July 12,2021 Project No. C1614
Ben Wagenman
oleoconstruction@qmail.com
Subsurface lnvestigation and Onsite Wastewater Treatment System Design
3-Bedroom Residence + 2-Bedroom ADU
TBD CR 238
Garfield County, Colorado
Ben,
CBO lnc. performed a subsurface investigation and completed an onsite wastewater treatment system
(OW|.S) design for the subject residences. The 5.543-acre propefi is located outside of New Castle, in
an area where OWTSs and wells are necessary. We have made some clarifications from the design
dated June 29,2021, which should be discarded and replaced with these dated July 12,2021 .
Legal Description: Section: 6 Township: 6 Range: 91 A TR lN SEC 6 CONT 6.35 AC AKA LOT 2 MAVES
SUBDIVISION EXEMPTION. EXCEPT A TR OF ISND CONT .807 AC +/. AS DESC IN BNDY LINE ADJ
BK 1636/937 AND QCD BK 1636/940 5.543 ACRES
Parcel lD: 2181-062-00-283
SITE CONDITIONS
The property is currently undeveloped. A 3-bedroom, single-family residence and detached 2-bedroom
accessory dwelling unit (ADU) are proposed.
The property will be served potable water from a private well. The well is located to the west of the
proposed ADU. The well will be located greater than S0-feet from the proposed septic tank and greater
than 100- feet from the proposed soil treatment area (STA). The water line will enter each residence
from the east and will not come within 25-feel of any OWTS component.
The proposed STA location has an approximate 5-10% slope to the southwest. The proposed area
vegetated with native grasses.
There should be no Oaffic or staging of material over the fufure STA site to avoid compaction of soils
prior to construction of the STA.
SUBSURFACE
The subsurface was investigated on May 4,2021 by digging two soil profile test pit excavations (Test Pits). A
visual and tactile soil analysis was completed by Carla Ostberg at the time of excavalion.l
I Carla Ostberg holds a Certificate of Attendance and Examination from the CPOWVisualand Tactile
Evaluation of Soils Training.
Page2
The materials encountered in Test Pit #1 consisted of dark brown topsoil to 0.S-feet, underlain by light
brown, dense sandy loam to a maximum depth explored of 8.O-feet. No bedrock or groundwater was
encountered.
The materials encountered in Test Pit #2 were consistent with those encountered in Test Pit #1. Test Pit #2
was elplored to a maximum depth of 8.O-feet. No bedrock or groundwater was encountered.
A sample of the soils was taken from Test Pit #1 at 3-feet below grade. Soil structure grade was weak.
The soil formed a ball and a ribbon less than 1-inch in length before breaking. Soil structure shape was
blocky and consistence was friable. Soil texture was more gritty than smooth.
STA sizing is based on Soil Type 2A, Sandy Loam with weak structure grade. A long term acceptance
rate (LTAR) of 0.5 gallons per square foot will be used to design the OWTS.
Test Pit #1
Page 3
Test Pit #1
Sieved sample
Looking est
Page 4
Sidewall of Test Pit #2
Page 5
View of site
DESIGN SPECIFICATIONS
Desion Calculations:
nverageOesignFlow=75GPDx2people/bedroomx3Bedrooms=450GPD+2-BedroomADU(300
GPD; = 750 GPD
LTAR = 0.5 GPD/SF
750 GPD / 0.5 GPD/SF x 1.0 (gravity trenches) x 0.7 (chambers; = 1050 SF
The OWTS design is based on 3-bedrooms in the main house and 2-bedrooms in the ADU. An average
daily wastewater flow of 750 GPD will be used.
For the purposes of this OWTS design, Benchmark Elevation 100' has been identified Finished Floor of
the Main House. CBO lnc. should be notified of any discrepancies or problems with grade elevations of
proposed components during installation of the OWTS.
*Elevations are based upon standard OWTS installation
installation due to site conditions.
