To:
October 11,2023
Dave Cardiff Construction
Dave Cardiff, 97 0-37 9-4458, davecardiffconstruction@gmail.com
Project: 1003 Cattle Creek Ridge Road, Carbondale, CO
RE: Micropile Testing Results
It has been a pleasure working with you on the micropiles associated with the foundation for the
addition at 1003 Cattle Creek Ridge Rd. Rock Solid Solutions (RSS) installed 24 plles ranging in
length from 30 to 40 feet. In order to assess the performance of the micropiles, RSS conducted two
proof tests on randomiy selected micropiles on October 11,2023. Enclosed with this letter are the
results of the testing performed, demonstrating that the piles are capable of supporting the required
design loads.
It is essential that the micropile foundation system is discussed with the curent and all future
homeowners. Xeriscaping is highly recolnmended and the void space between the soil surface and
the concrete footer must be maintained over the lif-e of the foundation (a minimum 4-inch void
form was specified in the soils report). Additionally, above-ground downspout extensions are
recommended because underground downspout extensions do not allow for monitoring of the
integrity of the pipe.
Thank you for the opportunity to work with you on this project. If you have any questions or
concerns regarding this testing report, please contact ns.
Respectfully,Reviewed by,
&/*ry(-e-w
Stephanie M. Nocks, P.E.Donald J. Berger, P.E
195 Lodgepole Circle, Parachute, CO 81635
Office: (970) 903-3028 Fax: (970) 712-5715
1003 Cattle Creek Ridge
Micropile Testing Results
Test #1 during Creep Test Test #1 at Max Test Load
.'-:-a,.:' ,:
":,)'
ROCI( SOTNsoturtoNs
Test#2 during Creep Test Test #2 at Max Test Load
IL- 10t
lM@s
\
n\-
t.1sk
ta-r,,t\
tr
i,:ri'.f r i,\-r:,.ji.,
\.L,
NOIE:
ALL
Total Pile Lengtho32'
42'o
Plate size: 6"x6"x3/4"
Bar size: min #9 G
Borehole size: min 4"
PROPOSED FOUNDATION PLAN
STRUClURAL PLANS
HUTTEN RiSIDiNCI
1C5J CATTIT CRIIK RIDGI RCAD
GLiNWCOD SPR]NGS, CO 81601
TED:3//6,/2023
Proof Tlst I l
IN
I
o o
._.F a; iNir
lr ., {a f,! i.r! r !rr.a:
A=1Ok
TL- 1sk i, _l ,. r^N ,, I,rl'' .')ll!')l;lr\. l\t
rIr.\ | f! ri tt\.\.
rii:,. a. i r:.:. lr
3axf i-:i,r .i:)
alrtl\a ; a. :iirl11N. i,,-::Pt! fi
i.(!r. r, -\rL r.t,D
iProof Test 2
J
1 r i:lr .Lrl,!r
r.i i:!j:.iii,r'
'l
I
It = 15k _,1
e IOUNDATION DITAIL_ 1 FOUNDAT]ON DI, Ti\II,*2
IROPOSTI] TCUNDAI ON PLAN
.:.r.i/.:i !. -l
@ 2.-
12" ]HCK CCNC. GRADT BAitS SHAL| HAVI ilC LiAiS
o.c.t.w-
8" 1HICK CONC. GPADE 9UMS SHAIL. IJAVE A SINCII
l4 @ iE" O.C.i.W.
Tail Sleeved Length Bond Length Lotd20' 10' 1Okips20' 15' 15kips20' 20' 2Okips
Quantity
14
6
4
75 Epoxy Coated
:,,:i ,-'r.'
