HomeMy WebLinkAboutManual J Reportf2anuaf C Kepar* Heating System SummaryRicky Harrell Dahl Plumbing Supply 3366 S Glen Ave Glenwood Springs, CO 81601 Phone: 970-945-2331 Email: ricky. harrell@hajoca. com Project lnformation Project #: Name: Dufff Residence Location: 1360 CR 331 Silt, CO 81652 Notes August 23, 2024 RECEIVHD AUG 2 7 ?O?E DAH Project Summary Design Location: Load Calculation Method Outdoor Temperature: Floorplans i Levels: Ground Floor Total Area: Total Zones: Zone Heating Summary COM..IU P{iTY DEVEL' }PIdENT (User Specified) Rifle, Garfield Co. Regional AP, Colorado Manual J8 -2.O "F Component Losses: lnfi ltrationA/entilation: Total Heating Load: Forced Air: Central Ventilation Load: Total Heating Load: 931 931 1 ft' ft' 15,229 Blulhr 4,802 Btu/hr 20,031 Btu/hr 19,353 Btu/hr 678 Btu/hr 20,031 Btu/hr Total 101 Zone# 931 931 Area Slab On Grade Slab On Grade Construction FA FA Heating Types 0 0 RH Load- '19,353 19.353 FA Load 19,353 19,353 Supplemental 19,353 Zone Load* *RH Loads include intemal panel back loss that may not be included in the project total. Room Heating Summary (By Floorplan) Ground Floor Length=ft Area=ft' HeadLoss=fiwater Rv = hr.ft"F/btu N = Not Heated Temperalure = "F Flowrale = USGPM Air Flow = cfrn Heat Loss = Btu/hr Unit Heat Loss = Btu/(hrft'z) RH = Radiant Floor Heating BB = Baseboard FA = Forced Air OTH = Other Heating SM = Snowmeli See end of report for important Notes and Disclaimers. Created Using HeatCAD 2024 (812612024) Version:24.0.0280 R Pagel oI2 101 101 101 101 Zone# Bath Kitchen Ofiice Bed Room Name FA FA FA FA Heating Type 94 479 148 209 Area 87 448 138 186 Heated Area 12 12 12 12 Tube Spacing 0.5 0.5 0.5 0.5 Floor Cover RV 0.0 0.0 0.0 0.0 Unit RH Load 0 0 0 0 RH Load 0 0 0 0 BB Load 1,343 10,149 3,028 4,833 FA Load 0 0 0 0 Other Load 1,343 10,149 3,028 4,833 Total Load Evild,i n3 Fit ?0t&g-07-4Ll-9779 {r S., "g ,..t..* l"r t t-l --jr ,* -,, Itl';-*e * ,;o't "Heating t..i f a System Summary August 23, 2024 Creaied Using HeatCAD 2024 (812612024) Version:24.0.0280 R Page 2 oI 2 '*,: :. .,-i" :, ,. I .4 s,; Disclaimers ACCA, Manual J and Powered by ACCA Manual J are registered trademarks of the Air Conditioning Contractors cf America. All rights reserved. carefully, and to have the calculated results reviewed by an experienced heating professional to ensure reasonableness and suitability lor your application. NO GREATER _HAN THE AMOUNT OF FEES PAID TO AVENIR UNDER THE SOFTWARE LICENSE AGREEMENT. Name:Duffl Residence Project #: "*f, Length=ft ArEa=ff2 Temperature='F Flowrale=USGPM AirFlow=cfm HeatLoss=Btu/hr UnitFleatLoss=Btu/(hr'fi') Head Loss = ff water RH = Radiant Floor Heating BB = Baseboard FA = Forced Air OTH = Oiher Heating SM =' Snowmelt See end of report for important Notes and Disclaimers. Rv = hr.ft''"F/btu N = Not Heated Project lnformation Prcject #: Name: DufoResidence Location: 1360 CR 331 Silt, CO 81652 Ricky Harell Dahl Plumbing Supply 3366 S Glen Ave Glenwood Springs, CO 81601 Phone: 97G945-2331 Email :ricky.harell@hajoca.mm Notes: Form Jl Manual Jg Load Calculation August 23, 2024 created Using HeatcAD 2024 (aDEDoz4) Sofrware Version:24.0.0280 R Page 1 of 2 All load values shown in Btu/hr 15 13 1a 9 8 7 TYpe ot Erposure Form Jl (Summer) Iotal Loed AFO Ercursion Blower Heat PiDinE Loa.l Ventilaton Loads Duct Loadg subtotals other lntemal lnfiltntion Flooc Ceilings Below Gnde WatlE Above Gnde walls and Partltions wood and Metal Dooc Skyliqhte WindoG and Glass DooE C€llino Slom lDeo.l and Grcss Cellino Area {SoFtl R6m Dimension3 aRl and Floor plan Area (SqFtl Ceiling Heiqht {Ftl and Gross Wall Area (SqR} Runnhs Feet ot Exposed wall Name ot Roon Dutrv Rsrdence Sum lins 13 tnrouoh lg ELG EHLF & ESGF Sum Ines 5 lhrouqh 13 User soecified addilional loads d c b a Latent Load (Bluhl a a a b a a a c b a Vent Cfifi Plen19 Occupants et 230 end 200 Btuh 228'1Ao Cuslm 12B{sw(Partilion) 128-Osw 't lJ MFSA COUNTY WNDOW MESA COUNTY WlNDOW MESA COUNTY WNDOW Condruction Number N Panel Faceg GaUDay E Cfm Eftscl ACH 25 56 147 6.98 6.98 43.20 21 60 21 60 21.60 Htg" HTM 21 o 217 0 405 102 21.60 17 64 31 2A 12.27 clg. Del 2 wAR 1,0 931 282 840 40.37 24.O4 15 07 15.07 AH of Length 100 91 Entire House 20 031 678 19.353 4.'124 3.1 10 1 367 1.973 5.855 1 .74A 518 326 326 Heating Biuh 93't 931 l taa 10.E65 57 1.706 282 8.909 1.200 460 921 9S 649 2"778 472 423 471 185 s419. 