Loading...
HomeMy WebLinkAboutEngineer's Design PlanHuddleston-Berry Engineering & Tssting, LLCI August 26,2024 Projecf#02890-0001 Reeves & Sons Electric 1560 Main Street Silt, Colorado 81652 Attention: Mr. Andrew Reeves OWTS Design 111 W. Main Street Silt, Colorado Dear Mr. Reeves, At your request, Huddleston-Ben)' Engineering & Testing, LLC completed design of an Onsite Wastewater Treatment System (OWTS) for 111 W. Main Street in Silt, Colorado. HBET understands that a new commercial building is proposed at the site. The site location is shown on Figure I - Site Location Map. A site plan is included as Figure 2. Site Descrintion At the time of the investigation, an existing residence occupied the eastern portion of the site. The remainder of the site was open. The site sloped generally gently down to the east. Site topography is shown on Figure 2. Vegetation consisted primarily of grasses and weeds with a few trees. The site was bordered to the north by Main Street, to the south by railroad tracks, to the west by an existing commercial property, and to the east by a vacant lot. Subsurface Investisation In order to evaluate the subsurface conditions at the site, two pits were excavated in the vicinity of the Soil Treatment Area (STA). Using visualtactile classification methods, the soil profile consisted of tan, moist, medium stiff, structureless sandy loam (Soil Type 2A) to the bottoms of the excavations. Groundwater was not encountered in the subsurface at the time of the investigation. In general, based upon the results of the subsurface investigation, HBET believes that the seasonal high groundwater elevation is deeper than 9.0 feet below the existing grade at this site. 2789 Riverside Parkway Grand Junction, Colorado 81501 Phone: 970-255-8005 Info@hudd lestonbeny. com Subject: The locations of the test pits are shown on Figure 2. Copies of the test pit logs are included in Appendix A. lll W, Main St. #02890-0001 08/26124 Onsite Wastewater Treatment Svstem Huddleston-Berry hnrlr{crhg"t !r{inr, l-l-C Seepage Bed Deslgn The design of the absorption system generally follows the requirements of the Garfield County On-Site Wastewater Treatment System (OWf\ Regulations, effective June 2018. Based upon infonlation provided, HBET understands that the new commercial structure will serve six employees for one shift/day with no showers. Based upon the visualltactile soil classificationo a Long-Term Acceptance Rate (LTAR) of 0.5 will be utilized for the absorption field design. The daily flow of the sewage disposal system is calculated below and a plan and profile of the absorption system are shown on Figure 3. Averege Daily Flow: (6 persons)(2O GPD/person) - 120 GPD Soil Treatment Area = (120 CPD / 0.5) = 240 Squnre Feet Adjusted Soil Treatment Area : (240 SFXl.2X0.7):202 Square Feet # of Quick4 Chambers : (202 I 121:17 Chambersl Use 18 Chambers System Installation The installation of the septic tank, plumbing lines, Infiltrators, etc, should be completed in accordance with the Garfield County regulations and Infiltrator Systems, Inc. specifications. In addition, the following construction procedures are recommended:r The septic tank and distribution box should be placed level over native soils that have been scarified to a depth of 8 to 12 inches, moisture conditioned, and recompacted to a minimum of 95% of the standard Proctor maximum dry density, within *2Yo of optimum moisture content. However, up to 3-inches of washed rock or pipe bedding passing the f -inch sieve may be used as a leveling course under the septic tank and/or distribution box.. The bottoms of trenches and backfill around the septic tank and distribution box which will support sewer or effluent lines should be compacted to at least 90 percent of the standard Proctor maximum dry density, within t2o/o of optimum moisture content. Pipe bedding should have a maximum particle size of l-inch.. Vehicular or heavy equipment traffic and placement of structures should not encroach within 10 feet of the septio tank or distribution box. Inspection Schedule Huddleston-Berry Engineering & Testing LLC should be retained to monitor the construction of the OWTS, The following schedule of observation and/or testing should be followed: ' Observe the absorption bed excavation prior to placement of Infiltrator chambers.. Observe placement of the septic tank, distribution box, and all connecting sewer and effluent lines prior to backfill. Veriff proper fall between inverts.. Observe and veriff installation of the absorption bed prior to placement of cover and backfill. 