20
10
Batch Iesf
Tinte Time
10:44 AM 'l 1:30 AM
1:20 PM 2:00 PM
Field Tests (ASTM Cl38, C143, C231, and C1064 / AASHTO T119,T121, and T152)
Sample No. Conuete Temp. ('F) Slump (in) Air Cont. (o/o) Meas- Vot. {ft1 Empty Meas. (lb) Futl Meas. (lb) Unit Wt. (pct) Lab Samples Casf
4 80 4 2.3 0.250 7.37 44.05 146.7
5 79 6.5 2.6 0.250 7.37 43.49 144.5 Yes
Gompressive Strength (ASTM C31 and C39 / AASHTOT22 and T23)
A set of compresslve sfrengfh speclnens were cast. Iesf resulls will be forwarded upon completion.
parmission of GROUND Engin€ering Consultants, lnc.
101 Airpark Drive, Unit A, Gypsum, Coforzdo wmtt.groundeng.com 970-524-0720
Englewood I Commerce City I londand I Granby I Gypsum I Colorado Springs Page I of 2
Client:
Atlantic Aviation Hangar 6
Work Order No.: 23-6522.Concrete.0002; ver: 1
Reviewed by: Chris Hufto
Nicholas Marquez
Tectonic Management Group, lnc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Repoi Date:
Work Order Date:
ENGINEERING
Sep 8, 2023
Sep 7, 2023
Concrete
Photos
,l
t
I
:
I
:
t'
I
t
I
'
l
a
I
:
-a
:!
Partial view of southern portion of footings Highlighted areas indicate where concrete was placed. Arrows indicate test
and sample locations.
pemission of GROUND Engineering Consultants, lnc.l0l Airpark Drive, Unit A, Gypsum, Colorado wMr.groundeng.eom 97&524-0720
Englewood I Commerce City I Loveland I Granby I Gypsum I Colorado Springs Page 2 of 2
Compressive Strength (ASTM C31 and C39 / AASHTO T22 and T23)
Sample No.Lab ID Age (d)Diameter (in)Area (in²)Fracture Type Max. Load (lb-f)Corrected
Strength (psi)
Strength at
Acceptance (psi)17
C3693 7 4.00 12.57 5 / Side 64,980 5,170 -
C3694 28 4.00 12.57 5 / Side 86,410 6,870 6,870
C3695 28 4.00 12.57 3 / Columnar 86,820 6,910 6,910
C3696 28 4.00 12.57 3 / Columnar 82,570 6,570 6,570
Average Compressive Strength (psi):6,780
Compressive Strength (ASTM C31 and C39 / AASHTO T22 and T23)
Sample No.Lab ID Age (d)Diameter (in)Area (in²)Fracture Type Max. Load (lb-f)Corrected
Strength (psi)
Strength at
Acceptance (psi)19
C3697 7 4.00 12.57 3 / Columnar 60,900 4,850 -
C3698 28 4.00 12.57 3 / Columnar 89,630 7,130 7,130
C3699 28 4.00 12.57 3 / Columnar 87,490 6,960 6,960
C3700 28 4.00 12.57 3 / Columnar 88,540 7,040 7,040
Average Compressive Strength (psi):7,040
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0016; ver: 3Apr 17, 2024
Reviewed by:Work Order Date:Mar 20, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 2 of 3
Photos
Highlighted equals area represented.
Blue area equals approximate test locations.
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0016; ver: 3Apr 17, 2024
Reviewed by:Work Order Date:Mar 20, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 3 of 3
SOG bound by GL H.0-M.0/6.5-11.0Placement Location:
Mays ConcreteConcrete Contractor:Performed by:John Riley
Placement Method:Pumped
Weather:Partly Cloudy
Finish Method:Broom Finished|Hand Finished|Machine
Finished|Trowel Finished
Total Quantity Placed:200 yd³
Sample No.Location Sampled From Quantity
(yd³)
Truck
No.
Ticket
No.
Batch
Time
Test
Time
Air
Temp.
(ºF)
Water
Added
(gal)
21 H.5/10.5(See Location 1)Point of Delivery 10 56229 3307992 6:58 AM 7:55 AM 27 30
22 I.5/10.0 (See Location 2)Point of Delivery 60 56397 3308001 8:57 AM 9:35 AM 29 7
23 J.5/9.5 (See Location 3)Point of Delivery 110 56397 3308010 10:28 AM 11:25 AM 36 0
24 K.25/8.0 (See Location 4)Point of Delivery 160 56229 3308018 11:43 AM 12:20 PM 39 8
Sampling (ASTM C172 / AASHTO R60 / CDOT CP61)
Field Tests (ASTM C138, C143, C231, and C1064 / AASHTO T119, T121, and T152)
Sample No.Concrete Temp. (ºF)Slump (in)Air Cont. (%)Meas. Vol. (ft³)Empty Meas. (lb)Full Meas. (lb)Unit Wt. (pcf)Lab Samples Cast
21 66 6 2.0 0.250 7.39 43.92 146.1 Yes
22 67 5.5 1.8 0.250 7.39 44.29 147.6
23 67 6 2.1 0.250 7.39 44.00 146.4 Yes
24 66 6 2.1 0.250 7.39 44.17 147.1
Test Specified
Air Content (%)NP to NP
Slump (in)2 to 6
Unit Weight (pcf)-
Comp. Strength (psi)4000
Mix Design
-
-
-
-
On-Site Notification(s)
Dwayne Felker with Tectonic Management
Group, Inc.
