HomeMy WebLinkAboutDuct Leakage ReportTest Date: 2024-11-06 Client Tester Building Description Miguel Salvidrez Company Dexter Diagnostics Building Address 129 Sage Meadow Address 18 Crescent Pl Glenwood Springs, CO 81601 Glenwood Springs, CO 81601 Contact Miguel Salvidrez Technician Amanda Poindexter Phone 970-309-5416 Phone 720-219-3683 Test Type Total Duct Leakage Gauge S/N 2070150 Fan series 200 Fan S/N LF2001000 Conditioned Floor Area 1158.0 sq ft Air Handler Flow 1600 CFM Percentage of Duct Leakage to Outdoors Supply Return Average Duct Operating Pressure 25.0 Pa 25.0 Pa Leakage Split 50% 50% Leakage Penalty 100% 50% Pressurization Duct Pressure 25.7 Pa Fan Pressure 209.0 Pa Range Configuration Low Duct Leakage 25.5 CFM Leakage Area 4.7 sq in Leakage constant, C 3.63 Leakage Exponent 0.60 (assumed) Total Duct Leakage Duct Leakage as % of Air Handler Flow 1.6% Duct Leakage to Outdoors (estimated) Leakage/Conditioned Floor Area 22 CFM/1,000 sq ft at 25 Pa 2.2 CFM/100 sq ft at 25 Pa Duct Leakage Test Report 0.022 CFM/sq ft at 25 Pa Building and Duct Details 25.5 CFM at 25 Pa Leakage Results Leakage Data Per the 2018 IECC: R403.3.6 Duct leakage (prescriptive). The total leakage of the ducts, where measured in accordance with Section R403.3.5, shall be as follows: 1.) Rough-in test: Total leakage shall be less than or equal to 3 CFM per 100 SF of conditioned floor area where air handler is not installed. Maximum allowable: 3 CFM x 1,158/100 sq ft = 32.74 CFM at 25 Pa - Note that SF is for ductwork servicing the upstairs only as this is the only ductwork that is outside of the thermal envelope. PASSES at 25.5 CFM at 25 Pa.