HomeMy WebLinkAboutOWTS Installation Observation 12.12.24Page 14 of 17
TO: Mr. Ted White, Garfield County Env Health / Shania McCain, Env Health Specialist
FROM: Rick L Barth, PE, SGM Civil Services
DATE: December 12, 2024
RE: Umbrella Commercial Site OWTS Record Affirmation OWTS Permit SEPT-7909
In November of 2024 SGM was contacted by Terralink Structures on
behalf of Loose Cannon for the commercial parcel 5169 County Road
154, south of Glenwood Springs. The site was a new construction on
a previous light industrial yard for a commercial/business facility and
warehouse. The original design report was submitted in the fall of
2022.
Minor but understandable alterations have been made to the layout.
Plumbing exits from the building warranted (for ease of construction)
two separate connections that led to the relocated tank in the parking
(as opposed to next to the driveway). The tank is traffic rated and
has concrete topping above for load bearing. The Orenco pump
system is in the tank and panel attached to the structure.
The field is in the targeted location of the test pits, with ever so slight
re-orientation just to fit the available flat space better. The final ADV
was installed and grades/vegetative cover are per Reg 43 standards
of relatively flat and non-irrigated grasses only.
These alterations have been shown and were noted in the permit application in January. This
memo is to provide our affirmation of that installation. The elements are in the appropriate locations
or just with very mild alteration due to construction constraints, but nothing to alter design intent or
function. Altitude Septic provided photos of the squirt test for the STA bed and such documentation
is included.
Please accept this letter as our affirmation of the OWTS installation for the above site associated
with the record drawings of Fall 2024, provided by the installer, Altitude Septic. Our field walk affirm
this as an accurate representation of the constructed conditions.
Attachments:
Photos
Tank specification
www .s gm-in c .co m
GLENWOOD SPRINGS 118 West Sixth St, Suite 200 | Glenwood Springs, CO 81601 | 970.945.1004
Page 15 of 17
Photo of full bed.
Snip screen of pump test
PREPARED FOR:
Valley Precast, Inc.
28005 CO. RD 317
Buena Vista, CO 81211
PERFORMANCE TEST FOR:
Standard Septic Tank
1,500 Gallon Top Seam
5’-8” x 11’-0” x 5’-10” O.D.
H-20 Loading
SPECIALTY ENGINEERING SERVICES PROVIDED BY:
Project No. 15-18.01 Designed By: KRWB - 3/24/2015 Sheet 1 of 12
3/26/15
Project No. 15-18.01 Designed By: KRWB - 3/24/2015 Sheet 2 of 12
Client:
Job Number: 12-18.01
File Name: stdesign.xls
Entered By: SDG
Date:2/24/2015
PRECAST CONCRETE SEPTIC TANK Sheet: ________ of _________
WALL DESIGN BASED ON VACUUM TEST
Denotes input field
Tank Model
Volume 1500 Gallons
Length Width Height
Outside Dimensions (ft) 11.00 5.67 5.67
Top Slab Base Slab Walls
Member Thickness (in) 7.00 4.00 4.00
Joint Height 4.92 ft
Weight 14780 lbs Ref ASTM C1227
**Vacuum 10.5 in Hg Geographic Area
Uniform Load 756 psf Minimum Live Load 100 psf
Safety Factor 1.5
Allowable Uniform Load 504 psf 80 psf - LL Surcharge
Equivalent Fluid Pressure 40 pcf (Dry) 80 pcf (Saturated)
Soil Weight 120 pcf
Earth Fill (ft) 1.0 1.5 2.0 3.0 4.0
Dead Load (psf) 120 180 240 360
Maximum Live Load (psf) 384 324 264 144 504
Depth to bottom of tank (ft) 6.7 7.2 7.7 8.7 9.7
Design Depth (ft) 4.21 4.71 5.21 6.21 7.21
Lateral earth pressure at design depth:
Water tbl (ft) Earth Pressure (psf)
0 417 457 497 N/A N/A
1 377 417 457 N/A N/A
2 337 377 417 497 N/A
3 297 337 377 457 N/A
Dry 168 188 208 248 288
Water Table Depth (ft) 0 1 2 3 4
Maximum Fill Depth(Walls) (ft) 2.0 2.0 3.0 3.0 4.0
Maximum depth controlled by lateral soil pressure for water table <3'
**Vacuum test results were provided by the client and have not been witnessed or
independently verified by Concrete Engineering Solutions, LLC
Wall Capacity
Valley Precast
CO
1500 Top-Seam
Base Slab Capacity
Project No. 15-18.01 Designed By: KRWB - 2/24/2015 Sheet 3 of 12Project No. 14-18.01 Designed By: KRWB - 3/2/2015 Sheet 3 of 12Project No. 15-18.01 Designed By: KRWB - 3/24/2015 Sheet 3 of 12
Client:
Job Number: 12-18.01
File Name: stdesign.xls
Entered By: SDG
Date: 2/24/2015
PRECAST CONCRETE SEPTIC TANK Sheet: ________ of _________
WALL DESIGN BASED ON VACUUM TEST
DESIGN SUMMARY
Notes:
*Concrete Strength 6000 psi **Tank should not be drained during
Vacuum Test Load 10.5 in Hg periods of high groundwater.
