HomeMy WebLinkAboutDuct Leakage Test Report9/13/2024 Air Leakage Test Report In compliance with ASTM E-779-10 (2019) Building Address:186 Maroon Drive Glenwood Springs, Garfield CO USA Performed for: Performed by: Amanda Poindexter Test date:2024-09-12 Associated Test file: 186 Maroon Drive Report Number: Unique Property ID Number: Dexter Diagnostics 9/13/2024 Summary 186 Maroon Drive FanTestic version: 5.11.88 licensed to: Test date: 2024-09-12 By: Amanda Poindexter Customer: Building Lot Number: Building address: 186 Maroon Drive Glenwood Springs, Garfield CO USA Building and Test Information Test file name:186 Maroon Drive Building volume [cu ft]:39,683 Envelope Area [sq ft]:0 Floor Area [sq ft]:2,949 Building Height (from ground to top) [ft]:20 Results CFM at 50 Pa:1967.0 Leakage Area (EqLA) [sq in]:214.5 Leakage Area (EfLA) [sq in]:117.5 Air Changes per hour ACH50:2.97 Dexter Diagnostics Test Date: 2024-09-12 Client Tester Building Description Bailon Company Dexter Diagnostics Building Address 186 Maroon Drive Address 18 Crescent Pl Glenwood Springs, CO 81601 Glenwood Springs, CO 81601 Contact Luis Technician Amanda Poindexter Phone 970-355-5386 Phone 720-219-3683 Test Type Duct Leakage to Outdoors Gauge S/N 2070150 Fan series 200 Fan S/N LF2001000 Conditioned Floor Area 2949.0 sq ft Percentage of Duct Leakage to Outdoors 50% (estimated) Supply Return Average Duct Operating Pressure 25.0 Pa 25.0 Pa Leakage Split 50% 50% Leakage Penalty 100% 50% Depressurization Duct Pressure -25.0 Pa Fan Pressure 235.0 Pa Range Configuration Mid Duct Leakage 113.7 CFM Leakage Area 21.1 sq in Leakage constant, C 16.49 Leakage Exponent 0.60 (assumed) Duct Leakage to Outdoors Duct Leakage to Outdoors (estimated) Leakage/Conditioned Floor Area 39 CFM/1,000 sq ft at 25 Pa 3.9 CFM/100 sq ft at 25 Pa Duct Leakage Test Report 0.039 CFM/sq ft at 25 Pa Building and Duct Details 113.7 CFM at 25 Pa 56.9 CFM at 25 Pa Leakage Results Cost of Duct Leakage Leakage Data Per the 2018 IECC: R403.3.4 Duct leakage (prescriptive). The total leakage of the ducts, where measured in accordance with Section R403.3.3, shall be as follows: 1.) Postconstruction test: Total leakage shall be less than or equal to 4 CFM per 100 SF of conditioned floor area. Maximum allowable: 4 CFM x 2,949/100 sq ft = 118 CFM at 25 Pa * Total Duct Leakage - DOES NOT PASS * Duct Leakage to Outdoors - If considered, this project would pass at 113.7 cfm.