Nicholas Marquez with Tectonic Management
Group, Inc.
Item / Structure Type
Interior SOG
Mix Placed
United Companies 4000
Interior spec w/ non chloride
accelerator1
On-site Notifications, Specification, and Mix Information
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0017; ver: 3Apr 24, 2024
Reviewed by:Work Order Date:Mar 27, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 1 of 3
Compressive Strength (ASTM C31 and C39 / AASHTO T22 and T23)
Sample No.Lab ID Age (d)Diameter (in)Area (in²)Fracture Type Max. Load (lb-f)Corrected
Strength (psi)
Strength at
Acceptance (psi)21
C3714 7 4.00 12.57 5 / Side 57,400 4,570 -
C3715 28 4.00 12.57 5 / Side 78,430 6,240 6,240
C3716 28 4.00 12.57 3 / Columnar 80,190 6,380 6,380
C3717 28 4.00 12.57 3 / Columnar 82,460 6,560 6,560
Average Compressive Strength (psi):6,390
Compressive Strength (ASTM C31 and C39 / AASHTO T22 and T23)
Sample No.Lab ID Age (d)Diameter (in)Area (in²)Fracture Type Max. Load (lb-f)Corrected
Strength (psi)
Strength at
Acceptance (psi)23
C3718 7 4.00 12.57 5 / Side 60,710 4,830 -
C3719 28 4.00 12.57 5 / Side 82,090 6,530 6,530
C3720 28 4.00 12.57 3 / Columnar 77,800 6,190 6,190
C3721 28 4.00 12.57 3 / Columnar 85,190 6,780 6,780
Average Compressive Strength (psi):6,500
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0017; ver: 3Apr 24, 2024
Reviewed by:Work Order Date:Mar 27, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 2 of 3
Photos
Highlighted equals area represented.
Blue area equals approximate test locations.
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0017; ver: 3Apr 24, 2024
Reviewed by:Work Order Date:Mar 27, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 3 of 3
SOG bound by GL C.0-M.0/1.0-3.0Placement Location:
Mays ConcreteConcrete Contractor:Performed by:John Riley
Placement Method:Drop Chuted
Weather:Snow|Rain
Finish Method:Hand Finished|Vibrated-
Internally|Rodded|Broom Finished|Trowel
Finished
Total Quantity Placed:30.01 yd³
Sample No.Location Sampled From Quantity
(yd³)
Truck
No.
Ticket
No.
Batch
Time
Test
Time
Air
Temp.
(ºF)
Water
Added
(gal)
25 K.5/2.5 (See Location 1)Point of Delivery 10 56607 3308022 6:51 AM 7:45 AM 35 0
Sampling (ASTM C172 / AASHTO R60 / CDOT CP61)
Field Tests (ASTM C138, C143, C231, and C1064 / AASHTO T119, T121, and T152)
Sample No.Concrete Temp. (ºF)Slump (in)Air Cont. (%)Meas. Vol. (ft³)Empty Meas. (lb)Full Meas. (lb)Unit Wt. (pcf)Lab Samples Cast
25 65 5.5 1.4 0.250 7.39 45.12 150.9 Yes
Compressive Strength (ASTM C31 and C39 / AASHTO T22 and T23)
Sample No.Lab ID Age (d)Diameter (in)Area (in²)Fracture Type Max. Load (lb-f)Corrected
Strength (psi)
Strength at
Acceptance (psi)25
C3732 7 4.00 12.57 5 / Side 56,980 4,530 -
C3733 28 4.00 12.57 3 / Columnar 75,710 6,020 6,020
C3734 28 4.00 12.57 3 / Columnar 76,650 6,100 6,100
C3735 28 4.00 12.57 3 / Columnar 76,980 6,120 6,120
Average Compressive Strength (psi):6,080
Test Specified
Air Content (%)NP to NP
Slump (in)2 to 6
Unit Weight (pcf)-
Comp. Strength (psi)4000
Mix Design
-
-
-
-
On-Site Notification(s)
Dwayne Felker with Tectonic Management
Group, Inc.
Item / Structure Type
Interior SOG
Mix Placed
United Companies 4000
Interior Spec Non-chloride
Accelerator 1
On-site Notifications, Specification, and Mix Information
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0018; ver: 3Apr 27, 2024
Reviewed by:Work Order Date:Mar 29, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 1 of 2
Photos
Highlighted equals area represented.
Blue area equals approximate test location.