400 400 400 L€19. See sections at end of report for important Notes, Assumptions and Disclaimers. Prcject #: Name: Duffo Residene Form J1 Augusl23,2024 Warnings This appli€tion has glass areas thal produced relalively large cooling loads for parl ofthe day. Zoning may be required lo overcome spikes in solar load for one or more rooms. A zoned system may be required or some rooms may require zone control iprovided by hdividual, motorized, themostatically controlled damper9. Disclaimerc by ACCA. The prograh and data are provided "as is'Mhout waranly of any kihd either exprFsed cr implied. The entire dsk as the quality and perfomance ofthe program ahd data iswilh you. ln no eventwill ACCA be liable to you for any damag6, ihcluding without limitation any lost profts, lost sevings, or other incidental or cohsequehtial dahages adsing out otthe use or inability to use this program or the date. @ 201 5 Air Conditioning Confactors ofAmedca. All Rights R6eryed. wM.acca.org AccA, lllahual J and Powered by AccA Manual J are registered tEdeharks ofthe Air conditjoning contEdore ofAmerica. All dghts reseryed. cold weather humidifcation, or some litestyles that produce excessive moisture damage. The responsibility to do so The €lculated values showh ih this report are based on the dah inpd by the user ofthe sofrware. lnaccu€te or erroneous data input will resuft in inaccurate or erroneous results. You are strohgly advised to review all input data @refully, and to have the €ldlated r€sults reviewed by an experienced heating professiohal to ensure reasonableness and suitaUlity for your applicatioh. IN NO EVENT WLL AVENIR SOFTWARE INC. ('AVENIR) OR ITS AFFILIATES BE -IABLE UNDER ANY CONTRACT. NEGLIGENCE, STRICT LIABILITY OR OTHER LEGAL OR EOUITABLE THEORY FOR ANY CONSEQUENTIAL. INCIDENTAL, INOIRECT OR SPECIAL OR PUNITIVE DAMAGES WHATSOEVER (NCLUDING, 8UT NOT LIMITED TO, DAMAGES FOR LOSS OF BUSINESS PROFITS, BUSINESS INTERRUPTION, LOSS OF BUSINESS INFORMATION OR DATAAND THE LIKE), EVEN IF SUCH PARTY HAS BEEN ADVISED OF THE POSSIBIUry OF SUCH OAMAGES. AVENIR'S CUMULATIVE LIABILITY FROIII AI.IY CAUSE RELATED TO OR ARISING FROM THE USE THIS REPORT, AND REGARDLESS OF THE FORM OF THE ACTION, SHALL BE LIMITE) TO NO GREATER THAN THE AMOUNT OF FEES PAID TO AVENIR UNDER THE SOFTWARE LICENSE AGREEMENT. Allload values shNn in Btu/hr Created Using HeatCAD 2024 (8126f2024) Soffware Vecion:2/1,0.0280 R Page 2 ol 2See sections at end of report for important Notes, Assumptions and Disclaimers. Ricky Harell Dahl Plumbing Supply 3366 S Glen Ave Glenwood Springs, CO 81601 Phone: 97G945-233 1 Email:ricky.harell@hajo€.mm Notes: lndoor Conditions Load Summary Manual J8 Load Calculation August 23, 2024 Project lnformation Project #: Name: Dufry Residence Location: 1360 CR 331 Silt, CO 81652 Outdoor Conditions Location: (user Specjfied) Rife. carfield Co. Regional AP,Colo.ado Elevation: 5548' Latituder 40 Heating Cooling Dry Bulbi -2.0 "F 105.0 "F Daily Range: High Wet Bulb: 59.0 "F Floorplan/Levels Ground Floor Room Temp: Design Temp Diff: Humidity: lVoisture Diff (Grains): Ventilation Num Occupants: Heating 70'F 72.O'F Cooling 75'F 30.0 "F -52.S 2 Heating Heat Recovery 0.1 3 21 ctm 50 o/o Type: ACH: Outside Air: Sensible Eff: Cooling Heat Recovery 0.13 21 cfm 50 o/o e31 fr" Total Heated Area: Tolal Cooled Aree: 931 931 lnfiltration Method: Storiesi Construclion: Exposure Category: Num Fireplaces: Net Air changes (H/c) Net Flow (H/C): Simple 1 Semi-Tight Three or Four Exposures None 0.40ti.22 63 cfm/34 cfm Type: ACH: outside Air: Sensible Efi: Total Heating: 20,031 Btu/hr Total Sensible: 10,965 Btu/hr Total Latent: 400 Btu/hr Load BreakdoM Iotal Area Iotal qED* Blwer Heat Radiant Back Loss Pipinq Load Humidifrcalion Ventilation Duct Loads Other lnternal lnfiltration Floors Ceilinqs Below crade Walls Walls Doors Skvliqhts* UVindows* Name 931 fi' 20,031 0 0 0 678 0 0 4,124 3,I 't 0 1,367 0 7,e37 1,744 0 1,170 Heatinq 931 fi' 10.965 61 1,706 282 0 1,660 921 0 950 3,427 472 0 1,080 Sensible 400 0 0 400 0 Latent 'Average Load Procedure Heating AT': 70.0 Cooling AT!: 18.0 Est. Heating CFM':314 Esl. Cooling CFM'z: 668 JSHR:0.96 MJ8 Tons: 0.95 SqFt/Ton:983 CFli/SqFt:0.72 Herting Losd &eakdolvn Sensble Load Braakalq'lrr FsEslrdion Loadtrs Hur of Dq, - Blodr Lsad (s$nmsrl 3U(rr-l ?D00 1 0t"10 E5 ib S e l0 ll 1: 13 1il 15 16 li 18 1S t0 Hsut af Oav Legend - Lmd Line - A\,€rage - 38Fercffd Created Using HeatCAD 2024 (812612024) Software VeEion:24.0.0280 R Average Load: 1,473 Eltu/hr Excursion Limit 1,915 Btu/hr Peak Load: 1.982 Btu/hr AED Load: 67 Eltu/hr (1)AT:Difierencebetueensupplyalandretuhaf (2)EsthatedatrflowbasedonspedfedsupdyakAT Length=fi Area=fl.r Temperature="F Flowrate=USGPN, AirFlow=cfm HeatLoss=Btu/hr Unit Heat Loss = Btu/(hrff) Rv = hrff 'Flbtu Head Loss = frwater RH = Radiant Floor Heating BB=Baseboad FA=ForcedAir OTH=oiherHeatins sl\il=Showmelt N= NotHeated See sections at end of report for important Notes, Assumptions and Disclaimers.Page 1 of 2 Project #: Name: Du11V Residence Load Summary August 23, 2024 Created Using HeatCAD 2024 (8n6ng24) Sotuare Vecion:24.0.0280 R Warnings This appli€tion has ghss areas lhat produced relatively large cooling loads for part ofthe day. Zoning may be required to overcome spikes in solar load for one or more rooms. A zoned syslem may be required or some rooms may require zone contrcl (orcvided by individud, motodzed, themos{aticall} @ntrclled damper9. Disclaimers Wth lhe pemission of:he Air Conditioning Contractor of Aherica CACCA'), matedal s reproduced from lManual J Residential Load Calculation (8th Edition) which is copyrighted by ACCA. The program and data arc provided "as is" wlthout wananty of any kind eiiher expressed or implied. The entire dsk as the quality and perfomance ofthe program and data is with you. ln no eventwill ACCA be liable to you lor ahy dahag6, including