Loading...
HomeMy WebLinkAboutDuct Test Report - SupplyRetrotec rCloud 1 Quality Assurance Report Iecc Duct Test PASS Your Result: 2.5 CFM/100 ft² (43 CFM * 100 / 1689 ft²) Target < 3 CFM/100 ft² Test Information Test Name 325 Eagle Ridge Dr Test Date 2024-09-20 03:47 PM (MDT) Export id FHRXTXR5 Company Name Elite Energy Concepts Technician Name Coltan Gechter Technician Email coltan@eliteenergyconcepts.com Building Information Address 325 Eagle Ridge Dr City Parachute State CO Zip/postal Code 81635-7805 Country United States Year Constructed Not available Elevation 5354 ft Address Verified?Yes Building Latitude, Longitude 39.444264, -108.032138 GPS validation Latitude/Longitude: 39.444244, -108.032209; Accuracy: 16 ft Estimated Distance From Address 16 ft Test Equipment Fan Model Retrotec 300 Fan Serial Number 3XLFT00701 Pressure Gauge Model Retrotec DM32 10A Gauge Serial Number 415340 Environmental Conditions Pre-test Indoor Temperature 76 °F Pre-test Outdoor Temperature 83 °F Wind Speed 14 MPH Average Barometric Pressure 101.4 kPa Test Dimensions Conditioned Floor Area 1689 ft² Volume 16191 ft³ Retrotec rCloud 2 Test Results Summary Test Type Iecc Duct Test Flow Reference Pressure 25 Pa Time Averaging 10 seconds Induced Duct Pressure (includes baseline)-24.76 Pa Nominal Fan Flow 42.68 CFM @ 25 Pa Test Results Test Data Set 1 Flow Direction Depressurize Gauge Location Outside Measured Pressure (Pa)-24.76 Fan Pressure [300 - 47] (Pa)171.46 Flow (CFM)42.44 Retrotec rCloud 3 Test Notes No notes entered. Flow Equation Parameters - Factory Default Fan Model Retrotec 300 Fan Serial Number 3XLFT00701 Flow Equation Parameters - B1 Units Used For Flow Parameters in Equation CFM Fan pressure (FP) is the measured fan pressure when using a self-referenced fan or when the room pressure is negative. If using a fan which is not self-referenced, and the room pressure is positive, fan pressure is calculated by subtracting the measured room pressure from the absolute value of the fan pressure. If PrA is greater than 0 or fan is self-referencing: FP = |PrB| - PrA If PrA is less than 0 or fan is self-referencing: FP = PrB Flow calculations are not valid if fan pressure is less than either MF or (K2 x |RP|) FP = fan pressure, RP = room pressure Range N K K1 K2 K3 K4 MF Open 0.5010 28.9100 0.0000 0.4000 0.0000 1 20 74 0.5045 7.0770 0.0000 0.2500 0.0000 1 15 47 0.5000 3.2410 0.0000 0.1000 0.0000 1 10 29 0.5020 1.1900 0.0000 0.2000 0.0000 1 20 18 0.4990 0.4570 0.0000 0.2500 0.0000 1 25 11 0.4800 0.2080 0.0000 0.2500 0.0000 1 25 7 0.5000 0.0718 0.0000 0.1100 0.0000 1 25 102 0.5900 10.7000 0.0000 0.4000 0.0000 1 100 flow = (FP - RP x K1)n x (K + K3 x FP) x K4