Component elevations may change during
The 4-inch diameter SDR-35 sewer line exiting the residence must have a double-sweep clean out and a
minimum 2o/o grade to the septic tank.
The system installation must include a 1S0O-gallon, two-compartment poly lnfiltratot@ septic tank with an
effluent filter on the outlet tee. A concrete septic tank may be substituted, if desired. Risers must bring
the manhole lids to grade for access. lf more than one riser is added to the septic tank, an extension
handle must be installed on the effluent filter.
Minimum ElevationOWTS Component
Approximate horizontal distance 143' / min. 2o/o fall
to septic tank / min. 35.75" fall
Primary Tank lnlet lnvert
Approximate horizontal distance 37' / min. 1o/o fall
to d-box / min. 4.625" fall
Distribution Box
Approximate horizontal distance 10' / min. 1o/o fall
to infiltrative surface / min. 1.25" to upper-most
trench
lnfiltrative Surface
Page 6
Effluent will gravi$ flow to a distribution box, and then to five gravelless chamber trenches. The
distribution box must be accessible from grade and must have flow equalizers, or similar product,
installed on each outtet pipe in the distribution box to assure equal flow to each trench.
Each trench will consist of 18 'Quick 4' Standard Plus lnfiltrator@ chambers for a total of g0 chambers
and 1080 square feet of infiltrative area. There must be at least 4-feet of undisturbed soil between each
trench. lnspection ports must be installed at the beginning and end of each trench. Ports may be cut to
grade and placed in sprinkler boxes for access.
COMPONENT SPECIFICATIONS
The component manufacturers are typical of applications used by contractors and engineers in this area.
GBO lnc. must approve alternative components prior to installation of the OWTS. Requests must
be submitted, in writing, to our office for approval prior to installation. Component technical data
sheets are available upon request.
Construction must be according to Garfield County On-Site Wastewater Treatment System Regulations, theowrs Permit provided by Garfield county Building Department, and this design.
INSTALLATION CONTRACTOR
CBO lnc. expeCs that the installer be experienced and qualified to pei'form the scope of woi'r outlined in this
design. The installer must review this design thoroughly and coordinate with our ofiice in advance of
installation. Any additional conditions in this design or county permit must be completed and documented
priorto final approval of the OWIS installation. Communication between the installer and this office is
expected throughout the installation.
INSTALLATION OBSERVATIONS
CBO lnc. must view the OWTS during construction. The OWTS observation should be performed before
backfill, after placement of OWTS components. Septic tanks, distribution devices, pumps, dosing
siphons, and other plumbing, as applicable, must also be observed. CBO lnc. should be notified 48 houri
in advance to observe the installation.
ln an effort to improve the accuracy of the record drawing, we request that the installer provide a
sketch of the installation, including path of the sewer lines, water line installation (if applicable),
septic tank location, STA location, and measurements from building cornens or anothei fixed
gbjects on the property. This sketch is most easily provided on Sheet \ 2.0 of the OWTS Design
Packet. Photographs of the installation and final cover are also requested to supplement our installation
documentation.
COMPONENT IMANUFACTURER MODEL NO.lcoMMENTs
Septic Tank
f
nfiltrator@ tM-1530-2CP ll 500gallon, 2-compartment
lpolv septic tank
Biotube Effluent Filter
frenco@
lFutlsize
lhousinq
Effluent Filter and
fank Risers and Lids
f*""*
lDouble-walled PVC
lr-ios
tz+'diameter)
Risers and
Distribution Box
leoVrot lDistribution box, flow
bqualizers. risers. lid
Shambers
llnfiltrator@
Standard Plus lgo 'Quick 4'
lChamoers
Standard Plus
PageT
REVEGETATION REQUIREMENTS
An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire
disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing
characteristics (but without tiaproots), provides a maximum transpiration rate, and competes well with
successional species. No trees or shrubs, or any vegetation requiring regular inigation shall be placed over
the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented
and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation
cover.
