HomeMy WebLinkAboutSubsoils Report for Foundation Designrc n $N;1f;'ff:":'flr:f*iiyi'*"
An Emplcygs Owned Compony
5020 Counfy Road 154
Glenwood Springs, CO 81601
phone: (970) 945-7988
fax: (970) 945-8454
email: kaglenwood@kumarusa.com
www.kunarusa.com
Office Locatiors: Denver- (lIQ), Parker, Colorado Springs, Fort Collins, Glenvood Springs, and Summit Coutty, Colorado
SUBSOIL STUDY
FOR X'OUNDATION DESIGN
PROPOSED RESIDENCE
240 RIPPY LANE
NEW CASTLE, COLORADO
PROJECT NO.23-7-568
NOVEMBER 20, 2023
PREPARED F'OR:
TIM F'INHOLM
P.O. BOX 503
NEW CASTLE, COLORADO 81647
tfi nholm@uniq ueprop.com
TABLE OF CONTENTS
PIIRPOSE AND SCOPE OF STUDY
PROPOSED CONSTRUCTION
SITE CONDITIONS
FIELD EXPLORATION
SUBSURFACE CONDITIONS
DESIGN RECOMMENDATIONS ........--..
FOI.INDATIONS
FOLTNDATION AND RETAINING WALLS .........
FLOOR SLABS
UNDERDRAIN SYSTEM ..............
SURFACE DRAINAGE
LIMITATIONS.......-
FIGTIRE I - LOCATION OF EXPLORATORY BORINGS
FIGURE 2 - LOGS OF EXPLORATORY BORINGS
FIGURE 3 - LEGEND AND NOTES
FIGURE 4 - GRADATION TEST RESULTS
TABLE 1- SUMMARY OF LABORATORY TEST RESULTS
-1-
I
1
",
a-L-
-2-
-3-
-4-
4-
5-
5
Kumar & Associates, lnc. o Project No.23-7-568
PURPOSE AND SCOPE OF STUDY
This report presents the results of a subsoil study for a proposed residence to be locate d at 240
Rippy Lane, New Castle, Colorado. The project site is shown on Figure l. The purpose of the
study was to develop recommendations for the foundation design. The study was conducted in
accordance with our agreement for geotechnical engineering services to Tim Finholm dated
September 26,2023.
A field exploration program consisting of exploratory borings was conducted to obtain
information on the subsurface conditions. Samples of the subsoils obtained during the field
exploration were tested in the laboratory to determine their classification and other engineering
characteristics. The results of the field exploration and laboratory testing were analyzed to
develop recommendations for foundation types, depths and allowable pressures for the proposed
building foundation. This report summarizes the data obtained during this study and presents our
conclusions, design recommendations and other geotechnical engineering considerations based
on the proposed construction and the subsurface conditions encountered.
PROPOSED CONSTRUCTION
Plans for the proposed residence were conceptual at the time of our study. The proposed
residence is assumed to be a one- or two-story stmcture located on the site in the area of the
borings shown on Figure 1. Ground floor could be slab-on-grade or structural over crawlspace.
Grading for the structure is assumed to be relatively minor with cut depths between about 2 to 4
feet. We assume relatively light foundation loadings, typical of the proposed type of
construction.
If building loadings, location or grading plans change significantly from those described above,
we should be notified to re-evaluate the recommendations contained in this report.
SITE CONDITIONS
The subject site was developed with an access drive, single-story residence and shop at the time
of our field exploration. The ground surface was gently sloping down to the southeast at a grade
of between 3 and 5 percent. Vegetation consists of landscaped grass and aspen trees. The
Colorado River borders the property to the southeast.
Kumar & Associates, Inc. @ Project No.23-7-568
-2-
F'IELD EXPLORATION
The field exploration for the proj ect was conducted on October ll , 2023 . Two exploratory
borings were drilled at the locations shown on Figure 1 to evaluate the subsurface conditions.
The borings were advanced with 4-inch diameter continuous flight augers powered by a truck-
mounted CME-45B drill rig. The borings were logged by a representative of Kumar &
Associates, Inc.
Samples of the subsoils were taken with a l%-inch I.D. spoon sampler. The sampler was driven
into the subsoils at various depths with blows from a 140-pound hammer falling 30 inches. This
test is similar to the standard penetration test described by ASTM Method D-1586. The
penetration resistance values are an indication of the relative density or consistency of the
subsoils. Depths at which the samples were taken and the penetration resistance values are
shown on the Logs of Exploratory Borings, Figure 2. The samples were returned to our
laboratory for review by the project engineer and testing.
SUBST]RFACE CONDITIONS
Graphic logs of the subsurface conditions encountered at the site are shown on Figure 2. The
subsoils consist of about 4 to 6 inches of topsoii overlying dense, very sandy silty gravel with
cobbles and possible boulders to the maximum explored depth of 3Yz feet. Drilling in the coarse
granular soils with auger equipment was difficult due to the cobbles and possible boulders and
drilling refusal was encountered in the deposit.
