HomeMy WebLinkAboutObservation of Excavation 10.11.2023ROCK $OIJIISOLUTIONS . BulL9 To: October 11,2023 Dave Cardiff Construction Dave Cardiff, 97 0-37 9-4458, davecardiffconstruction@gmail.com Project: 1003 Cattle Creek Ridge Road, Carbondale, CO RE: Micropile Testing Results It has been a pleasure working with you on the micropiles associated with the foundation for the addition at 1003 Cattle Creek Ridge Rd. Rock Solid Solutions (RSS) installed 24 plles ranging in length from 30 to 40 feet. In order to assess the performance of the micropiles, RSS conducted two proof tests on randomiy selected micropiles on October 11,2023. Enclosed with this letter are the results of the testing performed, demonstrating that the piles are capable of supporting the required design loads. It is essential that the micropile foundation system is discussed with the curent and all future homeowners. Xeriscaping is highly recolnmended and the void space between the soil surface and the concrete footer must be maintained over the lif-e of the foundation (a minimum 4-inch void form was specified in the soils report). Additionally, above-ground downspout extensions are recommended because underground downspout extensions do not allow for monitoring of the integrity of the pipe. Thank you for the opportunity to work with you on this project. If you have any questions or concerns regarding this testing report, please contact ns. Respectfully,Reviewed by, &/*ry(-e-w Stephanie M. Nocks, P.E.Donald J. Berger, P.E 195 Lodgepole Circle, Parachute, CO 81635 Office: (970) 903-3028 Fax: (970) 712-5715 1003 Cattle Creek Ridge Micropile Testing Results Test #1 during Creep Test Test #1 at Max Test Load .'-:-a,.:' ,: ":,)' ROCI( SOTNsoturtoNs Test#2 during Creep Test Test #2 at Max Test Load IL- 10t lM@s \ n\- t.1sk ta-r,,t\ tr i,:ri'.f r i,\-r:,.ji., \.L, NOIE: ALL Total Pile Lengtho32' 42'o Plate size: 6"x6"x3/4" Bar size: min #9 G Borehole size: min 4" PROPOSED FOUNDATION PLAN STRUClURAL PLANS HUTTEN RiSIDiNCI 1C5J CATTIT CRIIK RIDGI RCAD GLiNWCOD SPR]NGS, CO 81601 TED:3//6,/2023 Proof Tlst I l IN I o o ._.F a; iNir lr ., {a f,! i.r! r !rr.a: A=1Ok TL- 1sk i, _l ,. r^N ,, I,rl'' .')ll!')l;lr\. l\t rIr.\ | f! ri tt\.\. rii:,. a. i r:.:. lr 3axf i-:i,r .i:) alrtl\a ; a. :iirl11N. i,,-::Pt! fi i.(!r. r, -\rL r.t,D iProof Test 2 J 1 r i:lr .Lrl,!r r.i i:!j:.iii,r' 'l I It = 15k _,1 e IOUNDATION DITAIL_ 1 FOUNDAT]ON DI, Ti\II,*2 IROPOSTI] TCUNDAI ON PLAN .:.r.i/.:i !. -l @ 2.- 12" ]HCK CCNC. GRADT BAitS SHAL| HAVI ilC LiAiS o.c.t.w- 8" 1HICK CONC. GPADE 9UMS SHAIL. IJAVE A SINCII l4 @ iE" O.C.i.W. Tail Sleeved Length Bond Length Lotd20' 10' 1Okips20' 15' 15kips20' 20' 2Okips Quantity 14 6 4 75 Epoxy Coated :,,:i ,-'r.' FOUNDATION DETA]I-J CONSULTANTS, LLC i, l,'li1, itit.iiti t,:)(t-i :i,)tD, :tii:l' .,i.i i'l;:l i;a)li iiii, ai.t 81::i',d r ::li il! g .it,.,i), lilir. :'(:: l!iif .ir : it li il ir l' .:t , i :,i i.. i : .:.r. ,:ri,.. i 1.,1 )l:r)Llri:lr ,i.l, -:: irl.i :t :.r,(i r..ii ;:rIi:]t,: :i)l: i n{)ffisOtD Test lD: MP Size:#9 Grade 75 1 Goulter Creek Addition 1003 Cattle Creek Ridge Road Proof Test Report - Micropile 37 35 4 90 Date: 10/1112023 