OPERATION INFORMATION AND MAINTENANCE
The property owner shall be responsible for the operation and maintenance of each OWTS servicing the
property. The propefi owner is responsible ficr maintaining service contracts for manuhctured units,
altemating STAs, and any other components needing maintenance.
Geo-fubrics or plastics should not be used over the STA. No heavy equipment, machinery, or materials
should be placed on the backftlled STA. Machines with tracks (not wheels) should be used during
construction of the STA for better weight distribution. Livestock should not graze on the STA. Plumbing
fixtures should be checked to ensure that no additionalwater is being discharged to OWTS. For example, a
running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA.
lf an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned
annually, or as needed. lf the OWTS consists of a pressurized pump system, we re@mmend the laterals be
flushed annually, or as needed.
The homeowner should pump the septic tank every two years, or as needed gauged by measurement of
solids in the tank. Garbage disposal use should be minimized, and non-biodegradable materials should not
be placed into the OWTS. Grease should not be placed in household drains. Loading from a water softener
should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS.
Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste
only.
ADDITIONAL CONSTRUCTION NOTES
lf design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of
freezing. The pump shall have an audible and visual alarm notification in the event of excessively high
water conditions and shall be connected to a control breaker separate from the high water alarm breaker
and from any other controlsystem circuits. The pump system shall have a switch so the pump can be
manually operated.
Excavation equipment must not drive in excavation of the STA due to the potential to compact soil.
Extensions should be placed on all septic tank components to allow access to them from existing grade.
Backfill over the STA must be uniform and granular with no material greater than minus 3-inch.
LIMITS:
The design is based on information submitted. lf soil conditions encountered are different from conditions
described in report, CBO lnc. should be notified. All OWTS construction must be according to the coun$
regulations. Requirements not specified in this report must follow applicable county regulations. The
contractor should have documented and demonstrated knowledge of the requirements and regulations of
the county in which they are working. Licensing of Systems Contractors may be required by county
regulation.
Page 8
Please call with questions.
Sincerely,
CBO lnc.
Carla Ostberg, MPH, REHS
Ce,\{u 0st6u.g
s 88"48'05'E ^--rZ.7sa-*uonht,@_9.
Fount2" Pipe & 3-1/4"
F6
Brass Cap Stamped
"Countg Suregor Qarfeld
countg co1/a s6 1979',
1,0' Aboue Surface
x
1 4.5'
)
I
I
Ferce
b
I
I
I
I
I
I
I
)
A
gy
toso'
^ho'
v
lq
\
CN
N
t
@ SCALE: 1'= 50'4'
Existing DittRoad
DRAWINGS MUST BE USED IN
CONJUNCTION WITH DESIGN
LETTER DATED 07 I 1212021
"."t'
I
I
CBO lnc,
129 Cains Lane
Carbondale, ColoEdo 81623
Phone 970,309.5259
cada.ostbsrg@gmail.@m
Wagenman Residence
TBD CR 238
Garfleld County, Colorado
Project Number: C1614
Datat 0612912021
Revlsedi07l121202'
Designed by: CBO
Drawn by: DD
w1 .0
Sheet I 0F 4
2.BEOROOM
AOU
N
1 8.s',
3.BEDROOM
RESIDENCE
BM 100'
FF
4' DIA SDR-35 SEWER PIPE WITH CLEANOUT
MIN 206 FALL TO TANK
1 sOO.GALLON, TWGCOMPARTMENT
SEPTIC TANK WITH EFFLUENT SCREEN
4'DIA SDR.35 SEWER PIPE WITH CLEANOUT
MIN 2OlO FALL TO TANK
\
SCALE: 1'= 20{"x
\
Barl
Wire
CLEANOUT
EVERY 1OO'
o
4,{m€
4" DIA SDR.35 SEWER LINE TO STA
(MrN. 1% rALL TO CrA)
BOX
10'
3.2',
4'DIA SDR-35 SEWER LINE TO EACH TRENCH
(MtN. 106 SLOPE TO TRENCH)
4'DIA SDR.35 INSPECTION PORT AT
BEGINNING ANO END OF EACH TRENCH
WITH ACCESS AT GRADE
I
PROPERry
'QUICK.4' CHAMBER TRENCHES.