Laboratory testing performed on samples obtained from the borings included natural moisture
content and gradation analyses. Results of gradation analyses performed on samples (minus i%-
inch fraction) of the coarse granular subsoils are shown on Figure 4. The laboratory testing is
summarized in Table l.
No free water was encountered in the borings at the time of drilling and the subsoils were
slightly moist.
DESIGN RECOMMENDATIONS
FOLINDATIONS
Considering the subsurface conditions encountered in the exploratory borings and the nature of
the proposed construction, we recommend the building be founded with spread footings bearing
on the natural granular soils.
Kumar & Associates, lnc. @ Project No. 23-7-568
3-
The design and construction criteria presented below should be observed for a spread footing
foundation system.
1) Footings placed on the undisturbed natural granular soils should be designed for
an allowable bearing pressure of 3,000 psf. Based on experience, we expect
settlement of footings desigrredfidfficted as discussed in this section will
be about 1 inch or less.
2) The footings should have a minimum width of 16 inches for continuous walls and
2 feet for isolated pads.
3) Exterior footings and footings beneath unheated areas should be provided with
adequate soil cover above their bearing elevation for frost protection. Placement
of foundations at least 36 inches below exterior grade is typically used in this
area.
4) Continuous foundation walls should be reinforced top and bottom to span local
anomalies such as by assuming an unsupported length of at least l0 feet.
Foundation walls acting as retaining structures should also be designed to resist
lateral earth pressures as discussed in the "Foundation and Retaining Walls"
section of this report.
5) Topsoil and any loose disturbed soils should be removed and the footing bearing
level extended down to the relatively dense natural granular soils. The exposed
soils in footing area should then be moistened and compacted. If water seepage is
encountered, the footing areas should be dewatered before concrete placement.
6) A representative ofthe geotechnical engineer should observe all footing
excavations prior to concrete placement to evaluate bearing conditions.
FOTINDATION AND RETAINING WALLS
Foundation walls and retaining structwes which are laterally supported and can be expected to
undergo only a slight amount of deflection should be designed for a lateral earth pressure
computed on the basis of an equivalent fluid unit weight of at least 45 pcf for backfill consisting
of the on-site granular soils. Cantilevered retaining structures which are separate from the
residence and can be expected to deflect sufficiently to mobilize the full active earth pressure
condition should be designed for a lateral earth pressure computed on the basis of an equivalent
fluid unit weight of at least 35 pcf for backfill consisting of the on-site granular soils. Backfill
should not contain organics, topsoil or rock larger than about 4 inches.
All foundation and retaining sffuctures should be designed for appropriate hydrostatic and
swcharge pressures such as adjacent footings, traffic, construction materials and equipment. The
pressures recommended above assume drained conditions behind the walls and a horizontal
backfill surface. The buildup of water behind a wall or an upward sloping backfill surface will
Kumar & Associates, lnc. @ Project No.23-7-568
-4-
increase the lateral pressure imposed on a foundation wall or retaining structure. An underdrain
should be provided to prevent hydrostatic pressure buildup behind walls.
Backfill should be placed in uniform lifts and compacted to at least 90% of the maxlmum
standard Proctor density at a moisture content near optimum. Backfill placed in pavement and
walkway areas should be compacted to at least 95Ya of the maximum standard Proctor density.
Care should be taken not to overcompact the backfill or use large equipment near the wall, since
this could cause excessive lateral pressure on the wall. Some settlement of deep foundation wall
backfill should be expected, even if the material is placed correctly, and could result in distress to
facilities constructed on the backfill.
The lateral resistance of foundation or retaining wall footings will be a combination of the
sliding resistance of the footing on the foundation materials and passive earth pressure against
the side of the footing. Resistance to sliding at the bottoms of the footings can be calculated
based on a coefficient of friction of 0.50. Passive pressure of compacted backfill against the
sides of the footings can be calculated using an equivalent fluid unit weight of 450 pcf. The
coefficient of friction and passive pressure values recommended above assume ultimate soil
strength. Suitable factors of safety should be included in the design to limit the strain which will
occur at the ultimate strength, particularly in the case of passive resistance. Fill placed against
the sides of the footings to resist lateral loads should be compacted to at least 95Yo of the
maxjmum standard Proctor density at a moisture content near optimum.
FLOOR SLABS
The natural on-site soils, exclusive of topsoil, are suitable to support lightly loaded slab-on-grade
construction. To reduce the effects of some differential movement, floor slabs should be
separated from all bearing walls and columns with expansion joints which allow unrestrained
vertical movement. Floor slab control joints should be used to reduce damage due to shrinkage
cracking. The requirements for joint spacing and slab reinforcement should be established by the
designer based on experience and the intended slab use. A minimum 4-inch layer of relatively
well graded sand and gravel such as road base should be placed beneath slabs for support. This
material should consist of minus 2-inch aggregate with at least 50% retained on the No. 4 sieve
and less than 12o/o passing the No. 200 sieve.