Allowable Uniform Load 504 psf
*Concrete Strength at time of vacuum test
Uniform Live Load Table
Earth Fill (ft) 1.0 1.5 2.0 3.0 4.0
Dead Load (psf) 120.0 180.0 240.0 360.0 0.0
Maximum Live Load (psf) 384.0 324.0 264.0 144.0 504.0
Maximum Fill Depth Table
Water Table Depth (ft) 0 1 2 3 4
Maximum Fill Depth (ft) 2 2 3 3 4
Maximum depth controlled by lateral soil pressure for water table <3'
Valley Precast
Project No. 15-18.01 Designed By: KRWB - 2/24/2015 Sheet 4 of 12Project No. 14-18.01 Designed By: KRWB - 3/2/2015 Sheet 4 of 12Project No. 15-18.01 Designed By: KRWB - 3/24/2015 Sheet 4 of 12
Project No. 14-18.01 Designed By: KRWB - 3/2/2015 Sheet 5 of 12Project No. 15-18.01 Designed By: KRWB - 3/24/2015 Sheet 5 of 12
β
β
Project No. 15-18.01 Designed By: KRWB - 2/24/2015 Sheet 6 of 12Project No. 14-18.01 Designed By: KRWB - 3/2/2015 Sheet 6 of 12Project No. 15-18.01 Designed By: KRWB - 3/24/2015 Sheet 6 of 12
ρ ρ ρ
ρ
ρ ρ 2 ρ
Project No. 15-18.01 Designed By: KRWB - 2/24/2015 Sheet 7 of 12Project No. 14-18.01 Designed By: KRWB - 3/2/2015 Sheet 7 of 12Project No. 15-18.01 Designed By: KRWB - 3/24/2015 Sheet 7 of 12
β
β
β
Project No. 15-18.01 Designed By: KRWB - 3/24/2015 Sheet 8 of 12
ρ ρ ρ
ρ
ρ ρ 2 ρ
Project No. 15-18.01 Designed By: KRWB - 3/24/2015 Sheet 9 of 12
β β
β β
β β
Project No. 15-18.01 Designed By: KRWB - 2/24/2015 Sheet 10 of 12Project No. 14-18.01 Designed By: KRWB - 3/2/2015 Sheet 10 of 12Project No. 15-18.01 Designed By: KRWB - 3/24/2015 Sheet 10 of 12
ρ ρ
ρ ρ ρ ρ
ρ ρ
ρ ρ 2 ρ ρ ρ 2 ρ
Project No. 15-18.01 Designed By: KRWB - 2/24/2015 Sheet 11 of 12Project No. 14-18.01 Designed By: KRWB - 3/2/2015 Sheet 11 of 12Project No. 15-18.01 Designed By: KRWB - 3/24/2015 Sheet 11 of 12
SEPTIC TANK VACUUM TEST REPORT
Manufacturer: _____Valley Precast Inc.______________________ Test Date: __12-12-13__________
Address _____28005 CR 317_________________________ Report By: __Derrick Eggleston____
_____P.O. Box 925_______________________
City, State Zip _____Buena Vista, CO 81211________________
TANK DESCIPTION (Attach detailed drawings)
Model No: __1000T Volume and/or working capacity: _1000 Gallons__ Mfg Date: 9/23,25,26/2013____
Outside Dimensions: Length_111”__ Width _60”___ Height __68”____
Member Thickness: Top Slab__5”____ Base Slab _4”____ Walls __4”____
Compartments: __x__Dual ____Single
Seam: ____Mid __x__Top
If top seam; does cover slab interlock with top of wall? __x__Yes ____No
Joint Sealant Brand/Size: ___Conseal CS 202, 7/8”________________
Pipe Seals Brand/Type: ___Press-Seal 402F______No. of Inlet Seals: ____1______ No. of Outlet Seals: ____1____
MIX DESIGN
Mix No: __#1 bottom, #2 top________ W/C Ratio ___.340________
Fibers: _Top__No _ Bottom__Yes Brand/Type _BASF MACMatrix MacroFibers_ Dosage
____5LBS____/cy
REINFORCING STEEL
Rebar: ____Grade 40 _X__Grade 60 ___None
Wire Fabric: ___Smooth (ASTM A185) ___Deformed (ASTM A497) _x__None
CONCRETE TEST RESULTS
Slump: __24”_______ %Air: ___5%_____ Temp: ___70%______ Unit Weight: __142lbs?ft3___
Compressive Strength: __Market @ 6000psi______ psi @ ___28____ Days
WATERTIGHTNESS TEST
Tank withheld 4” of mercury for 2 minutes without loss of vacuum: _x__Yes ___No
STRUCTURAL TEST
Vacuum measuring device: ____Manometer __x__Gauge: Date of last gauge calibration ___new 2013______
Tank tested to failure: ___Yes _x__No
Maximum vacuum pressure tested: __10”__ inches Hg. Additional load applied to top slab ___0____ psf
Tank was inspected after the load was applied and there were no signs of cracks: yes X no (describe below)
__one of three tanks showed facial cracks at 9.5 to 10”, when at 10” I stopped pressure increase and left tank at 10”
for 5 minutes, released pressure and cracks almost disappeared, no signs of cracking inside of tank and water check
showed no leaks_____________________________________________________________________________
Sheet 5 of 5
Project No. 15-18.01 Designed By: KRWB - 2/23/2015 Sheet 10 of 10Project No. 15-18.01 Designed By: KRWB - 2/24/2015 Sheet 12 of 12Project No. 14-18.01 Designed By: KRWB - 3/2/2015 Sheet 12 of 12Project No. 15-18.01 Designed By: KRWB - 3/24/2015 Sheet 12 of 12