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0018; ver: 3Apr 27, 2024
Reviewed by:Work Order Date:Mar 29, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 2 of 2
SOG Bound by GL H.0-M.0/1.0-6.5Placement Location:
Mays ConcreteConcrete Contractor:Performed by:John Riley
Placement Method:Pumped
Weather:Mostly Sunny|Snow
Finish Method:Broom Finished|Hand Finished|Machine
Finished|Trowel Finished
Total Quantity Placed:170.1 yd³
Sample No.Location Sampled From Quantity
(yd³)
Truck
No.
Ticket
No.
Batch
Time
Test
Time
Air
Temp.
(ºF)
Water
Added
(gal)
26 K.5/6.5 (See Location 1)Point of Delivery 10 56607 3308025 7:14 AM 8:10 AM 34 15
27 J.5/5.0 (See Location 2)Point of Delivery 60 56604 3308030 8:26 AM 9:05 AM 37 0
28 I.5/4.5 (See Location 3)Point of Delivery 110 56613 3308035 9:38 AM 10:33 AM 39 0
29 H.5/4.0 (See Location 4)Point of Delivery 160 56375 3308040 10:58 AM 11:45 AM 40 0
Sampling (ASTM C172 / AASHTO R60 / CDOT CP61)
Field Tests (ASTM C138, C143, C231, and C1064 / AASHTO T119, T121, and T152)
Sample No.Concrete Temp. (ºF)Slump (in)Air Cont. (%)Meas. Vol. (ft³)Empty Meas. (lb)Full Meas. (lb)Unit Wt. (pcf)Lab Samples Cast
26 65 6 1.4 0.250 7.39 42.24 139.4 Yes
27 65 6 1.8 0.250 7.39 42.15 139.0
28 65 6 1.7 0.250 7.39 42.22 139.3 Yes
29 66 6 1.7 0.250 7.39 42.18 139.2
Test Specified
Air Content (%)NP to NP
Slump (in)2 to 6
Unit Weight (pcf)-
Comp. Strength (psi)4000
Mix Design
-
-
-
-
On-Site Notification(s)
Dwayne Felker with Tectonic Management
Group, Inc.
Item / Structure Type
Interior SOG
Mix Placed
United Companies 4000
Interior Spec Non-Chloride
Accelerator 1
On-site Notifications, Specification, and Mix Information
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0019; ver: 3Apr 29, 2024
Reviewed by:Work Order Date:Apr 1, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 1 of 2
Compressive Strength (ASTM C31 and C39 / AASHTO T22 and T23)
Sample No.Lab ID Age (d)Diameter (in)Area (in²)Fracture Type Max. Load (lb-f)Corrected
Strength (psi)
Strength at
Acceptance (psi)26
C3745 7 4.00 12.57 5 / Side 60,960 4,850 -
C3746 28 4.00 12.57 3 / Columnar 83,800 6,670 6,670
C3747 28 4.00 12.57 3 / Columnar 83,200 6,620 6,620
C3748 28 4.00 12.57 3 / Columnar 83,360 6,630 6,630
Average Compressive Strength (psi):6,640
Compressive Strength (ASTM C31 and C39 / AASHTO T22 and T23)
Sample No.Lab ID Age (d)Diameter (in)Area (in²)Fracture Type Max. Load (lb-f)Corrected
Strength (psi)
Strength at
Acceptance (psi)28
C3749 7 4.00 12.57 5 / Side 62,480 4,970 -
C3750 28 4.00 12.57 5 / Side 86,740 6,900 6,900
C3751 28 4.00 12.57 5 / Side 82,050 6,530 6,530
C3752 28 4.00 12.57 5 / Side 88,220 7,020 7,020
Average Compressive Strength (psi):6,820
Photos
Highlighted equals area represented.
Blue area equals approximate test locations.
Typical concrete placement.
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0019; ver: 3Apr 29, 2024
Reviewed by:Work Order Date:Apr 1, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 2 of 2
SOG Bound by GL C.0-H.0/1.0-6.5Placement Location:
Mays ConcreteConcrete Contractor:Performed by:John Riley
Placement Method:Pumped
Weather:Mostly Sunny
Finish Method:Broom Finished|Hand Finished|Machine
Finished|Trowel Finished
Total Quantity Placed:170.1 yd³
Comments:For test #2 at 60CY, we recorded out specification slump. Dwayne Felker with Tectonic Management Group was notified and
accepted the results.
Sample No.Location Sampled From Quantity
(yd³)
Truck
No.
Ticket
No.
Batch
Time
Test
Time
Air
Temp.