2Z:'2008 ALL PROJECTS\02,990 - Reeves ohd Sons Electrici02S90-000 I I I I W Moin Street 20O - Geo 02890-000 I OWTS0826t4,doc l l l W. Main St. #02890-0001 08126124 ,@\ @ Huddleston-Beiry Ii$lil.crirs & l'r(lnt, l,l.c In conformance with Garfield County regulations, HBET will be required to provide Garfield County with documentation certifi/ing that the OWTS was placed in conformance to the plan and profile and Garfield County regulations. General Ngtes The OWTS design was based upon the results of the subsurface investigation and on our local experience. The design is valid only for the proposed construction. We are pleased to be of service to your project. Please contact us if you have any questions or comments regarding the contents of this report. Respectfully Submitted: Huddleston-Berry Engineerlng and Testingo LLC Michael A, Berry, P.E. Vice President of Engineering 3 010 IL g Z:,2008 AI-L PR0.IECTS.02890 - Reev€s nfld Sons Elect1ic,02890-0001 I I I W Moin Sheet 200 - C€o 0289G0001 OWTS082624.doc FIGURES t- Locatlon e€Hi CACI' Hffi trffiffi ffiffi OYERALL SITE PLAN SCALE: 1'r:301 C.I. = I FT A TESTPIT + I ProjectNo.: 02890-0001 Date: 08/26124 By: MAB @ lluddloston Bcrry Iiilghwrirg& IcsriuB, LLC 2789 Rivercido Parkway CnndJunction,CO 81501 1I I lV. MAIN STRTET PARCEL# 2r79091000t2 FIGURS2.SITEPLAN GENERALIZED SYSTEM PROFILE COilHERCIAL STNUCTURE RISERS (AS NECESSARY) INFiL CHATBERS IO FI HIN Egx rr4 8[LOW h*ISHS OMDE MAX" ER l0s A CDSPAR'MENI SEPTIC TANK FROfr C!PH[ APPRNVE! LIST INSIALL EFFLUENT IN NUTLET lTE CENERALIZED BED PROFILE NDT IO SCALE sollg 0n olH8R sulrAas CAIRY gUtrACg TYATER MINIMUM SETBACKS (UNITS -m) ..OISEN. SETBKKS N(N LISIND H&,8 SHOULD 9E N ACCOMANCE trTM GARFIELD COINTY OIVTS RECULATIONS WLcll,,lSD lftrril' Lr4 s 6 at DETAILED PLAN SCALE: l" - 20' DISTruAUTIOS lOX TIIAT lNl + SSPTICTANK VITH OALLON CNACITY STANDARD CTiMSN NHLIR1\TOR .IUSE i\rp {'S OR'two4r'sal D DECreB BNDS" Project No.r 02890-0001 DEte: 08n6/24 By: MAB lluddleston Beny Englrcrht & I'c!rhg, LLC 2789 lII W. MAIN STREET PARCEL# 2r7e0el000l2 FIGI'RE 3 - SEPTIC SYSTEM DETAILS APPENDIX A Typed Test Pit Logs -Io-Ft IIJo =3z F o. Fo UJF lro lllo o- oo (t) .g6 t ul =z (, ul oe,G cc =cL zo (,o ou otra- ()J,l ob 5 oF d8 ho .sE9c >.:-i bbgoo a.f; u doEAE ON* e65e I E?B:,J59. .y o\ i ti :l€ do,=r-Er;li e{ Ll o\ o oo lu o oa o6 ttIooft ()oo c)o, @No EutoE5z () Iu.toEg zUI J() t!N6 FE oulF :E -E zIF (Jxl.ll ILo clz!I oJlrl w e.utF 3 clz3oE(' zI oxut lto llt = F zo (txgl E,IT lL zo F ulJ IIJ clz oE(, {(\oc{ €o fo o UIF BIr =o(,(Do v()6to ,cvo PF oo I IUEzo F oxul EoluYolu 4() o o s6to C\| @ cl E.lFE o lrlF o to (, tr zoozotr C'x IIJ OF aaglFoz oo UJoooJ (u) HId3A q c 90'l SrHdvu9 zotro. & C)U' lJlo J & IUF U:lgYUnN :td^l_ 3-ldWVS {oou) % AH3nO3:rU Enlv N) sINnoc MO]8 0e)'N3dr.:txJod Oed) IAAINN AHO (o/o) ttt3rttoc Sunrslotl (,tl! (/)roF(= Lll =FJF ("/") l_NftNoc SSNH Itrll-1 €lnor-l Jnn crtsvld )CJONI /tltSrrs\nd C,I oo- F:o ct) so(D 0) :l of 6 Eo E =€o E .9.o € i(q c(ooJ Eco U) (l)o g O) (! go ao o Eo odt $t-riuF- E'ul^ IIJ YE. =:)zF o. Fo ]UF ool: U' .c(5 ; gl =z oo U) zo c,o o uJ oEA Folrl?oEA UrlFl ob '5 oF d 50 'i @o 30 E] o & (J o o t) () @troco(n.' 6o (DoE zul Jo oooo O)o$lo o o p, oa@ c.iloFo\ uuto =3z ouI oto. lrrN6 Eo. FoqI e 1C zotr "igEi -^<4fi elLtroturs= Clg31otr(9 tE Zroi Ea<F()<x>ul< ', CJ 3pfigt- L- zo ulJtllaz:ouo $oo €\l €o trl @otIIY(J ul (, cl IIJ ul o. =o(J oo-cgo(o @ cYo6 F oo I ur =zo oxul e(') 't$lo GI ct o UTFc. al, ut o troFo t zoozo (,xut oF oouIoc'oI olII oz (u) Htd3Ct qo 901 StHdvus zo F o-t() a,lllo J t UJF U3gWNN :dAI_:t-ldnvs (oou) % AulnoJfu 6nrvnH) stNnoc MO"tS 0sr)'NSdJ.3)tCOd (pd) IMIINN AHO (xlrnErttoc SUflrslo$l (ttut c0drFE=lll =FJF $"\ IN]INO3 S:INII I!1il'I crnon Jnlt SlISVld XSONI AIICIIS\rId (\ oo- F oo) ott(D o fo at, E an E Eo E lgo Ef6 c(soJ Ec t0a o(D g co {5 =o o(D o Eo oto H8 HC:U_O39