HomeMy WebLinkAboutConditions of Permitco NDITIONS OF PERMIT
BLRE-O 8.24-8845
PH ILIP ENSIG N
640 SO FT DETACHED UNHEATED GARAGE SHOP
(NO PLUMBING, WATER SUPPLY OR HEATING PROPOSED)
683 Overlook Dr, GWS
High Aspen Ranch Planned Community, Lot 23
1 ) ALL WORK SHALL COMply W|TH THE 2015 INTERNATTONAL RESIDENTIAL CODE
t.R.c. / t.B.c. AND 2018 TNTERNATTONAL ENERGY CONSERVATION CODE (l.E.C.C.)
2) PROPOSED IMPROVEMENTS ARE SUBJECT TO ALL APPLICABLE ITEMS CONTAINED
IN THE ATTACHED "GARFIELD COUNry BUILDING REOUIREMENTS". NUMBER
REFERENCES NOTED ON PLANS REFER TO SPECIFIC ITEMS ON THIS LIST.
3) ELECTRTCAL PERMtTTtNG AND TNSPECTIONS BY COLORADO STATE ELECTRIC
BOARD. ELECTRICAL ROUGH-IN APPROVAL IS REOUIRED AT FRAME INSPECTION.
ELECTRICAL FINAL APPROVAL IS REOUIRED FOR FINAL INSPECTION &
CERTI FICATE OF OCCU PANCY.
4) ALL EXTERTOR LIGHTING TO BE DOWNCAST AND SHIELDED.
5) WILDFIRE MITIGATION RECOMMENDATIONS: SHOULD COMPLYWITH WILDFIRE
MITIGATION AND DEFENSIBLE SPACE REOUIREMENTS PER COLORADO STATE
FOREST SERVICE AND LOCAL FIRE DISTRICT. PLEASE SEE GARFIELD COUNry
COMMUNIry DEVELOPMENT WEBSITE FOR FURTHER INFORMATION.
6) OPEN HOLE SOTLS REPORT rS REOUTRED AT FOOTTNG TNSPECTION 2,000 PSF SOIL
BEARING CAPACIry.
7) ALL HIGH STRENGTH BOLTING AND FIELD WELDING REOUIRES SPECIAL
INSPECTOR. PROVIDE APPROVAL REPORT AT FRAMING INSPECTION.
B) SOLAR PERMIT AND FUTURE INSPECTIONS THROUGH COLORADO STATE
ELECTRICAL INSPECTION DEPARTMENT. IF SOLAR BATTERY EOUIPMENT IS
INSTALLED, THEN SHALL PROVIDE SOLAR BATTER EOUIPMENT INSTALLATION
MANUAL TO BUILDING INSPECTOR AT FUTURE INSPECTIONS.
9) ENERGY STORAGE SYSTEMS (ESS)SHALL BE INSTALLED IN ACCORDANCE WITH
2021 R328 (ATTACHED).
1O)THE BUILDING STRUCTURE HAS BEEN REVIEWED AS A PRIVATE USE DETACHED
GARAGE SHOP ONLY ACCESSORY TO THE MAIN RESIDENCE. ANY FUTURE
CHANGE IN BUILDING OCCUPANCY OR USE, WILL FIRST BE SUBJECT TO A NEW
BUILDING PERMIT APPLICATION AND REVIEW FOR COMPLIANCE WITH ZONING
REGULATIONS, LAND USE & BUILDING CODES IN EFFECT AT TIME OF FUTURE
WORK.
*
,E\
N
N
aNbrTTatV #fBUILDING PLANNING
R326.4 Means of egress. The means of egress for habitable
attics shall comply with the applicable provisions of Section
R311. /
sEcTloN R327
SWIMMING POOLS, SPAS AND HOT TUBS
F.327.1 General. The design and construction of pools and
spas shall comply with the International Swimming Pool qnd
Spa Code.
sEcfloN R328
ENERGY STORAGE SYSTEMS
R328.1 General. Energ,, storage systems (ESS) shall
comply with the provisions of this section.
