HomeMy WebLinkAboutEngineer's OWTS Design PlansI29 CAINS LANE CARBONDALE,CO 41623 970.309.5259 CARLA. OSTBERG@GMAIL.COM SIr:ll'X';{.: t]a)N$t-If,'I'IIs{.* March 19,2024 Project No. C1827 Omar Saucedo osltile@ live.com Subsurface lnvestigation and Onsite Wastewater Treatment System Design Shop 210 Gemat Circle Garfield County, Colorado Omar, CBO lnc. performed a subsurface investigation and completed an onsite wastewater treatment system (OWTS) design for the subject residence. The 2.859-acre property is located outside of Rifle, in an area where OWTSs are necessary. Slight changes were made to the site plan. Original design documents dated September 1 1,2023 should be discarded and replaced with these dated March 18,2024. Legal Description: Section: 11 Township: 6 Range: 93 Subdivision: BIG R COMMERCIAL PARK Lot: 8 2.87 ACRES Parcel lD: 2177-11 1-03-008 SITE CONDITIONS The property is currently undeveloped. A Shop for a commercial tile business is proposed. lt is anticipated the shop will have two toilets and sinks. The Shop may have up to 6 employees. The Shop will be served water from a private well, which will be located on the property" At the time of this design, the well had not been drilled. The well must be located greater than SO-feet from the proposed septic tank and greater than 1O0-feet from the proposed soil treatment area (STA). No water line should come within 1O-feet of the proposed septic tank and 2S-feet of the proposed STA. A drainage ditch along side the county road to the north will be at least 2S-feet from the proposed STA. The proposed soil treatment area (STA) location is relatively flat and sparsely vegetated with sage and native grasses. There should be no traffic or staging of material over the future STA site to avoid compaction of soils prior to construction of the STA. SUBSURFACE The subsurface was investigated on August 21,2023 by observing three test pits approximately 4-feet in depth. Unfortunately, the excavator dug the pits prior to us being on the property. These are consistent with the formerly required depth of percolation test pits. The materials encountered in Test Pits #1 ,#2, and #3 consisted of light brown sandy clay loam to a maximum depth explored of 4.O-feet. No bedrock or groundwater was encountered. Page2 A sample of the soil was taken from Test Pit #1 at 3-feet below grade. Soil structure grade was moderate. The soil formed a ball and a ribbon 1 to 2-inches in length before breaking. Soil structure shape was blocky and consistence was friable. Soil texture was more gritty than smooth. Test Pit #1 was further excavated to a maximum depth explored of SJeet on October 13, 2023. No groundwater or bedrock was encountered. We have researched soils in the area through USGS Web Soil Survey. The report is enclosed. The area of the proposed STA is identified by map unit symbol40. The map unit name is Kim Loam, with 3 to 6% slopes. The report notes depth to limiting layer or groundwater is greater than 80-inches (6.67-feet). We are familiar with soils in this area and based on our observations, are classifying soils as Soil Type 3, Clay Loam, with moderate structure grade. A long-term acceptance rate (LTAR) of 0.35 gallons per square foot will be used to design the STA. One additional soil profile test pit excavation (Test Pit) extending to 8-feet below grade must be excavated prior to installation of the STA. This office must be contacted to verify soils are consistent with soils described in this design. Test pits dug to approximately 4-feet in depth Sieved sample Page 3 Ribbon 1 to 2-inches in length Test Pit #1 excavated to 8-feet. Upper portion of sidewall was weathered. DESIGN SPECIFICATIONS Desiqn Calculations: Design Flow = 15 GPD x 6 employees = 90 GPD (upsizing to 150 GPD) LTAR = 0.35 GPD/SF 150 GPD / 0.35 GPD/SF = 429 SF x 1.2 (gravity, bed) x 0.7 (chambers) = 360 SF The OWTS design is based on wastewater flow from a toilet and sink in the proposed Shop for a commercial tile business an estimated maximum of 6 employees. An average daily wastewater flow of 150 GPD will be used. For the purposes of this OWTS design, Benchmark Elevation has been established as 100' (Finished Floor). CBO lnc. should be notified of any discrepancies or problems with grade elevations of proposed components during installation of the OWTS. OWTS Component Minimum Elevation Primary Tank lnlet lnvert Approximate horizontal distance 5' / min. 2o/o fall I min. 1 .25" lall lnfiltrative Surface Approximate horizontal distance 76' / min. 1o/o fall to STA / min. 9.5" fall Page 4 *Elevations are based upon standard OWTS installation practices. Component elevations may change during installation due to site conditions. Minimum grade refers to piping between