witFout limitatioh any lost profits, lost savings, or other incidental or consequential damages adsing out of the use or inability to use this program or the data. @ 2015 Air Conditioni[g Contraclors of America. All Rights Reseiled. M.a6a.org ACCA, Mahual J and Powered by ACCA Manual J are registered tEdema*s olthe Air Condilioning ContradoE of America. All rights reserued. Cold weather humidifcation, or some lifestyles that produce excessive moisture, hay cause condensalion to occur ifthe absolute humidity ofthe indoor air is too high for the momehtary circuhstahc6. Condensation €n occur on surfac6 or concealed within tle strucfure, and en lead to mold, mildew, frost damage, ahd hoisturc dahage. The soflirarc does not perfom @lculations torthe estimation or deteclion ofpossible condensatior problems, Erd it is the designeE (.e. sofrware use6) responsibility to do so independently if required. For guidan@ and additional cautions rcler to AccA Mahual I 8th Ecition, including sedion 1 -1 1 ahd sectioh 27. The calculated values shown in this repon are based on the dab ihput by the user ofthe soltEre. lnaccurate or erroneous data input will result in ihaccurate or erroneous resulls. You are strongly advised to review all input data €refully, and to have the calculated rcsults r€viiled by an expedenced heating profFsional to ensurc reasohableness ahd suitability for your appliration. IN NO EVENT WLL AVENIR SOFTWARE INC. CAVENIR) OR ITS AFFILIATES BE LIABLE JNDER AN'Y 'ONTRACT. NEGLIGENCE, STRICT LIABILITY OR OTHER LEGAL OR EOUITABLE THEORY FOR ANY CONSEOUENTIAL, INCIDENTAL, INDIRECT OR SPECIAL OR PUNI-TIVE DAMAGES WHATSOEVER (INCLUDING, BUT NOT LIMITEO TO, DAMAGES FOR LOSS OF BUSINESS PROFITS, BUSINESS INTERRUPTION, LOSS OF BUSINESS INFORMATION OR DATA ATID THE LIKE), EVEN IF SUCH PARTY HAS BEEN ADVISED OF THE POSSIaILITY OF SUCH DAMAGES. AVENIR'S CUI\,IULATIVE LIABILITY FROM AI.IY CAUSE RELATED TO OR AR,SING FROM THE USE THIS REPORT, AND REGARDLESS OF THE FORM OF THE ACTION, SHALL BE LIMITED TO NO GREATEFI THAN THE AMOUNT OF FEES PAID TO AVENIR UNDER THE SOFTWARE LICENSE AGREEI\,IENT. (1) AT: Ditrerence beMen supdy air anc ielurh air (2) Esthated airflowrased oh specifred supdy ahST Length=frArea=ff TempeEture='F Flowrate=UscPl\,i AiiFlow=cfm HeatLoss=Btu/hr Unit Heat L6s = Btu/(hr.ff1 Rv = hr'ff 'Flbtu Head Loss = Rwaler RH = Radiant Floor Heating BB=Baseboad FA=ForcedAir oTH=otherHeating SM=Snowmelt N=NdHeated See sections at end of report for important Notes, Assumptions and Disclaimers.Page 2 of 2 Ricky Harrell Dahl Plumbing Supply 3366 S Glen Ave Glenwood Springs, CO 81601 Phone: 970-945-2331 Email:ricky. harrell@hajoca.com Simple 1 Semi-Tight Three or Four Exposures None 0.40 to.22 63 cfm / 34 cfm 931 ft" Load Report Project lnformation Project #: Name: Duffy Residence Location: 1360 CR 331 Silt, CO 81652 ManualJ Load Summary Total Heating: 20,031 Btu/hr Outdoor Gonditions Location: Elevation Latitude: Dry Bulb: Daily Range Wet Bulb: lnfiltration Method: Stories: Construction: Exposure Category: Num Fireplaces: Net Air Changes (HeaVCool): Net Flow (Heat/Cool): Floorplan/Levels Ground Floor Total Sensible: 10,965 Btu/hr (User Specified) Rifle, Garfield Co. Regional AP,Colorado 5548' 40 Cooling 105.0 "F High 59.0'F Notes: Total Latent: 400 Btu/hr lndoor Gonditions Room Temp: Design Temp Diff: Humidity: Moisture Diff (Grains): Ventilation Num Occupants: Type: ACH: Outside Air: Sensible Eff: Heating -2.0 "F Heating 70 "F 72.0'F 35 2 Heating Heat Recovery 0.13 21 cfm 50% Cooling 75 "F 30.0'F 45 -52.9 Manual J8 Load Galculation August 23, 2024 Cooling Heat Recovery 0.13 21 cfm 50% Created Using HeaiCAD 2024 (412612024) Version:24.0.0280 R Type: ACH: Outside Air: Sensible Eff: Total Heated Area: Total Cooled Area: ( l ) AT: Difference between supply air and retum air (2) Estimated air flow based on specified supply air AT Length = ft Area = n, Temperature ='F Flowrate = USGPM Air Flow = cfm Heat Loss = Btu/hr Unit Heat Loss = Btu/(hr'fi') HeadLoss=ftwater RH=RadiantFloorHeating BB=Baseboard FA=ForcedAir OTH=OtherHeating SM=Snowmelt See end of report for important Notes and Disclaimers. ft' ft2 931 93'1 Rv = hr.fi'''F/btu N = Not Heated Page 1 of 7 Name:Dufff Residence Project #: Constructions Walls Doors Load Report August 23, 2024 128-0sw 128-0sw Code Frame Wall or Partition; Wood Framing; R-11 lnsulation in 2 x 4 Stud Cavity; Stucco or Wood Siding, Plus lnterior Finish Frame Wall or Partition; Wood Framing; R-1 1 lnsulation in 2 x 4 Stud Cavity; Stucco or Wood Sidinq; Plus lnterior Finish Description '10.3 10.3 R-Value 282 840 Area 1.973 5,865 Heating 649 2,778 Cool:ng 11J Code Metal Door with Fiberglass Core Description 1.7 R-Value 40 Area 1.744 Heating 872 Cooling Floors 228-10p Code 228 - Yertical Board lnsulation Covers Slab Edge and Extends Straight Down to Three Feet Below Grade, any Floor Cover Description 10.0 R-Value 121'- 8" (F) Area 3,110 Heating 0 Gooling Geilings Custom Gode lnsulated Ceiling Under Attic or Attic Knee Wall (Vented wi Radiant Banier); R-54 Insulation; Roof Material: Metal; Roof Color: Dark; Description 49.0 R-Value 