All fill materials for support of floor slabs should be compacted to at least 95% of maxlmum
standard Proctor density at a moisture content near optimum. Required fiIl can consist of the on-
site granular soils devoid of vegetation, topsoil and oversized rock.
TINDERDRAIN SYSTEM
Kumar & Associates, lnc. @ Project No.23-7-568
5
The proposed shallow foundations should not need a perimeter foundation drain, provided that
the exterior foundation wall backfill is well-compacted and good surface drainage, as described
below, is maintained around the houses.
SURFACE DRAINAGE
The following drainage precautions should be observed during consffuction and maintained at all
times after the residence has been completed:
l) Inundation ofthe foundation excavations andunder slab areas shouldbe avoided
during consffuction.
2) Exterior backfill should be adjusted to near optimum moisture and compacted to
at least 95% of the maximum standard Proctor density in pavement and slab areas
and to at ieast 90% of the maximum standard Proctor density in landscape areas.
3) The ground surface surrounding the exterior of the building should be sloped to
drain away from the foundation in all directions. We recommend a minimum
slope of 6 inches in the first l0 feet in unpaved areas and a minimum slope of 2/'
inches in the first l0 feet in paved areas. Free-draining wall backfill should be
covered with filter fabric and capped with about 2 feet of the on-site finer graded
soils to reduce surface water infiltration.
4) Roof downspouts and drains should discharge well beyond the limits of all
backfill.
LIMITATIONS
This study has been conducted in accordance with generally accepted geotechnical engineering
principles and practices in this area at this time. We make no warrantlr either express or implied.
The conclusions and recommendations submitted in this report are based upon the data obtained
from the exploratory borings drilled at the locations indicated on Figure 1, the proposed type of
construction and our experience in the area. Our services do not include determining the
presence, prevention or possibility of mold or other biological contaminants (MOBC) developing
in the future. If the client is concerned about MOBC, then a professional in this special field of
practice should be consulted. Ow findings include interpolation and extrapolation of the
subsurface conditions identified at the exploratory borings and variations in the subsurface
conditions may not become evident until excavation is performed. If conditions encountered
during construction appear different from those described in this report, we should be notified so
that re-evaluation of the recommendations may be made.
This report has been prepared for the exclusive use by our client for design pulposes. We are not
responsible for technical interpretations by others of our information. As the project evolves, we
should provide continued consultation and field services during construction to review and
Kumar & Associates, lnc. @ Project No.23-7-568
-6-
monitor the implementation of our recommendations, and to verify that the recommendations
have been appropriately interpreted. Significant design changes may require additional analysis
or modifications to the recommendations presented herein. We recommend on-site observation
ofexcavations and foundation bearing strata and testing ofstructural fill by a representative of
the geotechnical engineer.
Respectfully Submitted,
Kurnar & Associates, lnc.
James H. Parsons, P.E.
Reviewed by:
fl*_/-
Steven L. Pawlak, P.E.
JHP/sls
t\.
w
58663
/ht
Kumar & Associates, lne. 6 Project No. 23-7-568
50 50 100
APPROXIMATE SCALE-FEET
23-7 -568 Kumar & Associates LOCATION OF EXPLORATORY BORINGS Fig. 1
I
+4=51
-2OO=1 1
BORING 1 BORING 2
0 0
FUU
t!
II
Fo-
LJo
I
FL!htt!
IIFo-
LIo
73/12
WC=2,2
*4=51
tnn-a
25/12
5 q
LEG END
TOPSOIL; SAND, GRAVELLY, CLAYEY, ORGANICS, FIRM, MOIST, DARK BROWN
GRAVEL AND COBBLES (GM); VERY SANDY, VERY SILTY, PROBABLE BOULDERS, DENSE,
SLIGHTLY MOIST, LIGHT BROWN.
I
t
DRTVE SAMpLE, 1 3/8-|NCH r.D. SPL|T SP00N STANDARD PENETRATION TEST.
DISTURBED BULK SAMPLE.
1'/4' DRIVE SAMPLE BLOW COUNT. INDICATES THAT 73 BLOWS OF A 14o-POUND HAMMERtr/ tz FALLTNG Jo TNCHES WERE REQUIRED To DRtvE THE SAMpLER t2 tNcHES.
i PRACTICAL AUGER REFUSAL. WHERE SHOWN ABOVE BOTTOM OF BORING, INDICATES THAT
MULTIPLE ATTEMPTS WHERE MADE TO ADVANCE THE HOLE.