components. The 4-inch Schedule 40 sewer line exiting the residence must have a double-sweep clean out and a minimum 2o/o grade to the septic tank. The system installation must include a 1000-gallon, two-compartment lnfiltrator@ poly septic tank with an Orenco@ Biotube effluent filter on the outlet tee. Risers must bring the manhole lids to grade for access. lf more than one riser is added to the septic tank, an extension handle must be installed on the effluent filter. A 4-inch diameter SDR-35 level manifold must be installed to connect each row of the chamber bed. The chamber bed will consist of 3 rows of 10 'Quick 4' lnfiltrator@ chambers for a total of 30 chambers and 360 square feet of infiltrative area. lnspection ports must be installed at each corner of the bed. Ports may be cut to grade and placed in sprinkler boxes for access. COMPONENT SPECIFICATIONS The component manufacturers are typical of applications used by contractors and engineers in this area. CBO lnc. must approve alternative components prior to installation of the OWTS. Requests must be submitted, in writing, to our office for approval prior to installation. Component technical data sheets are available upon request. Construction must be according to the jurisdiction's adopted On-Site Wastewater Treatment System Regulations, the OWTS Permit, and this design. PERMIT APPLICATION INSTRUCTIONS An OWTS Permit Application must be submitted to Garfield County Environmental Health Department. https://www.qarfield-countv.com/environmental-healthlfilesqcco/sitesi 16/OWTS-Application-Complete- PackeLQpc.-2O19.pd,f. lf the OWTS Permit Application will be submitted with a Building Permit Application, it should be submitted directly to Garfield County Building Department. All questions regarding permit submission can be directed to Garfield County Environmental Health Department, 970-945-661 4 x81 50. INSTALLATION CONTRACTOR CBO lnc. expects that the installer be experienced and qualified to perform the scope of work outlined in this design. The installer must review this design thoroughly and coordinate with our office in advance of COMPONENT MANUFACTURER MODEL NO.COMMENTS Septic Tank lnfiltrator@ rM-1060-2CP 1000-gallon,2- compartment poly septic tank Risers and Llds Orenco@ Double-walled rlsers and lrds Effluent Fllter Orenco@ 4" diameter full size tilter Chambers lnfiltrator@ Plus Standard 30'Quick 4' chambers Page 5 installation. Any additional conditions in this design or county permit must be completed and documented prior to final approval of the OWTS installation. Communication between the installer and this otfice is expected throughout the installation. INSTALLATION OBSERVATIONS CBO lnc. must view the OWTS during construction. The OWTS observation should be performed before backfill, after placement of OWTS components. Septic tanks, distribution devices, pumps, dosing siphons, and other plumbing, as applicable, must also be observed. CBO lnc. should be notified 48 hours in advance to observe the installation. ln an effort to improve the accuracy of the record drawing, we request that the installer provide a sketch of the installation, including path of the sewer lines, water line installation (if applicable), septic tank location, STA location, and measurements from building corners or another fixed objects on the property. This sketch is most easily provided on Sheet W2.0 of the OWTS Design Packet. Photographs of the installation and final cover are also requested to supplement our installation documentation. REVEGETATION REQUIREMENTS An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing characteristics (but without taproots), provides a maximum transpiration rate, and competes well with successional species. No trees or shrubs, or any vegetation requiring regular irrigation shall be placed over the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation cover. OPERATION INFORMATION AND MAINTENANCE The property owner shall be responsible for the operation and maintenance of each OWTS servicing the property. The property owner is responsible for maintaining service contracts for manufactured units, alternating STAs, and any other components needing maintenance. Geo-fabrics or plastics should not be used over the STA. No heavy equipment, machinery, or materials should be placed on the backfilled STA. Machines with tracks (not wheels) should be used during construction of the STA for better weight distribution. Livestock should not graze on the STA. Plumbing fixtures should be checked to ensure that no additionalwater is being discharged to OWTS. For example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA. lf an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned annually, or as needed. lf the OWTS consists of a pressurized pump system, we recommend the laterals be flushed annually, or as needed. The homeowner should pump the septic tank every two years, or as needed gauged by measurement of solids in the tank. Garbage disposal use should be minimized, and non-biodegradable materials should not be placed into the OWTS. Grease should not be placed in household drains. Loading from a water softener should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS. Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste only. Page 6 ADDITIONAL CONSTRUCTION NOTES lf design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of freezing. The pump shall have an audible and visual alarm notification in the event of excessively high- water conditions and shall be connected to a control breaker separate from the high-water alarm breaker and from any other control system circuits. The pump system shall have a switch so the pump can be manually operated. Excavation equipment must not drive in the excavation of the STA due to the potential to compact soil. Extensions should be placed on all septic tank components to allow access to them from existing grade. Backfill over the STA must be uniform and granular with no material greater than minus 3-inch. LIMITS: The design is based on information submitted. lf soil conditions encountered are different from conditions described in report, CBO lnc. should be notified. All OWTS construction must be according to the county regulations. Requirements not specified in this report must follow applicable county regulations. The contractor should have documented and demonstrated knowledge of the requirements and regulations of the county in which they are working. Licensing of Systems Contractors may be required by county regulation. Please call with questions. Sincerely, CBO lnc. {b"n{*- {"}YtbuY K.CRONfI{P.0. Ba;; rJtr C{}.3r g7tt. z5a. ui7 z / Aar,lrayJir.rrorlk(aorttlr;o&.c'r:rrl Revie ved By: Kachayla R. Crork. P.E. Csl*r'nd* License N*. $144ff ? Carla Ostberg, MPH, REHS DRAWINGS BE USED IN coNJUNcloN WtrH oesteru LETTER DATED Wn9I2O24 CBO lnc. 129 Cains Lane Carbondale, ColoEdo 81623 Phone 970.309.5259 carla.ostberg@gmail.com m tu ltuwtdM.45623) SHOP Countg + L TP No.221 Beddns S a9'01'49" E 653. 1 Z' STA 50'UTILITY Lda L t 2.o efu ond Ddry tutued R@ No. 736sss \ X Golorado Precision Tile 210 Gemat Circle Garfield County, Colorado ProjectNumber: C1827 x 09t11t2023 03t19t24 D6igned by: CBO Rsiiewed by: KC Drawn by: DD w1 .0 Sheet 1 0F 4 N t,-----HH.,11 lsfu SCALE: 1 = 50'=0" __J*--1 LINE T*** Io.0'eW %detuWaNo. lwlt THE LOCATION OF PROPOSED IMPROVEMETITS SHOWN ARE NOT THE RESULT OF A PROPERTY SURVEY. THE LOCATIONS ARE APPROXIMATE. IT IS THE HOMEOWNERS' DUTY TO ENSURE ALL CONSTRUCTION AND IMPROVEMENT LOCATIONS ARE ACCURATE. PROPERry LINES AND SETBACK DISTANCES SHOULD BE CONFIRMED PRIOR TO EXCAVATION, SCALED FOR PRINTING ON 1 1" X 1T PAPER. t 1/a'6anse Phsttu@gdtwd P@P @RIF,R A SITE PLAN CALL811 FOR UTILITY LOCATES CBO lnc. 129 Cains Lane Carbondale, Colorado 81623 Phone 970.309.5259 carla.ostberg@gmail.@m ']\DRAINAGE Ditch otO CountA RoPROPERTY (North9"o I '49 W 652 8 7'line of Big R Commercial Subdiuision) oo 1j2MtN. 72', Proposed Building A) LINE TO STA MANIFOLD No. 2 PoIe & Ouerhead Electic to TP3 62.1', + + Golorado Precision Tile 210 Gemat Circle Garfield County, Colorado Project Number: C1827 Dab: 091112023 Revised: 03/1 9/24 Designed by: CBO Reviewed by: KC Drawn by: DD WELL of Sheet 2 0F 4 w2.0 4' DIA SDR-35 SEWER PIPE WITH DOUBLE SWEEP CLEANOUT MIN 2% FALL TO TANK 145.o', SEPTIC TANK WITH EFFLUENT SCREEN OOO-GALLON, TWO.COMPARTMENT 25'4" DIA SDR.35 PVCBasis of Bearing S 89.01,49,,8 6 17' 50'UTILITY 4" DIA SDR-35 (MtN. 1% FALL TO --*_::*.-42.8e.g MtN. 10' 4" DIA SDR.35 INSPECTION PORT AT EACH CORNER OF BED 'OUICK.4' CHAMBER BED. 3 ROWS OF 1 CHAI\4BERS = 30 CHAMBERS = 360 SF Lot B 210 Gemat Court 2.866 t Acres N L scALE: 1" = 2o'P.O' Utititg and. Drainage Easement Reception No. 736g55 '49',E 545.57' Found#S Rebar and. L 1/ 4.:' _QreW e_.Pfa*tjp C apg+-.--^s ,DD^D -nDnraD CALL811 FOR UTILITY LOCATES..T..