(ºF)
Water
Added
(gal)
30 G.5/6.0(See Location 1)Point of Delivery 10 56608 3308042 7:07 AM 8:05 AM 34 14
31 F.5/5.0(See Location 2)Point of Delivery 60 56620 3308047 8:13 AM 8:55 AM 35 0
32 E.0/4.5 (See Location 2)Point of Delivery 110 56621 3308054 9:29 AM 10:45 AM 41 7
33 C.25/4.0 (See Location 4)Point of Delivery 160 56607 3308060 11:05 AM 12:15 PM 44 7
Sampling (ASTM C172 / AASHTO R60 / CDOT CP61)
Field Tests (ASTM C138, C143, C231, and C1064 / AASHTO T119, T121, and T152)
Sample No.Concrete Temp. (ºF)Slump (in)Air Cont. (%)Meas. Vol. (ft³)Empty Meas. (lb)Full Meas. (lb)Unit Wt. (pcf)Lab Samples Cast
30 66 5.75 1.8 0.250 7.39 44.02 146.5 Yes
31 67 9 1.8 0.250 7.39 44.12 146.9
32 67 5.5 1.9 0.250 7.39 44.32 147.7 Yes
33 68 6 1.9 0.250 7.39 44.28 147.6
Test Specified
Air Content (%)NP to NP
Slump (in)2 to 6
Unit Weight (pcf)-
Comp. Strength (psi)4000
Mix Design
-
-
-
-
On-Site Notification(s)
Dwayne Felker with Tectonic Management
Group, Inc.
Item / Structure Type
Interior SOG
Mix Placed
United Companies 4000
Interior Spec Non-Chloride
Accelerator 1
On-site Notifications, Specification, and Mix Information
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0020; ver: 3Apr 30, 2024
Reviewed by:Work Order Date:Apr 2, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 1 of 2
Compressive Strength (ASTM C31 and C39 / AASHTO T22 and T23)
Sample No.Lab ID Age (d)Diameter (in)Area (in²)Fracture Type Max. Load (lb-f)Corrected
Strength (psi)
Strength at
Acceptance (psi)30
C3761 7 4.00 12.57 5 / Side 71,740 5,710 -
C3762 28 4.00 12.57 5 / Side 93,900 7,470 7,470
C3763 28 4.00 12.57 3 / Columnar 89,580 7,130 7,130
C3764 28 4.00 12.57 3 / Columnar 92,470 7,360 7,360
Average Compressive Strength (psi):7,320
Compressive Strength (ASTM C31 and C39 / AASHTO T22 and T23)
Sample No.Lab ID Age (d)Diameter (in)Area (in²)Fracture Type Max. Load (lb-f)Corrected
Strength (psi)
Strength at
Acceptance (psi)32
C3757 7 4.00 12.57 5 / Side 58,670 4,670 -
C3758 28 4.00 12.57 5 / Side 75,200 5,980 5,980
C3759 28 4.00 12.57 5 / Side 75,950 6,040 6,040
C3760 28 4.00 12.57 3 / Columnar 80,440 6,400 6,400
Average Compressive Strength (psi):6,140
Photos
Highlighted equals area represented.
Blue area equals approximate test locations.
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0020; ver: 3Apr 30, 2024
Reviewed by:Work Order Date:Apr 2, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 2 of 2
SOG Bound By GL (C.0-M.0/1.0-3.0) See Attached MapPlacement Location:
Mays ConcreteConcrete Contractor:Performed by:John Riley
Placement Method:Drop Chuted
Weather:Sunny
Finish Method:Broom Finished|Hand Finished|Vibrated-
Internally|Rodded|Machine Finished|Trowel
Finished
Total Quantity Placed:30.01 yd³
Comments:For test 1 the slump was documented that it exceeded specification. Dwayne Felker with Tectonic Management Group was
notified and accepted the results.
Sample No.Location Sampled From Quantity
(yd³)
Truck
No.
Ticket
No.
Batch
Time
Test
Time
Air
Temp.
(ºF)
Water
Added
(gal)
34 K.5/2.5 (See Location 1)Point of Delivery 10 NA NA 7:10 AM 7:40 AM 40 0
Sampling (ASTM C172 / AASHTO R60 / CDOT CP61)
Field Tests (ASTM C138, C143, C231, and C1064 / AASHTO T119, T121, and T152)
Sample No.Concrete Temp. (ºF)Slump (in)Air Cont. (%)Meas. Vol. (ft³)Empty Meas. (lb)Full Meas. (lb)Unit Wt. (pcf)Lab Samples Cast
34 67 8 2.0 0.250 7.39 44.44 148.2 Yes
Compressive Strength (ASTM C31 and C39 / AASHTO T22 and T23)
Sample No.Lab ID Age (d)Diameter (in)Area (in²)Fracture Type Max. Load (lb-f)Corrected
Strength (psi)
Strength at
Acceptance (psi)34
C3813 7 4.00 12.57 5 / Side 68,730 5,470 -
C3814 28 4.00 12.57 5 / Side 98,990 7,880 7,880
C3815 28 4.00 12.57 3 / Columnar 98,530 7,840 7,840
C3816 28 4.00 12.57 3 / Columnar 94,420 7,510 7,510
Average Compressive Strength (psi):7,740
Test Specified
Air Content (%)NP to NP
Slump (in)2 to 6
Unit Weight (pcf)-
Comp. Strength (psi)4000
Mix Design
-
-
-
-
On-Site Notification(s)
Dwayne Felker with Tectonic Management
Group, Inc.
Item / Structure Type
Interior SOG
Mix Placed
United Companies 4000
Interrior Spec Non-Chloride
Aceelerator 1
On-site Notifications, Specification, and Mix Information
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0022; ver: 3May 9, 2024
Reviewed by:Work Order Date:Apr 11, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 1 of 2
Photos
Highlighted equals area represented.
