HomeMy WebLinkAboutConditions of PermitCONDITIO NS OF PERMIT
BLCO-05 -238129
COLORADO PERCISION TI LE
NEW SHOP AND OFFICE
210 GEMAT COURT
RIFLE, CO 81 650
TYPE VB CONSTRUCTION, F-2 AND B OCCUPANCIES
NONSEPARATED USES, FIRE ALARM REOUIRED PER PLAT
1) THE APPROVED PLANS ARE TO BE ON-SITE FOR INSPECTIONS.
2) A CONSTRUCTION YARD IS DEFINED AS AN INDUSTRIAL USE IN THE COUNTY
LAND USE CODE. THERE ARE SOME VERY SPECIFIC ZONING REOUIREMENTS
WHEN AN INDUSTRIAL USE IS ADJACENT TO RESIDENTIAL PROPERTIES. NATIVE
SPRINGS SUBDIVISION IS DIRECTLY NORTH OF THIS PROPERTY. OUTSIDE STORAGE
WILL BE DIFFICULT OR IMPOSSIBLE BASED ON THE REOUIREMENT TO BE 1OO'
FROM THEIR PROPERTY LINE OR WITHIN A BUILDING. PLEASE SEE THE ATTACHED
CODE FOR REFERENCE.
3) THE RECORDED PLAT REOUTRES ALL BUTLDTNGS lN THIS SUBDIVISION TO BE
PROTECTEDTHE FIRE ALARM ARE REOUIRED TO BE INSPECTED AND APPROVED BY
THE LOCAL FIRE PROTECTION DISTRICT. PLEASE PROVIDE SHOP DRAWINGS TO
THE FIRE DISTRICT FOR REVIEW AND SCHEDULE THE INSPECTIONS
ACCORDINGLY. PLEASE HAVE THE FIRE MARSHAL SIGN THE INSPECTION CARD
WHEN THE ROUGH INSPECTION IS APPROVED AND WHEN THE FINAL INSPECTION
IS APPROVED.
4) THE ELECTRICAL CODE REOUIRES A SEPARATE ELECTRICAL PERMIT FOR LOW
VOLTAGE FIRE ALARMS THAT HAS AN ALARM PANEL AND SEND A NOTIFICATION
TO THE FIRE DISTRICT WHEN UNDER ALARM. A ROUGH-IN INSPECTION WITH THE
STATE ELECTRICAL INSPECTOR IS REOUIRED (303) 869-3458. PLEASE HAVE THE
INSPECTOR SIGN THE BUILDING CARD OR PROVIDE WRITTEN DOCUMENTATION
OF THE INSPECTION.
5) SANTTARY FACILITIES ARE REOUIRED TO BE PROVIDED FOR WORKERS.
6) A LIST OF REOUIRED INSPECTIONS WILL BE ATTACHED TO THE PLANS. THE STATE
RMITS
7) UNDERGROUND UTrLtry LOCATES rS THE RESPONSTBTLTTY OF THE OWNER OR
CONTRACTOR. 811 IS THE COLORADO UTILITY LOCATE HOT LINE.
8) DRAINAGE ACROSS PROPERTY LINES SHALL NOT EXCEED THAT WHICH EXISTED
PRIOR TO GRADING. EXCESS OR CONCENTRATED DRAINAGE SHALL BE
CONTAINED ON SITE OR DIRECTED TO AN APPROVED DRAINAGE FACILITY.
EROSION OF THE GROUND IN THE AREA OF DISCHARGE SHALL BE PREVENTED BY
THE INSTALLATION OF NON-EROSIVE DOWN DRAINS OR OTHER DEVICES.
9) ALL BACKFLOW PREVENTERS ARE REQUIRED TO BE TESTED AND CERTIFIED BY A
LICENSED BACKFLOW SPECIALIST AFTER INSTALLATION AND PRIOR TO ISSUANCE
OF THE CERTIFICATE OF OCCUPANCY.
1O)SEPARATE SIGN PERMITS ARE REOUIRED FOR ANY EXTERNAL SIGNS. PLEASE
CONTACT THE COUNTY PLANII\ER FOR THE APPLICA.TION.
1 1)ELECTRICAL CODE COMPLIANCE WILL BE DETERMINED BASED ON FIELD
INSPECTIONS PERFORMED BY THE STATE ELECTRICAL INSPECTOR, (303) 869-3458.
PLEASE HAVE THE INSPECTOR SIGN THE BUILDING CARD OR PROVIDE WRITTEN
DOCUMENTATION OF THE INSPECTIONS.
12)PLEASE PROVTDE SPECTAL TNSPECTTONS REPORTS TO THE BUTLDTNG
DEPARTMENT, WELDING AND BOLTING IS MINIMUM.
13)GEOTECHNTCAL OBSERVATTON rS REOUTRED WHEN THE EXCAVATTON rS
COMPLETE AND WRITTEN VERIFICATION BE SUPPLIED AT FOOTING INSPECTION,
1 500PSF.
14)ALL EXTERTOR LTcHTtNG tS TO BE DOWNCAST AND SHtELDED.
15)SAFETY GLAZING IS NOT DESIGNATED ON THE PLANS. SAFETY GLAZING WILL BE
cHECKED DURTNG THE FRAMTNG AND FTNAL tNSPECTTON. (rBC 2406.4)
r 6)ANY MEMBRANE AND TiiROUGH PENETRAT|ONS OF THE FiRE RESiST|VE
CONSTRUCTION WILL BE REQUIRED TO BE FIRE-STOPPED WITH LISTED FIRE
STOPPING ASSEMBLIES. THE CONTRACTOR IS TO PROVIDE A CUT SHEET FOR THE
ASSEMBLTES AT THE FRAMTNG TNSPECTTON. (tBC 713)
17)A KNOX BOX IS REOUIRED TO BE MOUNTED ADJACENT TO THE FRONT DOOR.
PLEASE CONTACT THE LOCAL FIRE DISTRICT FOR EXACT LOCATION.
18)THE WALLS SURROUNDING THE TOILET ARE TO BE NON-ABSORBENT FOR A
HEIGHT OF 48'' AND 2' PAST ON EACH SIDE OF THE TOILET.
19)ALL ACCESSIBLE DOOR HARDWARE SHALL HAVE A SHAPE THAT IS EASY TO GRIP,
INCLUDTNG POCKET AND SLTDTNG DOORS. (ANS| A117.1 - 404.2.6)
20)GRAB BAR BACKTNIG tS TO tsE iN FLACE FOR ALL TOTLETS ANjD SHOWERS AT
trDn IrtNt/: tNtcDE/--rtr\ NtI t\htviltt\J il\Jt r_\- I t\JtY.
21)A PASSTNG BLOWER DOOR TEST OF THE OFFTCE AREA tS REOUTRED TO BE
SUBMITTED PRIOR TO ISSUING THE CERTIFICATE OF OCCUPANCY.
22)PROVIDE A MANUAL J REPORT PRIOR TO CALLING IN THE FRAMING INSPECTION.
23)THE SHOWER IS TO BE HANDICAP ACCESSIBLE OR REMOVE FROM THE SCOPE OF
WORK.
24)THE WATERHEATER tS REOUTRED TO BE 18" ABOVE THE SHOP FLOOR.
25)THE PROPOSED UNIT HEATER IN THE OFFICE DOES NOT PROVIDE THE REOUIRED
OUTDOOR AIR TO THE SPACES. ALTERNITIVE METHOD TO BE PROVIDED BY
FRAM I NG/M ECHANICAL I NSPECTION.