\\ rtrrllrlrr CBO lnc. 129 Cains Lane Carbondale, Colorado 81623 Phone 970.309.5259 carla.ostberg@gmail.com DIA SDR-35 SEWER LINE TO EACH ROW (t\,,flN.1% SLOPE) SLIP.ON PVC END PUTE INFILTRATOR CHAMBERS (4 x 3')DO NOT GLUE 4" DtA SDR-35 EFFLUENT PIPE (MlN.1% FAL FROM SEPTIC TANK) INSULATED TMCERWRE FINISHED GRADE 4'DIA SEWER LINE 4'DIA 1O CHAMBERS PER ROW 4' DIA SDR-35 INSPECTION PORT AT EACH CORNER OF STAPVC LEVEL MANIFOLD PLACED IN TOP PORT OF CHAMBER END PLATES TO TANK ACLEANOUT DETAILS\<-ffi 'ACHAMBER BED PLANU-ffi 4" SDR 35 SMALL VALVE COVER BOX OR IRRIGATION VALVE BOX AT GRADEINSPECTION PORT AT EACH CORNER OF STA INFILTRATOR(R) ourcK4(TM) cHAr\,4BERS, 3'X4'CF OR T}IREADED CLEANOUT ASSEi,BLY COMPACT BASE TO SUPPORT BOX PVC PIPE CUTTO FIT 4' USE HOLE SAWTO CUT THRU TOP OF END SURFACE EXTENT OF EXCAVATION /A INSPECIION PORT lN CHAI,IBER\9r-T- /^CIIAMBER BED SECTION\91-.rr@ BACKFILL MUST BE MINUS 3INCH MATERIAL 2' Golorado Precision Tile 210 Gemat Circle Garfield County, Colorado ProjectNumber: C1827 bale: O911112O23 hevised: 03/19/24 lDesigned by: CBO IReviewed by: KC lDrarn bV: DD w3.0 Sheet 3 0F 4 CBO lnc. 129 Cains Lane Carbondale, Colorado 81623 Phone 970.309.5259 carla.ostberg@gmail.com DESIGN sHoP (POSSIBLE 6 EMPLOYEES) 6 EMPLOYEES x 15 GPD = 90 GPD ESTIMATED WASTEWATER FLOW = 150 GPD STA TO WATER COURSE 50'N/A STA TO WELL 100'NOT DRILLED YET STA TO SHOP 10'14', SEPTIC TANK TO WATER COURSE 50'N/A SEPTIC TANK TO WELL 50'NOT DRLLED YET SHOP TO SEPTIC TANK 5' OWTS COMPONENTS AND PHYSICAL FEATTJRES MINIMUM REQUIRED SFTBACK APPROXIMATE PROPOSED SETBACK TANK; MIN. IOOO GALLONS USE lOOO-GALLON, TWO.COIVPARTMENT SEPTIC TANK SOIL TREATMENT AREA (STA): LONG TERM ACCEPTANCE RATE (LTAR) = 0.35 GAU SF CALCULATED STA = CyLTAR = 150 / 0.35 = 429 SF GRAVlry, BED = 429 SF X 1.2 = 514 SF CHAMBERS - 514 SF X 0.7 = 360 SF / 12 SF / CHAMBER = 30 CHAMBERS THREE ROWS OF IO 'OUICK 4' CHAMBERS TOTAL 30'OUICK 4' CHAMBERS ASETBACK CHART\rr-irs SOIL PROFILE TEST PIT NO. 1 SOIL PROFILE TEST PIT NO. 2 SOIL PROFILE TEST PIT NO. 3 0 1 2 LIGHT BROWN SANDY CLAY LOAM LIGHT BROWN SANDY CLAY LOAM LIGHT BROWN SANDY CLAY LOAM 3 4 FINISHED GMDE MEDIUM BROWN SANDY CLAY LOAM EXCAVATED 1U132023 24',MtN. 6 EElq f,l sandy clay IOam AN ADDITIONAL TEST PIT MUST BE EXCAVATED PRIOR TO INSTALLATION OF THE STA7 4" DIA SDR-35 SEWER LINE (MtN 2olo SLOPE TO TANK, MrN. 1% TO STA) SCREENED OR SAND FOR BEDDING 3" MlN. 10 8" MtN. ASOILS LOG\t-Effi AIRENCH DETAIL\9r................_nrs Colorado Precision Tile 210 Gemat Circle Garfi eld County, Colorado ProjectNumber: C1827 loau: ogt'ntzozz I Revised: 03/1 9/24 I Designed by: CBo I Reviewed by: Kc lDrawn bv: DD w4.0 Sheet 4 0F 4 Map Unit Description: Kim loam, 3 to 6 percent slopes--Rifle Area, Colorado, Parts of Garfield and Mesa Counties Rifle Arean Golorado, Parts of Garfield and Mesa Counties 40-Kim loam, 3 to 6 percent slopes Map Unit Setting National map unit symbol: jny7 Elevation: 5,000 to 6,000 feet Farmland classification: Prime farmland if irrigated Map Unit Composition Kim and smilarso/s;85 percent Esfimafes are based on obseruations, descriptions, and fransecfs of the mapunit. Description of Kim Setting Landform : Alluvial fans, benches Down-slope shape: Linear, convex Across-s/ope shape: Linear, convex Parent material: Alluvium derived from sandstone and shale Typical profile Hl - 0 to 17 inches: loam H2 - 17 to 60 inches: loam Properties and qualities S/ope:3to6percent Depth to restrictive feature: More than 80 inches Drainage c/ass: Well drained Runoff class: Low Capacity of the most limiting layer to transmit water (Ksat):Moderately high to high (0.60 to 6.00 in/hr) Depth to water table: More than 80 inches Frequency of f/oodrng: None F reque ncy of pondtng: None Calciu m carbonate, maxi m um content: 1 5 percent Available water supply, 0 to 60 inches: High (about 9.6 inches) lnterpretive groups Land capability classification (irrigated): 3e Land capability classification (nonirrigated): 3c Hydrologic Soil Group: A Ecologicalsrte: R048AY306UT - Upland Loam (\Afoming Big Sagebrush) LSbA5 Natural Resources Conservation Service Web Soil Survey National Cooperative Soil Survey 9t25t2023 Page 1 of2 Map Unit Description: Kim loam, 3 to 6 percent slopes--Rifle Area, Colorado, Parls of GameH and Mesa Counties Hydric soi/ ratlng,' No Data Source lnformation Soil Survey Area: Rifle Area, Colorado, Parts of Garfield and Mesa Counties Survey Area Data: Version 15, Sep 6,2022 SDA - Natural Resources Consgruation Seruice Web Soil Survey National Cooperative Soil Survey 9t2512023 Page 2 ot 2 =ii $ A Soil Map-Rifle Area, Colorado, Parts of Garfield and Mesa Counties MW 28t560 54580 HW B R 390 32'40'N 390 32'35'N 264/m Hffi H\n i64440 M M M &5n Map Scale: 1:1,020 if printed on A landscape (11' x 8.5') *reel_ ,Meters0153060s 0 45 S 180 270 Mapprojection: Weblulercator Comeraoodinates:WGS84 Edgetics:UTMbnel3NWGS&I I $ 390 32',40'N 390 32'35'N E g LI I s R a H a H a H aa H 2f/640 =eh $ = \N A Natural Resources Conservation Service Web Soil Survey National Cooperative Soil Survey 9125t2023 Page I of3 L$NAffi 264560 264580 2646m M Natural Resources Gonservation Service Soil Map-Rifle Area, Colorado, Parts of Garfield and Mesa Counties Web Soil Survey National Cooperative Soil Survey 912512023 Page 2 of 3 MAP LEGEND MAP INFORMATION The soil surveys that comprise your AOI were mapped at 1:24,O00. Warning: Soil Map may not be valid at this scale. Enlargement of maps beyond the scale of mapping can cause misunderstanding of the detail of mapping and accuracy of soil line placement. The maps do not show the small areas of contrasting soils that could have been shown at a more detailed scale. Please rely on the bar scale on each map sheet for map measurements. Source of Map: Natural Resources Conservation Service Web Soil Survey URL: Coordinate System: Web Mercator (EPSG:3857) Maps from the Web Soil Survey are based on the Web Mercator projection, which preserves direction and shape but distorts distance and area. A projection that preserves area, such as the Albers equal-area conic projection, should be used if more accurate calculations of distance or area are required. This product is generated from the USDA-NRCS certified data as of the version date(s) listed below. Soil Survey Area: Rifle Area, Colorado, Parts of Garfield and Mesa Counties SurveyArea Data: Version 15, Sep 6,2022 Soil map units are labeled (as space allo\Ms) for map scales 1:50,000 or larger. Date(s) aerial images were photographed: Aug 25, 2021-Sep 5,2021 The orthophoto or other base map on which the soil lines were compiled and digitized probably differs from the background imagery displayed on these maps. As a result, some minor shifting of map unit boundaries may be evident. Area of Interest (AOl) Area of lnterest (AOl) Soils Soil Map Unit Polygons ffi Spoil Area S Stony Spot ffi Very Stony Spot ff Wet Spot {I Other .r Special Line Features Water Featurea Streams and Canals Transportation +-t l Rails ,F,ut lnterstate Highways $qs*, US Routes , Major Roads Local Roads Background t Aerial Photography ed Soil Map Unit Lines E Soil Map Unit Points Special Point Features til Blowout HN Bonow Pil W Clay Spot * Closed Depression X Gravel Pit & Gravelly Spot S Landfill fr, Lava Flow dl& Marsh or swamp R Mine or Quarry dp Miscellaneous Water & Perennial Water \P Rock Outcrop + Saline Spot ;.; Sandy Spot sF Severely Eroded Spot S Sinkhole S, Slide or Slip @ SodicSpot USDA7 Soil Map-Rifle Area, Colorado, Parts of Garfield and Mesa Counties Map Unit Legend 4.5 100.0%40 Kim loam, 3 to 6 percent slopes 4.8 100.0%Totals for Area of lntercst TISBAn Gonselatlon Service Natural Resources Web Soil Survey National Cooperative Soil Survey 9t2512023 Page 3 of 3 msl E LO R* D fr"5 $ugpqrt srstelas Map Viewer I ntvn r Well Constructed r Final Permit [J County Legend r 4ql* $lr I rJt $ Location Notes 585 O 292 585 Feet 1: 3,508 0 This product is for informational purposes and may not have been prcpared for, or be suitable tor legal, engineeing, or suryeying pufposes. Use/s of tts information should review or consult the pimary data and information sources to asceftain the usability of the information. Date Prepared: 911112023 2:51:11 PM GlqRrblic-net'* Garfield County, CO 2019 Total Actual Value Overview Legend I Parcels Roads Parcel/Account Numbers Owner Name i'll Lakes&Rivers * CountyBoundary Line $t25,02O Last 2 Sales Date Price to/26/2022 $24s,000 3/26/202t $170,000 Account R044528 Physical 21OGEMATCT Number Address ParcelNumber 2t777tLO3OOg RIFLE Acres 3 Owner Address COLORADO PRECISION LandSqFt 0 TILE TaxArea O2t 1339ORCHARDAVENUE 2019Mill Levy 66.3370 S|LTCO81652 Date created: 9 / 7I/2Q23 Last Data Uploaded: 9 / fU2O23 2:O7:22 AM Deve'oped "(:l FrFmdxr 81650 9111123, 1:57 PM Garfield County, CO Account R044528 Parcel 2777TI7O3WB Prop€rtyAddress 2lOGEMAT CT, RIFLE, CO 81650 Legal Description Section: ll Tomship: 6 Range: 93 Subdivision: BIG R COMMERCIAL PARK Lot 8 2.87 ACRESAcres 2.869 LandSqFt 0TaxArea 2L Milltevy 663370 Subdivision BIG R COMMERCIAL PARK ViewMap Owner qPublic.net - Garfield County, CO - Property Record Card: R044528 2023 $r25,O2O.OO $o.oo 5ummary COLORADO PRECISION TILE 1339 ORCHARDAVENUE stLTco 81652 Land UnitType VACANT COM LOTS - 0200 (VACANT LAND) SquareFeet 0 Actual Values Assessed Year Land Actual Imp-r.gveTent Actyll Total Actual Assessed Values Assessed Year Land Assessed lmprovement Assessed TotalAsssed Tax History ThxYear Taxes Billed gfiskleffijs-yj€$,r th€.taxi$l-o..r$!3.tian fer t!!g p:rqel en !fte Garfield CgHfy*lrgegffCtt}rsbslle. Transfers Sale Date 70126t20?2 2022 $2Ao5.36 $125,020.00 2023 $o.oo $34,880.q) 2021 $2,707.96 2022 $125,020.00 $o.oo $125,020.00 2022 $34260"00 $o.oo $36,260.m 2020 $2,467.M 2021 $125,020.00 $o.oo $125,020.00 2027 $36260.00 ReeDtion Number Bmk- Pagc $o.oo $36,260.00 NE $2,3re.12 --,-,--selg f"r9s $245,000 $o gnn?96 to/26/2022 980725 70/24/2022 STATEMENTOF AUTHORITY 998667 SPECIALWARRANTY DEED STATEMENTOF AUTHORITY https://qpublic.schneidecorp.com/Application.aspx?ApplD=1038&LayerlD=22381&PageTypelD=4&PagelD=9447&Q=924715955&KeyValue=R04452ffi $0 '12 