931 Area 1,367 Heating 950 Cooling Glazing Windows (1) AT: Difference between supply air and return air (2) Estimated airflow based on specifled supply air AT Leng'th=ftArea=fl' Temperature="F Flowrate=USGPM AirFlow=cfm HeatLoss=Btu/hr UnitHeatLoss=Btu/(hrft') HeadLoss=ftwater RH=RadiantFloorHeating BB=Baseboard FA=ForcedAir OTH=OtherHeating SM=Snowmelt See end of report for important Notes and Disclaimers. CEated Using HeatCAD 2024 @12612024) Version:24.0.0280 R MESACOUNryWNDOW MESA COUNTY WNDOW MESA COUNTY WNDOW Code BlindsMedium45 (50%) , BlindsMedium 45 (5oo/o\ , BlindsMedium4s (5lo/o) Description S N Exposure 3.33 3.33 3.33 R-Value 0.3 0.3 0.3 SHGC 24 15 15 Area 518 326 326 Heating 423 47' 185 Cooling Rv = hr t' "F/btu N = Not tleated Page 2 of 7 Name:Duffo Residence Project #: lnternal Loads Description Default (1,200 Btuh) 2 Occupants: Total Latent Other Loads Blower Load 1,706 Btu/hrSensible '1,200 460 1,660 0 400 400 Load Report August 23, 2024 (1 ) AT: Difference between supply air and retum air (2) Estimated airflow based on specified supply air AT Length=ft Area=fiz Temperature='F Flowrate=USGPM AirFlow=cfm HeatLoss=Btu/hr UnitHeatLoss=Btui(hrfr') HeadLoss=fiwaier RH=RadiantFloorHeating BB=Baseboard FA=ForcedAir OTH=OtherHeating SM=Snowmelt See end of report for important Notes and Disclaimens. Rv = hr'ft'''F/btu N = Not Heated Created Using HeatCAD 2024 (812612024) Version:24.0.0280 R Page 3 of 7 Name:Dufff Residence Projec{ #: Load Breakdown Load Report August 23, 2024 ileilings Heating Load Breakdown \4tslls Flcrors Sec$ble Load Breakdown \'\'slls -l,,rgnlilatisn lnliltrstio-l -SoDrs *Averaqe Load Procedure Heatinq AT': 70.0 Coolinq ATr: 18.0 Est. Heatinq CFM': 314 Est. Coolinq CFM': 668 JSHR: 0.96 MJ8 Tons: 0.95 SqFVTon: 983 CFM/SqFt: 0.72 Ceilings lntiltrstiBn \,"entilatha ( l ) AT: Difference befween supply air and retum air (2) Estimated air flow based on specified supply air AT Length=fi Area=ft'z Temperature='F Flowrate=USGPM AirFbw=cfrn HeatLoss=Btu/hr UnitHeatLoss=Btu(hr'fl') HeadLoss=fiwater RH=RadiantFloorHeating BB=Baseboard FA=ForcedAir OTH=OlherHeating SM=Snowmelt See end of report for important Notes and Disclaimers. .{EDT Horver He$ Created Using HeatCAD 2024 (812612024\ Version:2,1.0.0280 R Total Area Total AED- Blower Heat Radiant Back Loss Piping Load Humidification Ventilation Duct Loads Other lntemal lnfiltration Floors Ceilings Below Grade Walls Walls Doors Skylights* Windows* Name 931 ft' 20,031 0 0 0 678 0 0 4,124 3,110 1.367 0 7,837 1,744 0 1.170 Heating 931 ft2 10,965 67 1,706 2A2 0 1,660 92'l 0 950 3,427 872 0 1,080 Sensible 400 0 0 400 0 Latent Rv = h*fia"F/btu N = No: Heted Page 4 ol 7 Name:Dufff Residence Project #: AED 30[0 l0L'|0 Load Report August 23, 2024 Lf, tb Fsestration Lodvs lfir of Day - Block Lod (Sunmterl 1t i3 1.t Huur r-rf Ds5r 15 'lE Legerd - Load Line - Average Percent 1 080 s Average Load: 1,473 Btu/hr Excursion Limit: 1,915 Btu/hr ll Peak Load: 1,982 Btuihr AED Load: 67 Btu/hr 1r 1S Rv = hr'ft"F/btu N = Not Heated 1g t0 0 6 lLl (1) AT: Difference between supply air and return air (2) Estimated air flow based on specified supply air AT Lengith=ft Area=ft, Temperalure='F Flowrate=USGPM AirFlow=cfrn HeatLoss=Blu/hr UnitHeatLoss=Btu/(hr'fi') HeadLoss=fiwater RH=RadiantFloorHeating BB=Baseboard FA=ForcedAir OTH=OtherHeating SM=Snowmeft See end of report for important Notes and Disclaimers. Created Using HeatCAD 2024 (812612024) Version:24.0.0280 R Page 5 of 7 Name:Duffy Residence Project #: Heating Zones Load Report August 23, 2024 Zone 101 Zone 931 Area 70 Room Tempr 19,353 Total Load Heating Rooms Office Kitchen Bed Bath Room 't48 475 209 94 Area 70 70 70 70 Room Tempr 3,028 10,149 4,833 1,343 Total Load* * The sum of room loads may not be equal to the projecl total due to additional system loads. Cooling Zones C1 Zone 931 Area 75 Room Temp NO AED '1r,225 Sensible Load Office Kitchen Bed Bath Room 148 479 209 94 Area 75 75 75 75 Room Temp YES NO NO YES AED 1 175 5.419 2.997 634 Sensible Load" (Peak Load Procedure) Cooling Rooms " (Peak Load Procedure) The sum of room loads may not equal the project total due to variations in solar gain and syslem loads. (1 ) AT: Difference between supply air and retum air (2) Estimated air flow based on specified supply air AT Length=ft Area=ft' Temperature="F Flowrate=USGPM AirFlow=cfm HeatLoss=Btu/hr UnitFleatLoss=Btu/(hr'fi') Head Loss = ft water RH = Radiant Floor Heating BB = Baseboard FA = Forced Air OTH = Other Heating SM =. Snomelt See end of report for important Notes and Disclaimers. C:eated Using HeatCAD 2024 Fl26l2O24) Version:24.0.0280 RRv = hr'ft'''F/btu N = Not Heated Page 6 of 7 Name:Duffy Residence Project #: ProvinceiState: Country: Outdoor Heating Design Temp: Outdoor Cooling Design Temp: MJSCustom Load Report August 23, 2024 Warnings require zone control (provided by individual, motorized, thermostatically controlled dampers). Design Locaton Location:Rifle, Garfield Co. Regional Altitude: Latitude: Wet Bulb Temperature: Daily Range: 5548' fi 40AP Colorado United States -2.O "F 105.0 "F 59.0 "F High Disclaimers ACCA, Manual J and