Blue equals approximate test locations.
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0022; ver: 3May 9, 2024
Reviewed by:Work Order Date:Apr 11, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 2 of 2
10” Radiant Paving West of Hanger (see attached map)Placement Location:
Mays Concrete Concrete Contractor:Performed by:Cody Peacock
Placement Method:Pumped|Hand Screeded
Weather:Night|Calm
Finish Method:Hand Finished|Trowel Finished
Total Quantity Placed:160 yd³
Comments:Concrete was scheduled for 7:00 a.m.
Concrete started at 7:50 a.m.
Sample No.Location Sampled From Quantity
(yd³)
Truck
No.
Ticket
No.
Batch
Time
Test
Time
Air
Temp.
(ºF)
Water
Added
(gal)
35 Location 1 Point of Delivery 10 56607 3308218 6:56 AM 7:58 AM 41 10
36 Location 2 Point of Delivery 60 999060 3308223 8:35 AM 9:06 AM 52 0
37 Location 3 Point of Delivery 110 56230 3308228 9:47 AM 10:40 AM 52 0
Sampling (ASTM C172 / AASHTO R60 / CDOT CP61)
Field Tests (ASTM C138, C143, C231, and C1064 / AASHTO T119, T121, and T152)
Sample No.Concrete Temp. (ºF)Slump (in)Air Cont. (%)Meas. Vol. (ft³)Empty Meas. (lb)Full Meas. (lb)Unit Wt. (pcf)Lab Samples Cast
35 61 6 6.0 0.250 8.50 43.80 141.2 Yes
36 61 6 6.0 0.250 8.50 43.80 141.2
37 61 6 6.2 0.250 8.50 43.70 140.8 Yes
Test Specified
Air Content (%)4.5 to 7.5
Slump (in)2 to 6
Unit Weight (pcf)-
Comp. Strength (psi)4500
Mix Design
-
-
-
-
On-Site Notification(s)
Dwayne Felker with Tectonic Management
Group, Inc.
Item / Structure Type
Exterior Site Concrete
Mix Placed
United Companies Class
D/P (2023072)
On-site Notifications, Specification, and Mix Information
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0023; ver: 3May 31, 2024
Reviewed by:Work Order Date:May 3, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 1 of 2
Compressive Strength (ASTM C31 and C39 / AASHTO T22 and T23)
Sample No.Lab ID Age (d)Diameter (in)Area (in²)Fracture Type Max. Load (lb-f)Corrected
Strength (psi)
Strength at
Acceptance (psi)35
C4121 7 4.00 12.57 3 / Columnar 59,210 4,710 -
C4122 7 4.00 12.57 5 / Side 60,450 4,810 -
C4123 28 4.00 12.57 3 / Columnar 69,440 5,520 5,520
C4124 28 4.00 12.57 3 / Columnar 76,800 6,110 6,110
C4125 28 4.00 12.57 5 / Side 74,230 5,910 5,910
Average Compressive Strength (psi):5,850
Compressive Strength (ASTM C31 and C39 / AASHTO T22 and T23)
Sample No.Lab ID Age (d)Diameter (in)Area (in²)Fracture Type Max. Load (lb-f)Corrected
Strength (psi)
Strength at
Acceptance (psi)37
C4126 7 4.00 12.57 5 / Side 64,070 5,100 -
C4127 7 4.00 12.57 5 / Side 66,850 5,320 -
C4128 28 4.00 12.57 3 / Columnar 84,360 6,710 6,710
C4129 28 4.00 12.57 5 / Side 84,250 6,700 6,700
C4130 28 4.00 12.57 3 / Columnar 84,680 6,740 6,740
Average Compressive Strength (psi):6,720
Photos
Highlighted = Area Represented
Blue = Approximately Test Locations
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0023; ver: 3May 31, 2024
Reviewed by:Work Order Date:May 3, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 2 of 2
Western Concrete Apron (See attached map)Placement Location:
Mays ConcreteConcrete Contractor:Performed by:John Riley
Placement Method:Tailgated
Weather:Sunny
Finish Method:Broom Finished|Hand Finished|Trowel
Finished
Total Quantity Placed:90.00 yd³
Comments:Test 1: United companies added 8 ounces of liquid air.
Test 2: Air content was non-conforming but load was accepted by Dwayne Felker.
Truck #7 was not tested but was rejected for high slump by Mays concrete.
Sample No.Location Sampled From Quantity
(yd³)
Truck
No.
Ticket
No.
Batch
Time
Test
Time
Air
Temp.