FOUNDATION DETA]I-J
CONSULTANTS, LLC
i, l,'li1, itit.iiti t,:)(t-i :i,)tD, :tii:l' .,i.i
i'l;:l i;a)li iiii, ai.t 81::i',d
r ::li il! g .it,.,i), lilir. :'(:: l!iif .ir : it li il ir l'
.:t ,
i :,i i.. i : .:.r. ,:ri,.. i 1.,1
)l:r)Llri:lr ,i.l, -::
irl.i :t :.r,(i r..ii ;:rIi:]t,: :i)l: i
n{)ffisOtD
Test lD:
MP Size:#9 Grade 75
1
Goulter Creek Addition
1003 Cattle Creek Ridge Road
Proof Test Report - Micropile
37
35
4
90
Date: 10/1112023 Tester: D. Berqer / S. Nocks
Bond Length (min);
Unbonded Length;
Jack Length:
Allowable Pullout Resistance
Design Test Load:
MP Cross-sectional area:
Total MP Length:
Bore Hole Depth:
Bore Hole Diameter:
Bore Hole lnclination:
ft
ft
in
psi
lbss
.)tn-
ft
ft
in
de
15.00
20.o
24.0
7.0
1 5000
n00ti x()t$
Tester's Comments
Load
Cycle
Reading
Times (min)
Load
lncrements
(%)
Load
lncrements
(lbs)
Pressure
Gauge (psi)DialGauqe Movement
Elastic
Movement
2.5 AL 2291 400 0.'185 0
Load 2.5 0.30 4500 575 0.202 0.017
2.5 0.45 6750 752 o.225 0.040
2.5 0.60 9000 930 o.246 0.061
2.5 0.75 11250 1 108 o.268 0.083
2.5 0.90 13500 1286 0.288 0.103
2.5 1.00 1 5000 1404 0.305 o.120
2.5 1.15 17250 1582 o.324 0.139
I 1.30 1 9500 1760 0.353 0.1 68
2 1.30 1 9500 1760 0.355 0.170
3 1.30 1 9500 1760 0.355 0.170
4 1.30 1 9500 1760 0.360 o.175
5 1.30 1 9500 1760 0.363 o.178
6 1.30 1 9500 1760 0.367 0.182
Creep Test
10 '1.30 19500 1760 0.368 0.183
2.5 1.45 21750 1937 0.376 0.191
2.5 1.60 24000 2115 0.402 4.217
4 1.30 1 9500 1760 0.365 0.1 E0
Unload 4 1.00 15000 1404 0.330 o.145
4 0.75 11250 1 108 0.292 o.107
4 0.50 7500 812 0.259 0.074
4 o.25 3750 s15 o.222 0.037
4 AL 2291 400 o.204 0.019 0.1 49
Load Displacement Curve
0.200
30000
0 1 00o
o)
o
Lr=
Load (pounds)
10000 200000
0.000
Allowable Creep (1-10 min):
Actual Creep:
0.04 in
0.015 in
Stiffness 111 kips/in
Calibration Equation:
Gauge Pressure = 0.079*Load + 219
Testing Equipment:
60ton jack RHA604D #350002, RSS2018
P159D Pump Serial# 0901AR79126,
10,000psi4inch Gauge
R0[[$0m
Coulter Creek Addition
1003 Gattle Greek Ridge Road
Proof Test Report - Micropile
Test lD:
MP Size
2
#9 Grade 75 epoxv-coated
Date: 10/1112023 Tester. D. Berger i S. Nocks
MP Cross-sectional area
Total MP Length:
Bore Hole Depth:
Bore Hole Diameter:
Bore Hole lnclination:
32
,2tn
ft
ft
in
deg
30
ft
ft
in
psi
lbs
4
Bond Length (min):
Unbonded Length:
Jack Length:
Allowable Pullout Resistance:
Design Test Load:
10.00
20.0
24.0
7.0
1 000090
nl}ffi $0til)
Tester's Comments:
Load
Cycle
Reading
Times (min)
Load
lncrements
(%\
Load
lncrements
(lbs)
Pressure
Gauqe (psi)Dial Gauqe Movement
Elastic
Movement
2.5 AL 2291 400 0.387 0
Load 2.5 o.45 4500 575 0.405 0.018
2.5 0.60 6000 693 o.423 0.036
2.5 0.75 7500 812 0.438 0.051
2.5 0.90 9000 930 o.448 0.061
2.5 1.00 1 0000 1 009 0.462 0.075
2.5 1.15 11500 I 128 o.472 0.0E5
1 1.30 1 3000 1246 o.487 0.100
2 1.30 I 3000 1246 0.488 0.1 01
3 1.30 1 3000 1246 0.489 0.102
4 1.30 1 3000 1246 0.490 0.'103
5 1.30 1 3000 1246 0.492 0.1 05
6 1.30 1 3000 1246 o.492 0.10s
Creep Test
10 1.30 1 3000 1246 o.494 0.107
2.5 1.45 14500 1 365 0.503 0.116
2.5 1.60 1 6000 1483 0.520 0.1 33
4 1.30 1 3000 1246 o.491 0.104
Unload 4 1.00 1 0000 1 009 0.459 o.072
4 0.75 7500 812 0.435 0.048
4 0.50 5000 614 o.416 0.029
4 AL 2291 400 0.389 0.002 0.098
Load Displacement Curve
30000
0.300 )
0
0.100
0.000 |
0.200
Load (pounds)
10000 20000
@o
o
0.400
0.500
Allowable Creep (1-10 min)
ActualCreep:
0.04 tn
0.007 in
Stiffness 120 kips/in
Calibration Equation:
Gauge Pressure = 0.079*Load + 219
Calibration Date: 1 I 1 212021
Testing Equipment:
60ton jack RHA604D #350002, RSS2018
P159D Pump Serial# 0901AR79126,
10,000psi4inch Gauge