NOTES
1. THE EXPLORATORY BORINGS WERE DRILLED ON OCTOBER 1 1, 2023 WITH A 4-INCH-DIAMETER
CONTINUOUS-FLIGHT POWER AUGER.
2. THE LOCATIONS OF THE EXPLORATORY BORINGS WERE MEASURED APPROXIMATELY BY PACING
FROM FEATURES SHOWN ON THE SITE PLAN PROVIDED.
3. THE ELEVATIONS OF THE EXPLORATORY BORINGS WERE NOT MEASURED AND THE LOGS OF
THE EXPLORATORY BORINGS ARE PLOTTED TO DEPTH.
4. THE EXPLORATORY BORING LOCATIONS SHOULD BE CONSIDERED ACCURATE ONLY TO THE
DEGREE IMPLIED BY THE METHOD USED.
5. THE LINES BETWEEN MATERIALS SHOWN ON THE EXPLORATORY BORINC LOGS REPRESENT THE
APPROXIMATE BOUNDARIES BETWEEN MATERIAL TYPES AND THE TRANSITIONS MAY BE GRADUAL.
6. GROUNDWATER WAS NOT ENCOUNTERED IN THE BORINGS AT THE TIME OF DRILLING
7. LABORATORY TEST RESULTS:
WC = WATER CONTENT (%) (ASTM D2216);
+4 = PERCENTAGE RETAINED ON NO. 4 SIEVE (ASTU OOSIS);
-200= PERCENTAGE PASSING N0. 200 SIEVE (ASTM D1140).
Kumar & Associates LOGS OF EXPLORATORY BORINGS Fig. 223-7-568
too
80
80
70
60
50
40
so
20
10
0
I{YDROVETER ANALYSIS SIEVE ANALYSIS
lME RADINCS
I,' HRS 7 HRSMrN aduttr lvlx IMIN
U.S. STANDARD SERIES CLEAF SQUARE OPENINCS
:/rr tl^. 1 t/t.
-, i----- - t- --1-
'l,tl
.i. f
-/ "t'
t-
'I
SAND CRAVEL
FINE MEDIUM lcoanss FINE COARSE
o
d
to
20
30
ir{t
50
a0
80
90
E
E
E
F
100
.150 ,600
32
DIAMETER OF IN MILLI
CLAY TO SILT COBBLES
GRAVEL 5' % SAND 41 %
LIQUID LIMIT - PLASTICITY INDEX
SAMPLE OF: Sllghlly Sllly V€ry Sondy Grqval
SILT AND CLAY A %
FROM:BorlnglO2'
z
a
I
I
t00
t0
ao
70
€0
50
40
!o
20
to
o
0
t0
20
t0
10
50
50
70
a0
90
100
az
E
fi
.ool 1,75
DIAMETER OF IN MI
CLAY TO SILT COBBLES
GRAVEL 51 % SAND 38 X SILT AND CLAY
LIQUID LIMIT - PLASTICITY INDEX
SAMPLE OF. Slightly Silty Very Sondy Grovel FROM: Boring 1 O 1'-2'
11 X
Th6.c t6sl rcrulls opply only lo lhc
romplor whlch wore leslsd. lhe
lesllhg ropod eholl nol bo r.produced,
cxcepl ln full, wllhoul lhc wrlllen
opprovol of Kuhqr & A!!oolol.!, lnc.
Slove onolylb losllng l3 pirform.d ln
ocqordqnca wlth ASTM D6913, ASIM D7928,
ASIM Cl36 ond/or ASTM D1t40.
HYDROMETER ANALYSIS SIEVE ANALYSIS
U.S. SANDARD SERIES CI.EAR SqIARE OPENINGS
r/rx 1/^. 1 1/D.i Mtx at24 HRS 7 HRSr( vt[ ri ul!
TME RETDINCS
doltN !eltx avl!
I
'll t1
rrr I r i '; ' 1""
SAND GRAVEL
FINE COARSEFINEMEDTUM ICOARSE
23-7 -568 Kumar & Associates GRADATION TEST RESULTS Fig. 3
lGn#**'ffin[i:nii:"d'.-'
,--_._""-__1-
TABLE 1
SUMMARY OF LABORATORY TEST RESULTS
No.23-7-568
ATT LIMITSSAMPLLOCATIONGRADATION
SAND
(%)
PERCENT
FASSING NO-
200 stEvE
LIQUID UMIT
lolJ trhl
PLASTIC
INDEX
(Dsfl
UNCONFINED
COMPRESSIVE
STRENGTiI SOIL TYPEBORING
lftl
DEPTH
NATURAL
MOISTURE
CONTENT
locll
NATURAL
DRY
DENSNY
GMVEL
("kl
51 41 8
Slightly Silty Very Sandy
GravelI22.2
Slightly Silty Very Sandy
Gravel51381t7to2