5 TRENCHES WTH 18 CHAMBERS PER TRENCH
FOR A TOTAL OF 90 CHAMBERS AND
1080 sF.
TP
sy
o:u/
*$/at/./
h
Ol\r
o|-r
o\
CBO lnc.
129 Calns Lans
Carbondals, Colorado 81623
Phone 970.309.5259
eda.ostbelg@gmail.om
Wagenman Residence
TBD CR 238
Garfleld County, Colorado
Project Number: C1614
Oale: 06n912021
Reubed$7 112!2021
Dasignad by: CBO
Drawn by: DD
w2.0
Shest 2 0F 4
CBO lnc-
129 Cains Lane
Carbondals, Colorado 81623
Phone 970-309.5259
@ds.ostberg@gmell.@m
FINFILRTOR
/ exoewre oucK4 DIA SDR.35 SEreR
CHAMBER (4'x 3)LIilE TO EACH TRENCH
(MlN.1%SLOPETO
TffircH)
4" OtA SDR-35
EFFLUENT HE FRN
NOE: MAINTAIN SHALCM
INSTALLATNN BETre€N Z
AND 3
BSREfi6N BOX WH DIA SDR-35
AT GRADE lNsPEClls,l
POffi
PLACED IN
1',TOP rcRT OF
CHNBER ENDMES so[-j'
PIPE TO LF!4lT
M TRENCH EXCAVATION fl&3',
cHmER (4 x 3)
1" DIA SDR-35 INSPECTION
PORT AT BEGINNING AND
END OF EACH TRENCH
/A olatBci{ IRENct{ rsEciitot{rgi---7f!lt
//iC+lAlBER IRENO{ Pt l{u./t-'---?!rE
VALW MWR
BOX OR IRRGATION
VIVE BOX AT GruE
SLIP-ON PVC
DO NOT GLUE
CAP OR THRAED 24" MIN-
CEANOUT ASSEilBLY
TRACER WIRE FINISHED GRAOE
,t" DIA SDR-35 SEvt ER
coilPAoT 4" DIA
(MtN 20; SLOPE TO TANK,
MlN. 1% TO STA)BASE TO SUPPORT
BOX
wc PIE cu To
FIT SEWER LINE
SCREENED
USE HOLE SAWTO
CUT THRUTOPOF ORSAND FOR
BEDDING
3" MtN-
END TO TANK
MN.
olNsEclleNlsl*tr rL /a\CLEAl'l OUT DEIAL\9|_il @.EssJErartu
18 CHffiERS ER TRENCH
zll
Wagenman Resldence
TBD CR 238
Garfi sld County, Colorado
ProisctNumben C1614
h,ee: o6t2gt2o21
heVsed:O7n2n121
besbned by: cBo
lDrawn by: oo
w3.0
Sheet 3 0F 4
CEOlm
129 Calns Lane
Csrbondds, ColoEdo 81623
Phons 970.309.5259
crla.Gtberg@gmail.@m
DESIGN
iI€EDROOIT RESII,E {CE + I.BEDROOM ADU
75 GPD x 2 PERSONS/BEDRCIOM x 3 BEDROOMS = 450 GPD + 2.BEDROOM
ADU (300 GPo) = 750 GPD
WASTEWATER FLOW = 750 GPD
STATO WATER COURSE 50'5{)'
STA TO WELL 100 218
STA TO HqJSE 20'm'
SEPNC TAHK TO WATER COURSE 50'50'
SEPTIC TAM< TO WELL 50'23s'
, HOUSE TO SEPTIC TANK 5'15
OWTS COUPONENTS AND
PHYSICAL FEATURES
MINIMI,'', REQUIRED
SETBACK
APPROXIMATE PROPOSED
SFTBA(]K
TANK:
MIN. is{N GALLONS
USE I5OGGALLON, TWGCOMPARTilENT POLY SEPTIC TANK
SOIL TREATMENT AREA (STA):
LOIIG TERM ACCEPTANCE RATE (LTAR) = 0.5 GAL/ SF
CALCULATED STA = Q/LTAR = 750 / 0.5 = 1 500 SF
GRAVITY, TRENCHES = |SOO SF X 1.0 = 15@ SF
CHAMBERS = 1s0O SF X 0-7 = 1050 sF / 12 SF / CHAMBER = 88 CHAMSERS
FIVE GRAVELLESS CHAMBER TRENCHES
18'QUICK il' CHAMBERS lN EACH TRENCH
TOTA 90 'QUICK 4' CHAMBERS
