Air Leakage Test Report
In compliance with ASTM E-779-10 (2019)
Building Address:186 Maroon Drive
Glenwood Springs, Garfield
CO
USA
Performed for:
Performed by: Amanda Poindexter
Test date:2024-09-12
Associated Test file: 186 Maroon Drive
Report Number:
Unique Property ID Number:
Dexter Diagnostics
9/13/2024
Summary 186 Maroon Drive
FanTestic version: 5.11.88 licensed to:
Test date: 2024-09-12 By: Amanda Poindexter
Customer:
Building Lot Number:
Building address: 186 Maroon Drive
Glenwood Springs, Garfield
CO
USA
Building and Test Information
Test file name:186 Maroon Drive
Building volume [cu ft]:39,683
Envelope Area [sq ft]:0
Floor Area [sq ft]:2,949
Building Height (from ground to top) [ft]:20
Results
CFM at 50 Pa:1967.0
Leakage Area (EqLA) [sq in]:214.5
Leakage Area (EfLA) [sq in]:117.5
Air Changes per hour ACH50:2.97
Dexter Diagnostics
Test Date: 2024-09-12
Client Tester
Building Description Bailon Company Dexter Diagnostics
Building Address 186 Maroon Drive Address 18 Crescent Pl
Glenwood Springs, CO 81601 Glenwood Springs, CO 81601
Contact Luis Technician Amanda Poindexter
Phone 970-355-5386 Phone 720-219-3683
Test Type Duct Leakage to Outdoors Gauge S/N 2070150
Fan series 200 Fan S/N LF2001000
Conditioned Floor Area 2949.0 sq ft
Percentage of Duct Leakage to Outdoors 50% (estimated)
Supply Return
Average Duct Operating Pressure 25.0 Pa 25.0 Pa
Leakage Split 50% 50%
Leakage Penalty 100% 50%
Depressurization
Duct Pressure -25.0 Pa
Fan Pressure 235.0 Pa
Range Configuration Mid
Duct Leakage 113.7 CFM
Leakage Area 21.1 sq in
Leakage constant, C 16.49
Leakage Exponent 0.60 (assumed)
Duct Leakage to Outdoors
Duct Leakage to Outdoors (estimated)
Leakage/Conditioned Floor Area
39 CFM/1,000 sq ft at 25 Pa
3.9 CFM/100 sq ft at 25 Pa
Duct Leakage
Test Report
0.039 CFM/sq ft at 25 Pa
Building and Duct Details
113.7 CFM at 25 Pa
56.9 CFM at 25 Pa
Leakage Results
Cost of Duct Leakage
Leakage Data
Per the 2018 IECC: R403.3.4 Duct leakage
(prescriptive). The total leakage of the ducts,
where measured in accordance with Section
R403.3.3, shall be as follows:
1.) Postconstruction test: Total leakage shall
be less than or equal to 4 CFM per 100 SF of
conditioned floor area.
Maximum allowable:
4 CFM x 2,949/100 sq ft = 118 CFM at 25 Pa
* Total Duct Leakage - DOES NOT PASS
* Duct Leakage to Outdoors - If considered,
this project would pass at 113.7 cfm.