Powered by ACCA Manual J are registered trademarks of the Air Conditioning Contractors of America. All rights reserved. carefully, and to have the calculated results reviewed by an experienced heating professional to ensure reasonableness and suitability for your application. IN NO EVENT WLL AVENIR SOFTWARE INC. CAVENIR) OR ITS AFFILIATES BE LIABLE UNDER ANY CONTRACT, NEGLIGENCE, STRICT LIABILITY OR OTHER LEGAL OR EQUITABLE THEORY FOR ANY oF BUSINESS TNFORMATTON OR DATA AND THE L|KE), EVEN tF SUCH pARTy HAS BEEN ADVTSED OF THE POSS|BIL|TY OF SUCH DAMAGES. AVENIR'S CUMULATIVE LlABlLlry FROM ANY CAUSE RELATED TO OR ARISING FROM THE USE THIS REPORT, AND REGARDLESS OF THE FORM OF THE ACTION, SHALL BE LIMITED TO NO GREATER THAN THE AMOUNT OF FEES PAID TO AVENIR UNDER THE SOFTWARE LICENSE AGREEMENT. Rv = hr'fi'z''F/btu N = Not Heated Created Using HeatCAD 2024 (812612024') Version:24.0.0280 R (1 ) AT: Difference between supply air and retum air (2) Estimated air flow based on specified supply air AT Length=ftArea=ft, Temperature='F Flowrate=USGPM AirFlow=cfm HeatLoss=Btu/hr UnitHeatLoss=Btu/(hr'fi2) HeadLoss=ftwater RH=RadiantFloorHeating BB=Baseboard FA=ForcedAir OTH=OtherHeating SM=Snowmelt See end of report for important Notes and Disclaimers.Page 7 of 7 Ricky Hanell Dahl Plumbing Supply 3366 S Glen Ave GlerMood Springs, CO 8160'1 Phone: 97G94$233'1 Email:ricky.hanell@hajoca.com Notes; Indoor Conditions Heating Room Temp: 7O"F Design Temp 72.O "F Diff: Humidity: 35 l\roisture Diff (Grains): AED Report Manual J8 Load Galculation August 23, 2024 Project Information Project #: Name: DuffoResidene Lo€tion: 1360 CR 331 Silt, CO 81652 Outdoor Conditions Lo€tion:(User Specified) Rifle, Garfield Co. Regional AP.Colorado Floorplan/Levels Ground FloorCooling 75'F 30.0 "F 931 ft' 931 fr Total Heated Area: Total Cooled Area: Elevation: Latitude: Dry Bulb: Daily Range: Wet Bulb: 3000 20w €5 fi 10110 Heating -2,O'F 5548, 40 Cooling 105.0'F High 59.0'F 8S101112 -52 I Fmdrdion Loadys ]hr of Dry{Smlllgl 13 j,t 15 Hour of Dsv 16 11 1& tS ?0 LeqBrxl - Led Llne - Average - 30Perceni Created Using HeatCAD 2024 (8l26nOU\ Son\dare VeEiohr24.0.0280 R Page I of3 0 Ave€ge Load: 1 ,473 Btu/hr ExdEion Limit 1,915 Btu/hr Peak Load: 1,982 Btu/hr AED Load:67 Btu/hr See sections at end of report for important Notes, Assumptions and Disclaimers. Prciect #: Name: Dury Residence Cooling Rooms 2000 H(SrfiErl AED Report August 23, 2024 created Using HeatCAO 2024 (A26PO21) Softdare VeFion:24.0,0280 R Page2ol3 fi rooo !ruo 0 fi rooo 0 Kftchr($lmnarl 10 lt 12 13 14 15 16 lt 18 1S 20 Hour ot Dny I s10111 13 t4 15 1l 18 19 l0 Hour ol Day Average Load: 756 Btu/hr Peak Load; 1,255 Btu/hr AED L@d: 272 Btu/hr AveEge Load: 717 Btu/hr Excursion Limit: 932 Eltu/hr PeakLoad: |,141 Btu/hr AEO Load: 209 Btu/hrExcursion Limit 983 Eitu/ht Alll@dvdlG shiln in Btu/hr See sections at end of report for important Notes, Assumptions and Disclaime6. Project #: Name: Dufry Residence AED Report August 23, 2024 Warnings This appli€tion has glass areas that produced relatively large cooling loads for parl ofthe day. Zonin!' may be requared to overcome spikes in solar load for one or more rooms. A zoned syslm may be required or some rooms may require zone control iprovided by individual, motorized, themostatically controlled damper9. Disclaimers by ACCA. The progran and data are provided "as is" Mhout watrahty of any kind either expressed or implied. The entire dsk as the quality and performahce ofthe program and data iswith you. In no eventwill ACCA be liable to you for any dahages, including without limtation any lod profits, lost savings, or otherihcidental or consequential damages arising out of the use or inability to use this program or the data. @ 2015 Air Conditioning ContrectoE of America. All Rights Reseiled. M.acca.org ACCA, l\,lanual J ahd Powered by ACCA Manual J are registered trademarks ofthe Ai. Condilioning Contr?cloE of Aherica. All rights reseryed. Cold weather humidifcation, or some lifestyles that produce excessive moisture, may rause cahdehsation to occur ifthe absolute humidity of the indoor air is too high for the momentary circumstarc6, Condenstion can occur on surfaces or concealed within the structute, and can lead to hold, hibew, fr6t damage, and moisture damage. The soflware does not perfDrm calculations forthe estimation or deteciion of possible condensation problems, and it is the designeE (.e. sofrware useE) responsibility to do so i ndepehdently if required. For guide nce and additional ca ulions refer to ACCA Nrahual J 8th Edition, inclucling Seclj on I - 1 1 ahd Sedion 27. You are strcngly advised to review all input data €refully, and to have the Blculated rcsults Gviewed by ah expedenced heating profe$ionallo ensure reasonableness and suitability for your application. IN NO EVENT WLL AVENIR SOFTWARE INC. ('AVENIR) OR ITS AFFILIATES 8E LIABLE UNDER ANY CONTRACT, NEGUGENCE. STRICT LIABILITY OR OTHER LEGAL OR EOUITABLE THEORY FOR ANY CONSEQUENTIAL, INCIDENTAL, INDIRECT OR SPECIAL OR PUNITIVE DAMAGES WHATSOEVER (NCLUDING, BUT NOT LIMITED TO, DAMAGES FOR LOSS OF BTJSINESS