9111123,1:57 PM Sale Date Deed Typ€ 9t30/2022 STATEMENTOFAUTHORIry 3/26/2027 SPECIAL WARRANTY DEED 3t26/2027 STATEMENT OFAUTHORITY 5t7U2020 DECLARATION 3/t9/2018 DECLAMTION 4/30/20ro WARRANWDEED LU70t2008 GRANT DEED ru5/2007 QUITCLAIM DEED t2ts/2007 WARRANTYDEED 7U3/2007 STATEMENTOFAUTHORIry 7U29/2007 STATEMENTOF AUTHORITY tu2at2007 POWEROFATTORNEY 77n/2007 DECLARATION Ltn/2007 AGREEMENT 70/tot2w7 ASSIGNMENT 70/70/2007 GRANT DEED 4/rtl2005 QUITCLAIM DEED 7U20/2004 RESOLUTION 12/t6t2004 RESOLUTION 7U76/2@4 SPECIALWARRANW DEED 7U76/2004 STATEMENT OF AUTHORIW 6/4/2004 QUITCLAIM DEED 9/24!999 QUITCL,AIM DEED 4/79/7996 WARRANTYDEED 4/70/r996 AGREEMENT 6t27/7995 BOUNDARY LINE ADJUSTMENT 6/23t7995 WARRANTYDEED 7/4/7995 AFFIDAVIT 7/4/7995 BOUNDARY LINE ADJUSTMENT 10/78/7993 RESOLUTION Property Related Public Documents {li{h bere tnviqry Proscrlyi*slcszulis-pffcficng No data availablefor thefolloving modules: Buildings, Photos, Sketches. qPublic.net - Garfield County, CO - Property Record Card: R044528 Reception Number Book- PaBe ?80s56 ,JJAI{ ?04$6S 7Cq431 73n617 73$816 I SSdtS 73S&14 738815 736857 736S5* 736861 736858 665764 721L84. Sale Price $o $170,000 $o $o $o $o $o $o $1,374,000 $o $o $o $o $0 $o $o $o $o $o $o $o $2ss,000 $20.000 $o $o $o $o $o $o 552673 L67a-135 165G110 1975-539 1650-L40 1550-139 7594-593 7752-55 o97+0797 o974-O795 0946-0319 0946-0324 0927-0724 0927-O774 0878-0964 _ _*xffi 4?r.835 4S0433 480434 47S*:t6 aTan\1L 453813 $o . i : :: -i:1s++r,r i :. '.r,ri l$ ir, .' -:ri++11 I Uier Fliye,p.v Pslicy i fi*F3ffly*sx.l*9*isc -L"n"sl"*Eta"Unlp"ad;_?J3"Xi"?8?fi *12,0?;??..&M, S*r*lnp** ilv f*Xsi'm$g https://qpublic.schneidercorp.com/Application.aspx?ApplD=1038&LayerlD=22381&PageTypelD=4&PagelD=9447&Q=924715955&KeyValue=R044528#2t2 Item #rt {o6&2cP {060 Gallan Turo Gompartment lnffltratol@ Poty Tank IT'Top View TANKTOP HALF CONTINUOUS GASKET 6rut TANK INTERIOR SEAM CLIP (e4) ALIGNMENT DOVITEL (34) TANK BOTTOM HALF Mid-Height Seam Section 24'AOCESSOPENlltlG\Section View Tank lndude llds 9.7' I 1T 41 OUTLET 127. o Compliont with CSA ond IAPMO Stondordso PVC risers ovoilobler Secondory sofety screen ovoiloble with PVC riser o Moximum buriol depth is 48" r Minumum buriol depth is 6"o Tonk is not roted for vehiculor troffic loodingr Exterior of monhole cover includes the following worning: "DANGER DO NOT ENTER: POISON GASES'' 9.7 EXTERIOR HEIGHT SEAM CLIP (rYPrcAr) LIFTING STRAP (TYPTCAT_) End View ffir,rr5il*n. ri,nArorSttlE/srG. I 1 f' Bulthd Digging Specs lnvert Dimensions Net Copocity Weight 12' Long x 7' Wide lnlet 47" 0utlet 44" Length 127" width 62.2" Height 54.7"1094 gol 320 lbs wffl Werbutr r$ysHre r hducile InG. r $onde cr{orsrytr{ ffipetr ru ft,Eg) ags.srgf R'alftb'cG8{ai tebdb: wruv.vdepnd,un End:wffi, Residential Biotube' Effluent Filters Applications Our patented* 4-in. (100-mm) Biotube Effluent Filters, Biotube Jr., Biotube Insert Filters, and Biotube Base Inlet Filters are ideal for residential septic tanks and have a lifetime warranty. They prevent large solids from leaving the tank, dramatically improving wastewater quality and extending the life of residential drainfields. 4-in. (100-mm) Biotube Effluent Filter 4-in. (1 00-mm) Biotube Jr. (4-in. Biotube cartridge auail- able separately as Insert Filter) 8-in. (200-rnm) Base Inlet Filter 4-in. (100-mm) Insert Fiher Orencols superior efluent fihers resist chging bener than all other brandl Our stan- dard, full+ized 4-in. (100-mm) Biotube Effluent Fiher prouides *a*i*um hng-tern protection in a complete package, uith housing. Our 4-in. (100-mm) BiotubeJx, at half the size of our standard mod.el, has more f.bering capacity than the full-sizedfhers sold by other manu.facturers. For tanks with existing outlet tees, the Biotube Insert Fiher is idcal. And for hw-profle tanhs, therels the Base Inlet Fiher. * Covered by patent numbers 5,492,635 and 4,439,323 To 0rder Call your nearest Orenco Systems@, Inc. distributor. For nearest distribu- tor, call Orenco at 800-348-9843 or go to wwworenco.com and click on "Distributor Locator. " APS-Fr-r Rev.3.4 @ 11/10 0renco Systems@. lnc. Standard Features & Benefits . Has 5-10times more flow area than other brands, so lasts many times longer between clean- ings, increasing homeowner satisfa cti o n . lnstalls in min- utes inside new or existing tanks; extendible tee handle for easy removal . Easyto clean by simply hosing off whenever the tank needs pumping . Removes about two-thirds of sus- pended solids, on average, extending drainfield life . Corrosion-proof construction, to ensure long life . Lifetime warranty 0ptional Features & Benefits Biotube Filtering Process . Alarm available, to signal the need for cleaning . FIow modulating discharge orifices available to limit flow rate leaving tank, mitigat- ing surges and increasing retention time . Custom and commercial sizes availa ble Effluent from the relatively clear zone of the septic tank, between the scum and sludge layers, horizontally enters the Biotube Effluent Filter. Effluent then enters the annular space between the housing and the Biotubes, utilizing the Biotubes'entire surface for filtering. Pa rlicles la rg e r th a n the Biotube's mesh are prevented from leaving the tank. rT\*-,. **rf!r** € Orenco$y*tem** fncorpcrsted {Jaarying tfu Way t*t Wa vtd I)o N W*teu, * t ero" wr/*ritr,of en co.cotlt Nomenclatures 4-in. Biotube Fiher (standard) FTn!04!!