SOIL PROFILE TEST PIT NO. 1 SOIL PROFILE TEST PIT NO.2
-0rilt,t!.I
t-,
DARK BROWN TOPSOIL DARK BROWN TOPSOIL
LIGHT BROWN SANDY LOAM WTH
WEAK STRUCTURE GMDE
LIGIIT BROW{ SANDY LOAM WTH
WEAK STRUCTURE GRADE
:u
-6
I
-9t,o
BOXANO COVER BROUGHTTO GRADE
CONCRETE
LEGEND
F topsoll
F-T ilH'
FINSHED GRADE
NO GROUNDWAIER OR BEDROCK ENCOUNTERED
DURING EXCAVATION
BAFFLE OR
ANGLED PIPE
TO BE USED
AT II\f,ET
asoil.s LoG\rr---TE //5\ DISTRIBUTION BOX DEIAIL\9r........'._tT[
CUTLETS
oooo
Wagenman Resldence
TBD CR 238
Garfi€ld County, CdoBdo
Proiec't Numb8r Cl6l4
lD.ate: o6t2gl2o21
hrerlrsed:O7l12Do2'
I oestsneo oy: cao
loramur: oo
w4.0
She€t 4 0F zl
#qFuHlcngt- Garfield County, CO
Physical
Address
Owner
Address
0
NEWCASTLE 8T647
WAGENMAN,THERESA&
BENJAMIN
PO BOX 1954
GLENWOOD SPRINGS CO 81602
2019Total Actual
Value
Overview
Legend
fl Parcels
- Roads
Parcel/Account
Numbers
Highways
r LimitedAccess
* Highway
* Major Road
* Local Road
- Minor Road
* OtherRoad
RamP
** Ferry
'' PedestrianWay
Owner Name
@ Lakes&Rivers
* CountyBoundary
Line
$160,000 Last2Sales
Date Price
5/74/2027 $O
4/76/202! $200,000
Account R0410@
Number
Parcel 2787062@283
Number
Acres 6
LandSqFt 0
TaxArea 752
2019MillLew 67.0920
DaE qeaEdtT/U2O27
Last Data Uploaded: 7 f2/XJ2l !7:37:23 AM
De.reloped bv /t S"l"=idOFt g€osPlrtt't
712t2021 qPublic.net - Garfield County, CO - Property Record Card: R041000
#qftruic,net* Garfield County, CO
Summary
Account
Parcel
Property
Address
lcgel
Deseription
Acres
Land SqFt
TaxArea
Mllltwy
Subdlvision
R041000
218106200283
, NEWCASTLE,CO 81647
Section:6 Townshlp:6 Range: 91 ATR lN SEC 5 CONT 6.35 AC AKA
LOT2 MAVES SUEDIVISION EXEMPTION. EXCEPTATROF LAND
CONT.807 AC +/- AS NFSC IN BNDY LINE AEIJ BK 1636/937 AND
QCD BK 1636/940 5.543 ACRES
5.543
0
752
67.0920
View Map
Owner
WAGENMAN, THERESA & BENJAMIN
PO BOX 1954
GLENWOOD SPRINGS CO 81602
Land
Unit lVpe 5 AC To L,lT 10 AC - 0530 (VACANT LAND)
Square Feet 0
Actual Values
Asscsscd Ycar 2021 20.20 2019
Land Aciual $160,000.00 $160,000.00 $160,000.0O
lmprovementActu", *0.* $O.OO $O.OO
TotalActual $160,qrO.OO $160,000.00 $16O,(X)O.OO
Assessed Values
AssessedYear 2O2l 2O2O 2C79
Land Assessed $46,21OO.00 $46,40O.0O $46,4013.00
Assessed
Total Assessed
thx History
TaxYear 2020
$46,400.00
20t9
$46,400.00
2078
$o.oo
$46,400.00
2017
Taxes Bllled $3,113.08
Cllck here to viewthe tax information for ihis oarcsl on the Garfreld County lieasurer's website.