PROFITS, BUSINESS INTERRUPTION, LOSS OF BUSINESS INFORMATION OR DATA AND THE LIKE), EVEN IF SUCH PARTY HAS BEEN ADMSED OF THE POSSIAIUTY OF SUCH DAMAGES. AVENIR'S CUMULATIVE LIABILITY FROM ATIY CAUSE RELATED TO OR ARISING FROIV THE USE THIS REPORT, AND REGARDLESS OF THE FORM OF THE ACTION, SHALL BE LIIIIITED TO NO GREATEIi THAN THE AMOUNT OF FEES PAID TO AVENIR UNDER THE SOFMARE LICENSE AGREEMENT. All load values shiln in Btu/hr Created Using HeatCAD 2024 (8DGn024) Sofrware Version:2i1.0.0280 R Page 3 of 3See sections at end of report for important Notes, Assumptions and Disclaimers. Proiect lnformation Project #: Name: Loffition: Ricky Harell Dahl Plumbing Supply 3366 S Glen Ave Glenwood Springs, CO 81601 Phone: 970-945-2331 Email :ricky.harrell@hajoca.com Notes: Manual J Worksheets Manual J8 Load Galculation August 23, 2024 Created Using HeatCAD 2024 1812612024) Sofrware VeBionr24.0.0280 R Page 1 of 14 Duffy Residence 1360 CR 331 Silt, CO 81652 All load values shown in Btu/hr I 7 6a llllPe ot ExPosure Fofm Jt (Summe0 Tot ll Load AED ExcuBion 8low.. l.a.t Piplnq Load Winter Humidifi €tian L@d Ventilailon Lmds Duct Loadg Sqbtotirls Other lntemal lnfiltration Floors Ceilinqs Eelo& Grade Welli Above Gndc Walls and Paadtions wood and Melal Dooc Skylights Wndows and Glass Doorg Ceilinq SloDe (Deq.l and Grcss Ceilinq Area (SqFtl Ceilino Heioht lFtl and GEss Wall Area lsoFtl Runninq Feet ot Erposed wall Name ot noom Duny Rsidence Sum lrnes 13 lhrouoh 19 ELG EHLF A ESGF Sum lines 6 thr0uqh 13 U*r specrlied addilional ioads e d c b a Latenl Load (Btuhl Sensible Load (Btuhl Heatino Load {Bluhl a a b a a 2 c b a Vent Ctn Plents Custom Aooliances Default Adlustreni9 scenario Number Oeupants at 230 and 200 Btuh 228-100 Custom 128-0sw(Panilion) 1 2B-Osw '11J MESA COUNTY l,tlNDOW MESA COUNTY WNDOW MESA COUNTY WNDOW Conslruclion Number 21 S N Panel Faceg Galnay E Ctn Eflecl ACH 25 56 1.47 6.98 6.98 4320 21 60 21 60 2J 50 Htc, HTM 2'l a 217 0 d05 142 230 21 60 17 64 31 28 12 27 Clc. Det 2 wAR 1.0 1ap\ 931 840 40.37 24 00 15 07 15 07 Area or Leng1h 100 9'! Eniire llous€ 20.031 678 19.353 4.12A 3 '110 1.367 1"973 5.865 1 744 518 326 325 Heatinq gtuh 931 931 1 217 10.965 67 1.706 282 8.909 1.200 460 921 950 649 2.778 472 471 185 S4lq. 400 400 400 L4lc. See sections at end of report for important Notes, Assumptions and Disclaimers. Projecl #: Name: Dufo Residence Manual J Worksheets August 23, 2024 Desion T€m!€ralure Dafterrnces llblc I Conditions lndoor Cmdidons- Heatind: Locetlon: (User Specified) Rme. Garll3ld Co Regional AP.Colorado WofishsetA Locaton And Design Condi0ons 99tl D€ . -2.0 'F OB= 70.0'F HID = 72.0 'F 1.3 DB 3 105.0 "F RH = 35% Elevatlon: 5.5,|8 ll CID=300'F Coincident tr,rts E 59_0 .F lndoor Conditlons. Coollno: Aeains = -52.9 OB * 75-0 'F Latilude: 40 RH E 45% Created ljsing HeatCAD 2021 (8n412021) Soflware Ve6ion:2,1.0.0280 R Page 2 ol 14See sections at end of report for important Notes, Assumptions and Disclaimers. c b a Panel Wor*$eetB HIU Valws 6or Wndo{F and Glass Doors DLryResiderEe MESA COUNTY wrNDow MESACOUNTY wru)ow MESACOUNTY WNDOW Cmst Nwbet 8{nttsirediwDls (50%l BlintlsMediun4S 150961 ElindsMedium4S {s0%} lntenal Shede s w N Fees o.300 o 300 o 300 U. value 0.30 0.30 o.!(} 3tGC Nme None Nore lnSect 3ct€en 100 1.00 1.OO Exaemrl Shaillnq None None None O\r€rhffiq 21 60 21.60 21.60 Hcrt Hlt 17.64 3't.28 12.27 Cool lfiM Proiect#: Name: Dury Residen€ Manual J Worksheets Argust 23, 2024 Created Using H€etCAD 2024 18/2612021) sofhrare Ve6ion:24.0.0280 R Page 3 of 14See sections at end of report for important Notes, Assumptions and Disclaimers. lFfl Worksheot C HTli Values for Skylights Dury Resideice Gonil Numbcr lntemal shadlng fitr Faces u-velre SHGC OescriFdon FerimeGr Al?a u€,ft He.dnq Hnt Cooling Hlllt Prcject#: Name: Dury Residence Allload valu6 shiln in Btu/hr Manual J Worksheets August 23, 2024 Created Using HeatcAD 2021 (a12612o21\ Software Versioh:24-0.0280 R Page 4 of 14See sections at end of report for important Notes, Assumptions and Disclaimers. Radiant Rools a Passlve Floors Ceillnqs Below Grrde Walls a Partition Walls Wood and Metal Dooc construction Nunber and Erposure DiECtiOn, oi Ceiling Slop€ Worksheet D HTM Valu* and Net Area for Opaque Panels Dury Residence 228-1OD Cuslm 12&0s (Parlilion) '12&4sw 11J 30 91 6 Length (Ft) HID = 72.O "F 10 10 7 Av€Ege Height wdth (Ft) 931 931 303 914 40 37 Gmss Area {sqFt} CrD=30O'F 20 18 74.U oPening Area (sqFrl 931 242 840 l,let Area (sqFt) Design Range = High 122 Slab Edg€ (Fr' 0.355 0 020 0 0s7 0.097 0 600 U-Value or Slab F-Value 4A 72.0 72.O 720 72.O 72.A HlD or PIDH Healing HTM = U xHTD or U xPTOH Cmlinq HTM = U xCLTD or U xPTOC d B Grcup NumbBr .tA 0.0 500 237 34 1 36.0 cLllt 4B oa PlDC 25.56 1]l7 598 6.S8 43.20 Heating HIIT'I 0.00 102 230 3.31 21 60 Coolidg Hrilt Prcject #: Name: Duffy Residence Allload values shNn in Btu/hr Manual J Worksheets August 23, 2024 created Using HeatCAO 2024 (812612021) sofiware VeFionr24.0.02E0 R Page 5 of '14See sections at end of report for important Notes, Assumptions and Disclaimers. 1 The room infifiralion load equals the block infiltration load 0n the cenlral equlpment munrplr€d Dy lhe gross wall area ratio (wAR). 