-nlf 4-in. Biotube Effluent Filter Extendible PVC handle Stainless steel set screws Top seal plate Air Biotube@ filter cartridge Solid base Filter housing 4-in. Biotube Jr. Tank wall -T_ I 0ptions: Blank = no optionsM = flow modulation plate installedA = float bracket attached Cartridge heightr 28" and 36" are standard Housing height: 36" and 44" are standard Filter diameter (inches) W = 'fits Type 3034 outlet pipe S = fits Schedule 40 outlet pipe Blank = 1/S" filtationP = '1116" filtration Biotube effluent filter series 8-in. Biotube Filter tbase intet model) FTJ 08 zz-14 Bf_-l---r-- I 0ptions:A = float bracket FS = 2" outlet orifice FSo = 2"outletorificeandoverfl0wplate. Base inlet model Cartridge height: 1 4" standard Housing height: 22" standard Filter diameter (inches) Riser wall 08 =8" Blank = 1/8" filtrationP = 1/16" filtration Biotube effluent filter series - Als0 available with coupling and sleeve as a "kil": FI-0VERFLOWKIT 4-in. Biotub€ JL (includes cartridge and housins) FTJ 04 18 0ptions: Blank = no optionsM = flow modulation plate installedA = lloat bracket attached Cartridge height (inches) Filter diameter (inches) fils Type 3034 outlet tee fits Schedule 40 oullet tee D_ Junior series 1/S" filtration 1/16" filtration Biotube effluent iilter series e_ Blank 4-in. Biotube Filter Insert (carnidse only) FTi 0418- W= fitsg = fits For customized options (e.9., NC indicates North Car0lina regions) Type 3034 outlet tee Schodule 40 outlet tee Carridge height (inches) Filter diameter (inches) Blank = 1/S" fillrationP = .l/16" fiftralion lnsert Biotube effluent {ilter series Distributed By: Double Walled PVG Riser & Lid Options Poly Lid (Stafic load tesbd b 5fi10 lbs). Skid leistance surhoe. Available in grcen. Highest level of UV Probction induded. lncludes a fuam gasketbrairlightand wabrtight applicatons. lncludes squarc drive scflutts b discoumge unauthorized eilfy. lnsulation panels achieve R-10 insulation nating 2'of lnsulaton Standad Orenco @ DuraFibern Access Lids (FLD) Not recommended br vehicular ffic 24'and 30'Diamebns. Solid, reein-infused fibeplass oonsfirclion. 20,00G1b breaking sfisngilr. Standad gr€en or broum oolors. Available with or without urerhane lid gasket. Available with carbon filfralion. 4 shinless sbel f,athead socket cap scrorys & ho< key wrcncfi. lnsulabd lids available -t or { Double Walled PVC Riser . Available ln24'' and 30'Diamebr. Cut to lengfrr. Sold in +l-2'incnmenb. Must be cut betrcen dbe w Mlrne.r$erutce {t{9} tou*rru4 ztrF&' ru'g',!? P.O,Eo(% Fu: fils) 3g$g72? B'ffilftb's$al $trbrtb: *rw.ilepmd.cn F,nt: Wfirt Werhrehr .q&Ht8 r Pmducfr IN FILTRATGR- wet#r l#*fuft{}I*#i*e ruu!^r*#,#-""'' The Ouick4'Plus Standard Chamber The Quick4 Plus Standard Chamber offers maximum strength through its two center structural columns. This chamber can be installed in a 36-inch-wide trench. Like the original line of Quick4 chambers, it offers advanced contouring capability with its Contour Swivel Connection" which permits turns up to 1S-degrees, right or left. It is also available in four-foot lengths to provide optimal installation flexibility The Quick4 Plus All-in-One 12 Endcap, and the Quick4 Periscope are available with this chamber, providing increased f lexibility in system configurations. Maximum Strength Quick4 Plus''Series Ouick4 Plus Standard Chamber Benefits: " Two center structural columns offer increased stability and superior strength . Advanced contouring connections . Latching mechanism allows for quick installation . Four-foot chamber lengths are easy to handle and install . Supports wheel loads of 16,000 lbs/axle with '12" of cover Ouick4 Plus All-in-0ne 12 Endcap Benefits: . May be used at the end of chamber row for an inleVoutlet or can be installed midtrench . Midtrench connection feature allows construction of chamber rows with center feed, as an alternative to inletting at the ends of chamber rows . Center-feed connection allows for easy installation of serial distribution systems . Pipe connection options include sides, ends or top Quick4 Plus All-in-0ne Periscope Benefits: . Allows for raised invert installations . 