(ºF)
Water
Added
(gal)
38 Location 1 Point of Delivery 10.00 56375 3308245 6:57 AM 8:05 AM 35 1
39 Location 2 Point of Delivery 60.00 56375 3308250 8:52 AM 9:40 AM 40 0
40 Location 3 Point of Delivery 80.00 999018 3308254 11:10 AM 10:40 AM 44 0
Sampling (ASTM C172 / AASHTO R60 / CDOT CP61)
Field Tests (ASTM C138, C143, C231, and C1064 / AASHTO T119, T121, and T152)
Sample No.Concrete Temp. (ºF)Slump (in)Air Cont. (%)Meas. Vol. (ft³)Empty Meas. (lb)Full Meas. (lb)Unit Wt. (pcf)Lab Samples Cast
38 68 6 6.1 0.250 8.53 43.75 140.9 Yes
39 68 5.5 4.2 0.250 8.53 44.68 144.6
40 70 5.5 5.3 0.250 8.53 44.40 143.5
Compressive Strength (ASTM C31 and C39 / AASHTO T22 and T23)
Sample No.Lab ID Age (d)Diameter (in)Area (in²)Fracture Type Max. Load (lb-f)Corrected
Strength (psi)
Strength at
Acceptance (psi)38
C4178 7 4.00 12.57 3 / Columnar 59,890 4,770 -
C4179 28 4.00 12.57 5 / Side 80,160 6,380 6,380
C4180 28 4.00 12.57 3 / Columnar 78,250 6,230 6,230
C4181 28 4.00 12.57 3 / Columnar 79,840 6,350 6,350
Average Compressive Strength (psi):6,320
Test Specified
Air Content (%)4.5 to 7.5
Slump (in)2 to 6
Unit Weight (pcf)-
Comp. Strength (psi)4500
Mix Design
-
-
-
-
On-Site Notification(s)
Dwayne Felker with Tectonic Management
Group, Inc.
Item / Structure Type
Exterior Site Concrete
Mix Placed
United Companies 2023072
Class D/P Non-Chloride
Accelerator 1
On-site Notifications, Specification, and Mix Information
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0025; ver: 3Jun 5, 2024
Reviewed by:Work Order Date:May 8, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 1 of 2
Photos
Highlighted equals area represented.
Blue equals approximate test locations.
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0025; ver: 3Jun 5, 2024
Reviewed by:Work Order Date:May 8, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 2 of 2
Northern Concrete Apron (See attached map)Placement Location:
MaysConcrete Contractor:Performed by:John Riley
Placement Method:Pumped
Weather:Sunny
Finish Method:Broom Finished|Hand Finished|Trowel
Finished
Total Quantity Placed:75.00 yd³
Comments:Test 1: Air content was non-conforming but truck was accepted by Dwayne Felker.
Test 2: United Companies added 20 oz of liquid air.
Sample No.Location Sampled From Quantity
(yd³)
Truck
No.
Ticket
No.
Batch
Time
Test
Time
Air
Temp.
(ºF)
Water
Added
(gal)
41 Location 1 Point of Delivery 10.00 56607 3308286 7:14 AM 8:10 AM 50 10
42 Location 2 Point of Delivery 30.00 999302 3308288 8:10 AM 9:20 AM 55 0
Sampling (ASTM C172 / AASHTO R60 / CDOT CP61)
Field Tests (ASTM C138, C143, C231, and C1064 / AASHTO T119, T121, and T152)
Sample No.Concrete Temp. (ºF)Slump (in)Air Cont. (%)Meas. Vol. (ft³)Empty Meas. (lb)Full Meas. (lb)Unit Wt. (pcf)Lab Samples Cast
41 70 6 4.5 0.250 8.53 44.53 144.0
42 68 6 5.8 .250 8.53 44.00 141.9 Yes
Compressive Strength (ASTM C31 and C39 / AASHTO T22 and T23)
Sample No.Lab ID Age (d)Diameter (in)Area (in²)Fracture Type Max. Load (lb-f)Corrected
Strength (psi)
Strength at
Acceptance (psi)42
C4230 7 4.00 12.57 5 / Side 54,970 4,370 -
C4231 28 4.00 12.57 3 / Columnar 67,510 5,370 5,370
C4232 28 4.00 12.57 3 / Columnar 67,600 5,380 5,380
C4233 28 4.00 12.57 3 / Columnar 70,200 5,590 5,590
Average Compressive Strength (psi):5,450
Test Specified
Air Content (%)4.5 to 7.5
Slump (in)2 to 6
Unit Weight (pcf)-
Comp. Strength (psi)4500
Mix Design
-
-
-
-
On-Site Notification(s)
Dwayne Felker with Tectonic Management
Group, Inc.
Item / Structure Type
Exterior Site Concrete
Mix Placed
United Companies 2023072
Class D/P
On-site Notifications, Specification, and Mix Information
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0026; ver: 3Jun 7, 2024
Reviewed by:Work Order Date:May 10, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 1 of 2
Photos
Highlighted equals area represented.
Blue equals approximate test locations.
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0026; ver: 3Jun 7, 2024
Reviewed by:Work Order Date:May 10, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 2 of 2
Concrete Pavement on N. Side of Hanger, See AttachedPlacement Location:
Mays concrete Concrete Contractor:Performed by:Jeff Haney
Placement Method:Pumped
Discrepancies
The following discrepancies were added as a result of services performed. It is the contractor's responsibility to resolve reported
discrepancies and schedule retesting. A list of open discrepancies can be provided upon request.