2 WAR = Gross room luall area / Gross trdll area for all rooms served by the central equipmenl l.:t Lo.d llens Loa.l Hcft Lord lyp€ ot Load step 2 - lnfitlnti,on Loads on Conlrll EquiFnant lAdluEta.l for Sprce Prr$ure) Coolinq Heetng Op€rathg Mode Step I, Opdon 1 - lnfftilaton Loa.ls ior Neulrrl Space Prrs6ul€ gased on ttble S rCH Values HrD = 72.0 "F Worksh€€tE lnfiltratbn Lo.ds 21 21 VCFM Line ll, Worksheet H 931 931 Floor Aru.(cuftl 21 OA Gfin Flowlng to space SemiTOht Semtfqht Xable 5 L€atage Category CrD = 3O.0 'F 21 21 Cfrn Erhaugtad frdn Spac€ o.n 0.4 Spae ACH 0 0 CFMru 0.308 9.306 AGV (cuFtl DesiEn Gnins = -52.9 3{ 63 ICFM (opdon 1) u 63 Space ICFM 34 63 Net lntilt. CFM NCFIt 0 Firepac€ ICFM lrble 104 ACF = 0 83 v21 4.124 HAC Loadg (Bruhl u 63 Totil tcFlil Project #: Name: Dufly Residence Manual J Worksheets August 23, 2024 CEated Using HeatCAD 2024 (8P8120241 Sofrware VeFion:2i1.0.0280 R Page 6 of l4See sections at end of report for important Notes, Assumptions and Disclaimers. ConsKterdiversitv. Load Factor = Averaoe hgul I Rated or Nameolate lnout: Use Faclor = percent operatinq time tor one hour Total pl.nt lm.l tor Fom Jl (Btuhl = e Total indivldual epDliane load for Form Jt {Btuh} E d Totll adluslrnent op{ons for Fofrr Jl (Btuh} = c O€fault scenado load tor Fonn Jl (Btuh) = b Tolal osupancy l€d for Fom Jl (Btuhl = a Source of lntemal Load Worksheet F lnbmal Loads Lame Medlum Small Plams None lndividual Appliance Options None AdiustmenG to Detault soenerio Default i1.200 8tun) Detault Scenario Occupanls 0 0 0 I couil 30 20 1o 1.200 230 Sensible Factor (Btuh) 200 Lrtcnt Factor (Btuh) 1.0 10 Load Factor 1.0 1.0 Use Factor 1"200 1.200 460 450 Senslble Loaal 400 400 Latent L€d Project #: Name: Dufry Residenc Allload values shiln in Btu/hr Manual J Worksheets August 23, 2024 created Using HeatcAD 2024 (812612024) Sofrware VeEioh:24.0.0280 R PageT ot 14See sections at end of report for important Notes, Assumptions and Disclaimers. L.t Load Scn Ldd Heat Lcd Wpe ot Loaal Work3heet H Ventlafon Loads Dury Residence 21 21 vcFttt or CFMds 0 0.5 0.5 SER LER for Heal Recovery Ventilalor GFinw LATw lATw condition ot Air Leaving ventilation Oehumidfier FoT VDH Only lndgot Grrins for Slte El.vadol Titbt€ 12 -52.,9 1050.F -2.0 "F lieblc! I Outdoor Condition To arid Gr!ins 30.0 "F 720 "F HID and ctD Fmm wft(sht 00 900 34.0 l-ATrst l-ATea V€rains for venfllatbn air 0.83 Site Elevation 5.548 Irble 10A ACF 750 70.0 tl lndoor Drybulb 282 576 Vsnt. Loads (Btuh) Project #: Name: Dul1y Residence Allload values sh@n in Bfu/hr Manual J Worksheets August 23, 2024 Created Using HeatcAD 2021 (ADEl2o2q Sofrware VeBion:24.0.0280 R Page 8 of 14See sections at end of report for important Notes, Assumptions and Disclaimers. Moistu€ will mqrate lhmugh porous ceiling. wall. and floor malenals lhat are not prolecled by a vapor retarding membrane the latent morslure migEtion ,ud for summer coolrng may be an important issue if the structure does not have an appropnate vapor relarding membrane lor lhe Imal summer climate For unter humadifcation. moisture mgration may cau* visible or concealed condensatron. mold" mrldew. and structura' damage Str the tull veGion of lvlanual J. Sectron 28 tor basic guidance. Contact the Energy Eflicrent Burlding Asstr€tron (EEBA) tor comp€hensve guidance pertaining to mffibrane need and us€ See the 201 2 ASHRAE Handbook of Fundamenlals. Cnapter 25 and Cnap€r 25 Compate local €ode with EEBA,/ASHME gurdance lncompatibilnaes require the atlention ot the local code authority Jm Lslrburek rs the primary aulhority on lnis issue iobtain contact info from the EEBA. ASHRAE, or inlernet *arch) Manulacture/s Sensible Capacity Data not Adjusted for Blower Heat Blower Motor Load SizelI'ype Hot Water Plping Load Heal ofevaporation provided by cenlral neatng equipmenl. Humidification {RH value) shall not cause visrble or concealed condensation (per Seclion 27 Druedures) Heating Load = 0 68 x TCFM x (IDGR Gallons Per Day = 0 00272 - ODGR) x AcF x Heating Load 700 Dy Eulb lndoor Conditions Winter HumidifiHtion Heatlng Load Worksheet I Ancillary Loads Duffy Residence Relative Humidity watls Blower Motor Power trom Feet ol Pipe L; -20 Winler Dry Bulb Table I Values KW Water Temp. T*"F 5 548 Site Elevation HP Ambient Temp. T".F o 4291216 Table 10A ACF 500 Watts Detault Power Wall ID WTDi outdoor ODGR Table 12 Gnins 1 706 Btuh Defautt Loaal Table I Factor F9i 467 lndoor IDGR Btuh Sensible Load Piping Load PL; 63 Net lnfilt NCFM Outdoor CFM Sensible Load = 3 413 xwatls Sensibie Load = 3.113 x K$/ SensibleLoad=3600xHP vfio = T,,-T, PL'=1 lxLixWIDixFgr System Total (Btuh) = Sum PLI 21 vent VCFM Totill TCFM Humld H-Load (Eruh) 0.0 Gallons P€T Day Prcject #: Name: Duffy Residence System Manual J Worksheets August 23, 2024 Created Using HeatCAO 2024 (826nO24) Softuare Version:24.0.0280 R Page I of 14See sections at end of report for important Notes, Assumptions and Disclaimers. Projeci #: Name: Dury Residene oru Kldr.i 8cd ffi Rooatr RoomLoa& Odfy Residence 3.024 10.149 4.8il] 1,3.i' lldl@d F0hl 1.175 5.4f9 2,997 834 Sef,r Lo€rt(tuhl ?ea* L€d ProeduG Used For Room LGds All load vahes shdn in 8tu/hr Manual J Worksheets August23,2024 Ceated Using HeetCAD 2021 (8EEDO21, Sofrv{aie VeFioh:24.0.0280 R See sections at end of report for important Notes, Assumptions and Disclaimers.Paqe 10 of '14 Prcject #: Name: Dufry Residen€ lotalHerury;200ll Tot lSeosiuert0,965 Totrll-alent400 Totil AE. Tobl Ldd Ra6wd Bld Los R dhnt86dLo$ Pbhq Ld XffiS Vm&tu Dld Ld hbmal hffi&n Fbrs Ceh0s Behw G& Wtk Doo6 sh shts. kmc gtn n,03t 0 0 0 0 678 0 1.121 1,X7 0 7,837 1,74 0 1,1 70 ffa.hg cal ffF 10365 6? 