Transfers
Reception Book- Sale
SaleDate DeedType Number Pas. Price Grantor
$2,930.96 $2,447.12 $2,183.88
Gmnte
5/14/2021 Easement
4IT6/202I SPECIALWARRANry
DEED
95j7A4
954622
$0 WAGENMAN, BENJAMIN; WAGENMAN, PUBLIC SERVICE COMPANY OFTHERESA COLORADO
$2OO,OOO TTTUS,DALER WAGENMAN, THERESA; WAGENMAN,
BENJAMIN
3/TOI2O2T STATEMENTOF
AUTHORIry
952746 $0 TITUS,SUZANNE-DEC T|TU5, SUZANNE-DECi TlTUs, DALE R
7/25/2021 DEATH CERTIFICATE
77/3/2OO4 QUITCLATMDEED
a\t1M
66?A9I ],636-
$O TITUS,SUZANNE
$O TITUS,SUZANNE&DALE
TITUs, DALE R
GUCCINI,TOEY& DEBRA
94
AI3/2OA4 AFFIDAVIT 6(,?A9O 7636-$o
937
3/29/2004 tNCLUStON 654545 1598-
320
$o
https://qpublic.schneidercorp.com/Application.aspx?ApplD='t 038&LayerlD=22381&PageTypelD=4&PagelD=9447&Q=1526834&KeyValue=R041000 1t2
7t2t2021 qPublic.net - Garfield County, CO - Property Record Card: R041000
7/27/2OO4 WARRANryDEED 647047 1563-$o
225
7/27/?OO4 WARRANryDEED 645446 7556-
929
$747,OOO MAVES,DAV|DW TITUS, SUZANNE & DALE R
t/20/2004 RESOLUTION 645280 1556-$o
494
I7/2O/2OO3 BOUNDARY LINE
ADJUSTMENT
1540-
917
$o64r452
7\/2O/2OO3 QU|T CLATM DEED 641457 t54o-$o
975
t7/20/2003 EASEMENT 641450 1540-$o
972
T7/74/2OO3 POWEROFATTORNEY 645447 1556-$o
931
3/27/2OO7 QUITCLAIMDEED 5A?549 1260-$O MAVEs, DAVIDW& MAXINE J MAVEs, DAVIDW
669
6/311992 Deeds 0833-
0386
$o
7/!/t9OO Deeds 0458-
o72A
$o
tltllg00 Deeds 0393-
0510
$o
tltlt900
iitnsoo
Deeds 0369-
0463
$o
Deeds 0362-
0582
$o
tltllg00 Deeds 0357-
0591
$o
tltltg00 Deeds 0205-
0004
$o
Photos
No data available for the following modules: Buildings, Sketches.
crr;n;:l l:* guar:ntesi.
$evtloirrl l4rtt#^ider
lher Privacv Pqlicy
9.P P.F f rivacv.Nptic"q
La l Data uplendr..Z?/201t-?: li:AAM Varsion ?.3.1?8
https://qpublic.schneidercorp.com/Application.aspx?ApplD=1038&LayerlD=22381&PageTypelD=4&PagelD=9447&Q=1526834&KeyValue=R041000 212