Number Description
Concrete 1 Test 3, N. Pavement, location marked by number 3 on map attached to
report. Low air (3.5). Asked pump operator and concrete truck driver to wait
for test results before continuing to pour.
Weather:Calm|Clear|Sunny
Finish Method:Trowel Finished|Hand Finished|Float
Finished
Total Quantity Placed:110 yd³
Comments:While conducting test 3(70 yards), pump operator and concrete truck driver were asked to hold until results were confirmed.
They did not wait and had poured/pumped the majority of truck before test was finished. The air came out at 3.5% (non-
conforming). Attached photos mark location of placed non-conforming concrete.
Sample No.Location Sampled From Quantity
(yd³)
Truck
No.
Ticket
No.
Batch
Time
Test
Time
Air
Temp.
(ºF)
Water
Added
(gal)
43 Test 1 Point of Delivery 10 56607 3308342 6:27 AM 7:35 AM 36 0
44 Test 2 Point of Delivery 40 56620 3308345 7:20 PM 8:15 AM 40 0
45 Test 3 Point of Delivery 70 999302 3308348 7:55 AM 9:00 AM 44 0
46 Test 4 Point of Delivery 80 999018 3308349 8:13 AM 9:30 AM 46 0
47 Test 5 Point of Delivery 90 56608 3308350 8:27 AM 9:35 AM 46 0
Sampling (ASTM C172 / AASHTO R60 / CDOT CP61)
Field Tests (ASTM C138, C143, C231, and C1064 / AASHTO T119, T121, and T152)
Sample No.Concrete Temp. (ºF)Slump (in)Air Cont. (%)Meas. Vol. (ft³)Empty Meas. (lb)Full Meas. (lb)Unit Wt. (pcf)Lab Samples Cast
43 68 5 5.8 0.250 7.38 42.45 140.3
44 74 6 5.8 0.250 7.38 42.50 140.5 Yes
45 73 5 3.5 0.250 7.38 43.50 144.5
46 72 5.5 5.0 0.250 7.38 43.18 143.2
47 72 5 5.3 0.250 7.38 43.14 143.0 Yes
Test Specified
Air Content (%)4.5 to 7.5
Slump (in)2 to 6
Unit Weight (pcf)-
Comp. Strength (psi)4500
Mix Design
-
-
-
-
On-Site Notification(s)
Dwayne Felker with Tectonic Management
Group, Inc.
Item / Structure Type
Exterior Site Concrete
Mix Placed
United 37010750
On-site Notifications, Specification, and Mix Information
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0027; ver: 3Jun 19, 2024
Reviewed by:Work Order Date:May 22, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 1 of 3
Compressive Strength (ASTM C31 and C39 / AASHTO T22 and T23)
Sample No.Lab ID Age (d)Diameter (in)Area (in²)Fracture Type Max. Load (lb-f)Corrected
Strength (psi)
Strength at
Acceptance (psi)44
C4330 7 4.00 12.57 5 / Side 51,400 4,090 -
C4331 28 4.00 12.57 5 / Side 67,740 5,390 5,390
C4332 28 4.00 12.57 4 / Cone & Shear 66,850 5,320 5,320
C4333 28 4.00 12.57 5 / Side 66,560 5,300 5,300
Average Compressive Strength (psi):5,340
Compressive Strength (ASTM C31 and C39 / AASHTO T22 and T23)
Sample No.Lab ID Age (d)Diameter (in)Area (in²)Fracture Type Max. Load (lb-f)Corrected
Strength (psi)
Strength at
Acceptance (psi)47
C4334 7 4.00 12.57 3 / Columnar 60,520 4,820 -
C4335 28 4.00 12.57 5 / Side 80,050 6,370 6,370
C4336 28 4.00 12.57 4 / Cone & Shear 79,560 6,330 6,330
C4337 28 4.00 12.57 5 / Side 81,060 6,450 6,450
Average Compressive Strength (psi):6,380
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0027; ver: 3Jun 19, 2024
Reviewed by:Work Order Date:May 22, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 2 of 3
Photos
Photo shows location of discrepancy.
Highlighted shows location of concrete placement. Red numbers 1-5
indicate test and sampling locations and correspond to tests in report. Red
square marks approximate location of non conforming concrete.
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0027; ver: 3Jun 19, 2024
Reviewed by:Work Order Date:May 22, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 3 of 3
Eastern Concrete Apron & Southern Low Flow Liner (See attached map)Placement Location:
Mays ConcreteConcrete Contractor:Performed by:John Riley
Placement Method:Pumped
Weather:Sunny
Finish Method:Broom Finished|Hand Finished|Trowel
Finished
Total Quantity Placed:80.00 yd³
Sample No.Location Sampled From Quantity
(yd³)
Truck
No.
Ticket
No.
Batch
Time
Test
Time
Air
Temp.
