HomeMy WebLinkAboutState Rough-in Electrical Inspection ReportCOLORADO STATE ELEGTRICAL BOARD
INSPECTION REPORT / CORRECTION NOTICE
Date Receiv ed: 22- AUG-24 Permit Number: 1008557
Gontractor/HomeOwner:
Address:
Tlpe of lnspection:
Action:
lnspectors Name: Patrick Proctor
Phone Number: 303-894-2429
Pinnacle Electric Limited
1021t HwY 82
Rough In
Partial
Date:23-AUG-24
Comments or Gorrections: Photos of the corrections can be sent to
patrick.proctor@state.co.us Please make sure lnajlhe permit number shows within the photos.
This is a state requirement for photo inspectiEt"c-
1) 2SO.SO prounding Electrode System.\$l{rounding electrodes as described in 250.52(AX1)
through (A)14 that are present at each building or structure served shall be bonded together to
form the grounding electrode system (lnstall a Grounding electrode conductor to the ufer near
the new sub-panet) 2) 300.4(A)(1) lpstall notch plates where the edge of the bored hole is less
than 32 mm (1 114in.) (! locations marked in red)
#
COLORADO STATE ELECTRICAL BOARD
DEPARTMENT OF REGULATORY AGENCIES
1560 Broadway Suite 1350
Denver, Colorado 80202
Phone: (eOg) 8g'!j]ggE
8128124, 6:50 Ah.'!
Page 1 oi 1
https:l/www.dora.state.co.us/pls/reallEp-Web-lnspection-GUl.Process-Page