Tester: D. Berqer / S. Nocks Bond Length (min); Unbonded Length; Jack Length: Allowable Pullout Resistance Design Test Load: MP Cross-sectional area: Total MP Length: Bore Hole Depth: Bore Hole Diameter: Bore Hole lnclination: ft ft in psi lbss .)tn- ft ft in de 15.00 20.o 24.0 7.0 1 5000 n00ti x()t$ Tester's Comments Load Cycle Reading Times (min) Load lncrements (%) Load lncrements (lbs) Pressure Gauge (psi)DialGauqe Movement Elastic Movement 2.5 AL 2291 400 0.'185 0 Load 2.5 0.30 4500 575 0.202 0.017 2.5 0.45 6750 752 o.225 0.040 2.5 0.60 9000 930 o.246 0.061 2.5 0.75 11250 1 108 o.268 0.083 2.5 0.90 13500 1286 0.288 0.103 2.5 1.00 1 5000 1404 0.305 o.120 2.5 1.15 17250 1582 o.324 0.139 I 1.30 1 9500 1760 0.353 0.1 68 2 1.30 1 9500 1760 0.355 0.170 3 1.30 1 9500 1760 0.355 0.170 4 1.30 1 9500 1760 0.360 o.175 5 1.30 1 9500 1760 0.363 o.178 6 1.30 1 9500 1760 0.367 0.182 Creep Test 10 '1.30 19500 1760 0.368 0.183 2.5 1.45 21750 1937 0.376 0.191 2.5 1.60 24000 2115 0.402 4.217 4 1.30 1 9500 1760 0.365 0.1 E0 Unload 4 1.00 15000 1404 0.330 o.145 4 0.75 11250 1 108 0.292 o.107 4 0.50 7500 812 0.259 0.074 4 o.25 3750 s15 o.222 0.037 4 AL 2291 400 o.204 0.019 0.1 49 Load Displacement Curve 0.200 30000 0 1 00o o) o Lr= Load (pounds) 10000 200000 0.000 Allowable Creep (1-10 min): Actual Creep: 0.04 in 0.015 in Stiffness 111 kips/in Calibration Equation: Gauge Pressure = 0.079*Load + 219 Testing Equipment: 60ton jack RHA604D #350002, RSS2018 P159D Pump Serial# 0901AR79126, 10,000psi4inch Gauge R0[[$0m Coulter Creek Addition 1003 Gattle Greek Ridge Road Proof Test Report - Micropile Test lD: MP Size 2 #9 Grade 75 epoxv-coated Date: 10/1112023 Tester. D. Berger i S. Nocks MP Cross-sectional area Total MP Length: Bore Hole Depth: Bore Hole Diameter: Bore Hole lnclination: 32 ,2tn ft ft in deg 30 ft ft in psi lbs 4 Bond Length (min): Unbonded Length: Jack Length: Allowable Pullout Resistance: Design Test Load: 10.00 20.0 24.0 7.0 1 000090 nl}ffi $0til) Tester's Comments: Load Cycle Reading Times (min) Load lncrements (%\ Load lncrements (lbs) Pressure Gauqe (psi)Dial Gauqe Movement Elastic Movement 2.5 AL 2291 400 0.387 0 Load 2.5 o.45 4500 575 0.405 0.018 2.5 0.60 6000 693 o.423 0.036 2.5 0.75 7500 812 0.438 0.051 2.5 0.90 9000 930 o.448 0.061 2.5 1.00 1 0000 1 009 0.462 0.075 2.5 1.15 11500 I 128 o.472 0.0E5 1 1.30 1 3000 1246 o.487 0.100 2 1.30 I 3000 1246 0.488 0.1 01 3 1.30 1 3000 1246 0.489 0.102 4 1.30 1 3000 1246 0.490 0.'103 5 1.30 1 3000 1246 0.492 0.1 05 6 1.30 1 3000 1246 o.492 0.10s Creep Test 10 1.30 1 3000 1246 o.494 0.107 2.5 1.45 14500 1 365 0.503 0.116 2.5 1.60 1 6000 1483 0.520 0.1 33 4 1.30 1 3000 1246 o.491 0.104 Unload 4 1.00 1 0000 1 009 0.459 o.072 4 0.75 7500 812 0.435 0.048 4 0.50 5000 614 o.416 0.029 4 AL 2291 400 0.389 0.002 0.098 Load Displacement Curve 30000 0.300 ) 0 0.100 0.000 | 0.200 Load (pounds) 10000 20000 @o o 0.400 0.500 Allowable Creep (1-10 min) ActualCreep: 0.04 tn 0.007 in Stiffness 120 kips/in Calibration Equation: Gauge Pressure = 0.079*Load + 219 Calibration Date: 1 I 1 212021 Testing Equipment: 60ton jack RHA604D #350002, RSS2018 P159D Pump Serial# 0901AR79126, 10,000psi4inch Gauge