Loading...
HomeMy WebLinkAboutBlower Door TestDexter Diagnostics 18 Crescent Pl, Glenwood Springs, CO 81601 720-219-3683 dexterdiagnostics@gmail.com Page 1 of 1 Blower Door Test Verification Form Builder / Developer: Modfin Design Build shaggs09@yahoo.com 970-948-3101 Site Address: 479 Spring Ridge Rd. Blower Door Testing Results: CFM50: 628 Fan PA: -50.1 Flow Ring: B4 Air Leakage Rate: 1.23 ACH50 Type of ventilation used to meet the code requirement: The only continuous ventilation is in the crawlspace; it is an exhaust fan. It is recommended that a BALANCED ventilation system is utilized (because there is an open vent water heater and you do not want to backdraft i). A balanced system can be achieved by utilizing an ERV or (because the house is finished) adding a vent with a damper to the exterior and this is tied to the furnace’s return. 60 cfm is required per M1507 of the IRC. Passes 2018 IECC Requirement? YES 2018 IECC Requirements: R402.4.1.2 Testing – The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding three air changes per hour in Climate Zones 3 through 8. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Signed, _____________________________________________________________________ Amanda Poindexter Date RESNET HERS Rater #3774492 9/26/24