Loading...
HomeMy WebLinkAboutState Rough-in Electrical Inspection ReportCOLORADO STATE ELEGTRICAL BOARD INSPECTION REPORT / CORRECTION NOTICE Date Receiv ed: 22- AUG-24 Permit Number: 1008557 Gontractor/HomeOwner: Address: Tlpe of lnspection: Action: lnspectors Name: Patrick Proctor Phone Number: 303-894-2429 Pinnacle Electric Limited 1021t HwY 82 Rough In Partial Date:23-AUG-24 Comments or Gorrections: Photos of the corrections can be sent to patrick.proctor@state.co.us Please make sure lnajlhe permit number shows within the photos. This is a state requirement for photo inspectiEt"c- 1) 2SO.SO prounding Electrode System.\$l{rounding electrodes as described in 250.52(AX1) through (A)14 that are present at each building or structure served shall be bonded together to form the grounding electrode system (lnstall a Grounding electrode conductor to the ufer near the new sub-panet) 2) 300.4(A)(1) lpstall notch plates where the edge of the bored hole is less than 32 mm (1 114in.) (! locations marked in red) # COLORADO STATE ELECTRICAL BOARD DEPARTMENT OF REGULATORY AGENCIES 1560 Broadway Suite 1350 Denver, Colorado 80202 Phone: (eOg) 8g'!j]ggE 8128124, 6:50 Ah.'! Page 1 oi 1 https:l/www.dora.state.co.us/pls/reallEp-Web-lnspection-GUl.Process-Page