HomeMy WebLinkAboutDuct Leakage TestTest Date: 2025-01-03 Client Tester Building Description Slawek Wojciuch Company Dexter Diagnostics Building Address 34 Vista Place Address 18 Crescent Pl Glenwood Springs, CO 81601 Glenwood Springs, CO 81601 Contact Slawek Wojciuch Technician Amanda Poindexter Phone 970-987-2353 Phone 720-219-3683 Test Type Gauge S/N 2070150 Fan series 200 Fan S/N LF2001000 Conditioned Floor Area 3343.0 sq ft Percentage of Duct Leakage to Outdoors 25% (estimated) Supply Return Average Duct Operating Pressure 25.0 Pa 25.0 Pa Leakage Split 50% 50% Leakage Penalty 100% 50% Depressurization Duct Pressure -11.6 Pa Fan Pressure 181.0 Pa Range Configuration Open- Duct Leakage 439.6 CFM Leakage Area 120.0 sq in Leakage constant, C 101.01 Leakage Exponent 0.60 (assumed) Duct Leakage to Outdoors Leakage/Conditioned Floor Area Duct Leakage Test Report 0.131 CFM/sq ft at 25 Pa Building and Duct Details 439.6 CFM at 25 Pa 109.9 CFM at 25 Pa Leakage Results Leakage Data 131 CFM/1,000 sq ft at 25 Pa 13.1 CFM/100 sq ft at 25 Pa Per the 2018 IECC: R403.3.4 Duct leakage (prescriptive). The total leakage of the ducts, where measured in accordance with Section R403.3.3, shall be as follows: 1.) Postconstruction test: Total leakage shall be less than or equal to 4 CFM per 100 SF of conditioned floor area. Maximum allowable: 4 CFM x 3,343/100 sq ft = 134 CFM at 25 Pa * Total Duct Leakage - DOES NOT PASS * Duct Leakage to Outdoors - If considered, this project would pass at 12 CFM. Target pressure of -25 Pa was not able to be achieved.