(ºF)
Water
Added
(gal)
48 Location 1 Point of Delivery 10.00 56607 3308376 6:32 AM 7:15 AM 55 0
49 Location 2 Point of Delivery 50.00 999770 3308380 7:47 AM 8:25 AM 60 0
Sampling (ASTM C172 / AASHTO R60 / CDOT CP61)
Field Tests (ASTM C138, C143, C231, and C1064 / AASHTO T119, T121, and T152)
Sample No.Concrete Temp. (ºF)Slump (in)Air Cont. (%)Meas. Vol. (ft³)Empty Meas. (lb)Full Meas. (lb)Unit Wt. (pcf)Lab Samples Cast
48 71 5 5.6 0.250 8.53 44.17 142.6 Yes
49 74 6 5.9 0.250 8.53 44.08 142.2
Compressive Strength (ASTM C31 and C39 / AASHTO T22 and T23)
Sample No.Lab ID Age (d)Diameter (in)Area (in²)Fracture Type Max. Load (lb-f)Corrected
Strength (psi)
Strength at
Acceptance (psi)48
C4390 7 4.00 12.57 3 / Columnar 59,840 4,760 -
C4391 28 4.00 12.57 3 / Columnar 69,190 5,500 5,500
C4392 28 4.00 12.57 3 / Columnar 67,900 5,400 5,400
C4393 28 4.00 12.57 3 / Columnar 72,660 5,780 5,780
Average Compressive Strength (psi):5,560
Test Specified
Air Content (%)4.5 to 7.5
Slump (in)2 to 6
Unit Weight (pcf)-
Comp. Strength (psi)4500
Mix Design
-
-
-
-
On-Site Notification(s)
Dwayne Felker with Tectonic Management
Group, Inc.
Item / Structure Type
Exterior Site Concrete
Mix Placed
United Companies 2023072
Class D/P
On-site Notifications, Specification, and Mix Information
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0028; ver: 3Jun 26, 2024
Reviewed by:Work Order Date:May 29, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 1 of 2
Photos
Highlighted equals area represented.
Blue equals approximate test locations.
Test location 1: Accurate dowel and support placements were observed
prior to pour.
Test location 1: Typical concrete placement.
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0028; ver: 3Jun 26, 2024
Reviewed by:Work Order Date:May 29, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 2 of 2
Southern Splash Pads (See attached map)Placement Location:
Mays CocnreteConcrete Contractor:Performed by:John Riley
Placement Method:Pumped
Weather:Sunny
Finish Method:Trowel Finished|Hand Finished|Broom
Finished
Total Quantity Placed:7.5 yd³
Sample No.Location Sampled From Quantity
(yd³)
Truck
No.
Ticket
No.
Batch
Time
Test
Time
Air
Temp.
(ºF)
Water
Added
(gal)
50 Location 1 Point of Delivery 7.5 56607 3308624 8:54 AM 9:50 AM 80 8
Sampling (ASTM C172 / AASHTO R60 / CDOT CP61)
Field Tests (ASTM C138, C143, C231, and C1064 / AASHTO T119, T121, and T152)
Sample No.Concrete Temp. (ºF)Slump (in)Air Cont. (%)Meas. Vol. (ft³)Empty Meas. (lb)Full Meas. (lb)Unit Wt. (pcf)Lab Samples Cast
50 85 3 4.5 0.250 8.53 45.10 146.3 Yes
Compressive Strength (ASTM C31 and C39 / AASHTO T22 and T23)
Sample No.Lab ID Age (d)Diameter (in)Area (in²)Fracture Type Max. Load (lb-f)Corrected
Strength (psi)
Strength at
Acceptance (psi)50
C4897 7 4.00 12.57 3 / Columnar 61,710 4,910 -
Average Compressive Strength (psi):
Test Specified
Air Content (%)4.5 to 7.5
Slump (in)2 to 6
Unit Weight (pcf)-
Comp. Strength (psi)4500
Mix Design
-
-
-
-
On-Site Notification(s)
Dwayne Felker with Tectonic Management
Group, Inc.
Item / Structure Type
Exterior Site Concrete
Mix Placed
United Companies 2023072
Class D/P 1% MB Delvo
Retarder
On-site Notifications, Specification, and Mix Information
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0029; ver: 2Jul 20, 2024
Reviewed by:Work Order Date:Jul 12, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.
101 Airpark Drive, Unit A, Gypsum, Colorado www.groundeng.com 970-524-0720
Englewood | Commerce City | Loveland | Granby | Gypsum | Colorado Springs Page 1 of 2
Photos
Highlighted equals area represented.
Red equals approximate test location.
6 splash pads located on south side of hanger.
Tectonic Management Group, Inc.
6695 W. 48th Avenue
Wheat Ridge, CO 80033
Nicholas Marquez
Atlantic Aviation Hangar 6
Client:
Report Date:Work Order No.:
Concrete
23-6522.Concrete.0029; ver: 2Jul 20, 2024
Reviewed by:Work Order Date:Jul 12, 2024 Chris Hutto
Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. Unless noted otherwise, specimens were received in adequate condition.
Compressive strength specimens, if tested, were capped in accordance with ASTM C1231 or ASTM C617, as applicable. This report should not be reproduced, except in full, without the written
permission of GROUND Engineering Consultants, Inc.