1,706 0 1,668 9?r 0 s0 3,a27 0 1,0€0 ScnsiM ,100 0 0 4& 0 L.bnl 'Awrage Load P'o€duE Allload values shwn in Btu/hr Manual J Worksheets August 23, 2024 Created Using HeatCAD 2024 l8l26D921l Sofiware VeBion:24.0.0280 R Page11 of14See sections at end of report for important Notes, Assumptions and Disclaimerc. Prcject #: Name: Dufry Residence Manual J Worksheets August 23, 2024 Cortrucdons Walls 12B-Osw(Partrtion) 12&Osw Frare Wall or Panition: Wood Framlng, R-11 lnsulalim tn 2 x 4 ritud Cavity: Stucco or Wood Siding: Plus lnterior Finlsh Frarne Wall or Parlilion: Wood Framlng; R-11 lnsulatim in 2 x 4 *tud Cavlty: Slucco or wood Siding: Plus htenor Finish 0.097 0 0s7 u-hb{m4k+rlt DooB 1lJ Metal Dmr with Fibemlass Cm o 600 u.v.lc|W+.fl1 Floors 22810p 228 - Venical Eoard lnsulatbn covers slab Edge and Extends stralgil Down to Thfee Feel Below Grade. any Floor Cover 0 lo0 Celllngs Custom lnsulalred Ceiling Under At[r or Afiic Knee Wall (vented W Radianl Bafier); R-54 lns{lalion; Roof Malerial: Metal: Roof Color Oar(0.020 0-v.rE lb{I.+Tll Glazings lMndos MESACOUNTY VVINDOW (SHGC: 0.3)0.300 U-V.hlMrG€l All load velues shown in Btu/hr Created Using HeatCAD 2024 (812612024\ Sofrware VeBion:24.0.0280 R Page'12 of 14See sections at end of report for important Notes, Assumptions and Disclaimers. Prcject #: Name: Dufly Residene 30[n 2000 Fanssfidion Loadvs Hdr of Day{Smilmr} Manual J Worksheets August 23, 2024 created using HeatcAD 2024 (El26no2q sotuare Versioh:2,1.0.0280 R Page 13 of 14 cJ6 1[00 AveBge Load: I,473 Blulht Excursion Limit 1,915 Btu/hr BS1ilt11l 13 14 15 HBur of Dav Peak Load: 1,982 Blu/hr AED Load: 67 Btu/hr 16 17 18 19 ?0 All load valu6 shown in Btu/hr 30 Ltrd Line *,veragc See sections at end of report for important Notes, Assumptions and Disclaimers. Project #: Name: Dufry Residene Manual J Worksheets August 23, 2024 ACCA, Manual J and PNered by ACCA Manual J are registered hademarks oI the Air Conditioning ContractoF ofAmedca. All rights re*rued. Cold weather humidifcation, or some lifFtyles that prcduce ercessive moisture, may trause condehsation to occur iflhe absolute humidit/ ofthe indoor air is too high for the mohentary citcumstances. Condensation can occut on sudacs or concealed within the structute, and can lead to mold, mildew, frost darage, and moisture damage. The software does not pedDm €lculalions forthe eslimation or detec'lion ofpossible condensation problems, and it is the designeF [.e. sofrvare usec) responsibility lo do so independentv il required. Forguidance and addiliohal cautjohs relerto AccA Manual J 8th Edition, ihclucling sectioh 1-11 and seclioh 2-. You are strongly advised to review all ihput data €refully, and to have the Blculated results revi*ed by ah expedenced heating profFsbhal to ensure reasohableness and suitatility for your appl,cation. IN NO EVENT WLL AVENIR SOFTWARE INC. CAVENIR") OR ITS AFFILIATES BE .IABLE UNDER ANY CONTRACT, NEGLIGENCE. STRICT LIABILITY OR OTHER LEGAL OR EOUITABLE THEORY FOR ANY CONSEOUENTIAL, INCIDENTAL, INDIRECT OR SPECIAL OR PLINITIVE DAI\,IAGES WHATSOEVER (l.lCLUDlNG, BUT NOT LIMITED TO, DAMAGES FOR LOSS OF BUSINESS PROFITS, BUSINESS INTERRUPTION, LOSS OF BUSINESS INFORMATION OR DATA AI]D THE LIKE), EVEN IF SUCH PARTY HAS BEEN ADVISED OF THE POSSIBIUTY OF SUCH DAMAGES. AVENIR'S CUMULATIVE UABILITY FROI\4 ANY CAUSE RELATEO TO OR ARISING FROM THE USE THIS REPORT, AND REGARDLESS OF THE FORM OF THE ACTION, SHALL BE LIIUITE] TO NO GREATER THAN THE AMOUNT OF FEES PAID TC AVENIR UNDER THE SOFTWARE LICENSE AGREEMENT. Warnings This appli€tion has glass areas that produced relatively large cooling loads for part ofthe day. Zoning may be required to overcom€ spikes in solar load for one or more rooms. Azoned system may be required or some rooms may require zone control (provided by individual, motorized, themostaticalt cordrolled dampers). Disclaimers Wth the permission ofthe Air Conditioning Codradore of America ('ACCA), material is reproduced from Manual J R*idenlial Load Calculalion (8th Editionl which is copydghted by ACCA, The prograh ahd data are provided "as is" withod warahty of any kind eitlEr expressed or implied. The entire risk as the qually and performance ofthe program and arisihg out of the use cr inability to use this program or the data. @ 2015 Air Conditioning ConbactoF of America. All Rights Reseryed. w.acca.org Allload values sh@n in Btu/hr Created lJsing HeatCAO 2024 (A26nO24') Software VeEion:24.0.0280 R Page 14 ol 14See sections at end of report for important Notes, Assumptions and Disclaimers,