Exceptions:
1. ESS listed and lqbeled in accordance with UL
9540 and marked "For use in residential dwelling
units" where installed in accordance with the
manufacturer's instructions and NFPA 70.
2. ESS less than 1 kWh (3.6 megajoules).
R328.2 Equipment listings. Energ,t storage systems (ESS)
shall be listed ar,ld labeled in accordance with UL 9540.
Exception: Where approved, repurposed unlisted baffery
systems from electric vehicles are allowed to be installed
outdoors or in detached sheds located not less than 5 feet
(1524 rnm) from exterior walls, property lines and public
ways.
R328.3 lnstallation. ESS shall be installed in accordance
with the manufacturer's instructions and thetr listing.
R328.3.1 Spacing. Individual units shall be separated
from each other by not less than 3 feet (914 mm) except
where smaller separation distances are documented to be
adequate based on large-scale fire testing complying with
Section 1207 .1.5 of the International Fire Code.
I{328.4 Locations. ZSS shall be installed only in the follow-
ing locations:
1. Detached garages and detached accessory structues.
2. Attached garages separated from the Awelling unit
living space in accordance with Section R302.6.
3. Outdoors or on the exterior side of exterior walls
located not less than 3 feet (914 mm) from doors and
windows directly entering the dwelling unit.
4. Enclosed utility closets, basements, storage or utility
spaces within dwelling units with finished or
noncombustible walls and ceilings. Walls and ceil-
ings of unfinished wood-framed construction shall be
provided with not less than s/r-inch (15.9 mm) Type
X gypsum wallboard.
ES,S shall not be installed in sleeping rooms, or closets or
spaces opening directly into sleeping rooms.
R328"5 Energy ratings. Individual ESS units shall have a
maximum rating of 20 kWh. The aggregate rating of the ESS
shall not exceed:
1. 40 kWh within utility closets, basements and storage
or utility spaces.
2. 80 kwh in attached or detached garages and detached
accessory structures.
3. 80 kwh on exterior walls.
4. 80 kwh outdoors on the ground.
ESS installations exceeding the permitted individual or
aggregate ratings shall be installed in accordance with
Section 1207 of the International Fire Code.
R328.6 Electrical installation. ESS shall be installed in
accordance with NFPA 70. Inverters shall be listed and
labeled in accordance with UL 1741 or provided as part of
the UL 9540 listing. Systems connected to the utility grid
shall use invefters lis ted for utility interaction.
R328.7 Fire detection. Rooms and areas within dwelling
units, basements and attached garages in which ES,S are
installed shall be protected by smoke alarms in accordance
with Section R314. A heat detector, listed and intercon-
nected to the smoke alatms, shall be installed in locations
within dwelling units and attached garages where smoke
alarms cannot be installed based on their listing.
R328.8 Protection from impact..E55 installed in a location
subject to vehicle damage shall be protected by approved
barriers.
R328.9 Ventilation. Indoor installations of ES,S that produce
hydrogen or other flammable gases during charging shall be
provided with mechanical ventilstion in accordance with
Section M1307.4.
R328.10 Electric vehicle use. The temporary use of an
owner or occupant's electric-powered vehicle to power a
dwelling unitwhile parked in an attached or detached garage
or outdoors shall comply with the vehicle manufacturer's
instructions and NFPA 70.
11.328.11 Documentation and labeling. The following
information shall be provided:
1. A copy of the manufacturer's installation, operation,
maintenance and decommissioning instructions shall
be provided to the owner or placed in a conspicuous
location near the ESS equipment.
2. A label on the installed system containing the contact
information for the qualified maintenance and
service providers.
sEciloN R329
STATIONARY ENGINE GENERATORS
R329.1 General. Stationary engine generators shallbe listed
and labeled in accordance with UL 2200 and shall comply
with this section. The connection of stationary engine gener-
ators to the premise wiring system shall be by means of a
I i s t e d tr ansfer switch.
N,t
.l
D