180" directional inletting . 12" raised invert is ideal for serial applications Certified by the lnternational Association of Plumbing and Mechanical Officials (IAPMO) Size 34"Wx53"Lx12"H (864 mm x 1346 mm x 305 mm) Effective Length 48" (1219 mm) Louver Height 8" (203 mm) Storage Capacity 47 sat (178 L) lnvert Height 0.6" (15 mm),5.3" (135 mm), 8.0" (203 mm),12.7" (323 mm) Ouick4 Plus Standard Gharn$er Specilications APPROVED in ffi Ouick4 Plus" Series fl6_{,,p,5!-t""'! Ouick4 Plus Standard Ghamber 12" 34 48', EFFECTIVE LENGTH Ouick4 Plus All-in-One 12 Endcap PRESSURIZED PIPE DRILL POINTS LOCATIONS (2 PLACES) FRONT VIEW 18' 8" INVERT SIDE VIEW INFILTRATOR WATER TECHNOLOGIES STANDARD LIMITED WARRANTY (a) The structural integrity of each chamber, endcap and other accessory manufactured by lnfiltrator ("Units"), when installed and operated in a leachfield of an onsite septic system in accordance with lnfitlraior's instructions, is wananted io the original purchaser ("Holde/') against defective materials and workmanship for one year from the date that the septic permit is issued for the septic system containing the Uniis; provided, however, that if a septic permit is not required by applicable law, the wananty period will begin upon the date that installation of the septic system commences. To exercise its wananty rights, Holder must notify lnfiltrator in writing at its Corporate Headquarters in Old Saybrook, Connecticut within fifteen (15) days of the alleged defect. lnfiltrator will supply replacement Units for Units determined by lnfiltrator to be covered by this Limited Warranty. lnfiltrator's liability specifically excludes the cost of removal and/or installation of the Units. (b) THE LIMITED WARHANTY AND REMEDIES lN SUBPARAGRAPH (a) ARE EXCLUSIVE. THERE ARE NO OTHER WARBANTIES WTH RESPECT TO THE UNITS, INCLUDING NO IMPLIED WARRANTIES OF MEHCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE (c) This Umited Wa(anty shall be void if any part of the chamber system is manufactured by anyone other than lnfilkator. The Limited Wananty does not extend to incidental, consequential, special or indirect damages. lnfiltrator shall not be liable for penalties or liquidated damages, including loss of production and proflts, labor and materials, overhead costs, or olher losses or expenses incurred by the Holder or any third party. Specifically excluded from Limited Warranty coverage are damage to the Units due to ordinary wear and tear, alteration, accident, misuse, abuse or neglect of the Units; the Units being subjected to vehicle traffic or other conditions which are not permitted bythe installation instructions; failureto maintain the minimum ground covers set forth in the installation instructions; the placement of improper materials into the system containing the Units; failure of the Units or ihe septic system due to improper siting or improper sizing, excessive water usage, improper grease disposal, or improper operation; or any other event not caused by lnfiltrator. This Limited Waranty shall be void if the Holder fails to comply with all of the terms set forth in this Limited Wananty. Furlher, in no event shall lnfiltrator be responsible for any loss or damage to the Holder, the Units, or any third party resulting from installation or shipment, or from any product liability claims of Holder or any third party. For this Limited Wananty to apply, the Units must be installed in accordance with all site conditions required by state and local codes; all other applicable laws; and lnfiltrator's installation instructions. (d) No representative of lnfiltrator has the authority to change or extend this Umited Wananty. No wananty applies to any pady other than the original Holder. The above represents the Standard Umited Wananty offered by lnfiltrator. A limited number of states and counties have different waranty requirements. Any purchaser of Units should contact lnfiltrator's Corporate Headquarters in Old Saybrook, Connecticut, priorto such purchase, to obtain a copy of the applicable warranty, and should carefully read that wananty prior to the purchase of Unib. Quick4 Plus All-in-One Periscope OUICK4 PLUS ALL-IN-ONE PEBISCOPE {360" SWTVEL) 12.7" INVEBT ls'l I I N F! !-TRATOR' arelter te*frrt*!q}gi** 4 Business Park Road P.O. Box 768 Old Saybrook, CT 06475 860-577-7000 . Fd 860-577-7001 1-800-221-4436 www,i ntiltratorwater.com PotyLok is a trademark oI PolyLok, lnc. TUF-TITE is a reglstered trademark of TUF-TITE, lNC. Ultra-Rib is a trademark of IPEX lnc. @ 2013 lnfiltrator WaterTechnologies, LLC. All rights reserved. Printed in U.S.A. PLUSos 0713 i ti Contast lnfiltrator Water Technologies'Technical Seruiees Depaftment for assistance at 1-8ffi-221-4436