Mechanical Compliance Gertificate
Profect lnformatlon
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
2018IECC
Carbondale, Colorado
5b
New Construction
Conshuction Site:Owner/Agent:
Addltional Efflclency Package(s)
Credib: l.0Requlred'1.0 ProPosed
On-slte Renewablo Energy. 1.0 credit
Mechanical Systems Llst
Quantlty Syetem Type & Deecrlptlon
1 HVAC System 1 (Single Zone);
Heating:2 each - Radiant Heater, Propane, Capaclty = 125000 kBtulh
No minimum efliciency requlrement applies
Fan System: None
Water Heater 1:
ElecMc lnslantaneous Water Heater, Capacity: 0 gallons w/ Circulation Pump
No mlnlmum effciency requirement applies
Deslgner/Contraclor:
1
Mechanlcal Compliance Statement
Compliance Statement The proposed mechanical design represented in this document is consistent with the building plans'
ipeilncations, ind ottrer calcirlations submitted with this peimit gOplication. The proposed m.echanical systems have been
OLiigneO to meet the 2018 IECC requirements in COMctre'ck Versi6n 4.1.5.5 and to comply with any applicable mandatory
requlrements listed in the lnspection Checklist.
Slgnature DateName - Tiile
Project Title:
Data filename: C:\Users\Robert Parrington\Documents\CoMcheck\Broadhurst'cck
Report datet l2ltBl24
Page 3 of 14
Assembly Gross Area
or
Perimeter
Cavity
R-Value
Cont.
R-Value
Proposed
U-Factor
Budget U-
Factorr.r
(compressed at girt), [Bldg. Use 1 - Warehouse]
Door 3: lnsulated Metal, Garage door 14o/o glazing, [Bldg. Use 1 -
Warehouse]
Door 4: lnsulated Metal, Swinging, [Bldg. Use 1 - Warehouse]
196
21
0.1 00
0.300
0.310
0.370
(a) Budget U-factors are used for software baseline calculations ONLY, and are not code requirements.
(b) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
Envelope Gompliance Statement
Compliance Staternent: The proposed envelope design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed envelope systems have been
designed to meet the 2018 IECC requirements in COMcheck Version 4.1.5.5 and to comply with any applicable mandatory
requirements listed in the lnspection Checklist.
Name - Title Signature Date
Project Title: Broadhurst shop
Data filename: C:\Users\Robert Parrington\Documents\COMcheck\Broadhurst.cck
Report date: 10129124
Page 2 ot 9
COMcheck Software Version 4.1.5.5
Envelope Gompliance Gertificate
Proiect lnformatlon
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
Vertical Glazing / Wall Area:
Construction Slte:
Additional Efficiency Package(s)
Credils: l.0Required 1.0 ProPosed
On-site Renewable Energy, 1.0 credit
Buildlng Area
2018IECC
Carbondale, Colorado
5b
New Construction
2Yo
OwnerlAgenl:Designer/Contractor:
Floor Arsa
1-Warehouse 6000
Envelope Assemblies
Aesembly Gross Area Cavlty
or R-Value
Perlmeter
Cont.
R-Value
Propoaed
U.Factor
Budget U-
Factoror
Roof 1: Metal Building, Screw Down, Llner System without Thermal
Blocks, [Bldg. Use 1 - Warehouse]
NPRTH
Exterior Wall 3: O{her Meial Building Wall, lBldg. Use 1 -
Warehousel (b)
Window 2: MnyUFibeqlass Frame:Operable, Perf. Specs.: Product lD
pella, SHGC 0.30, [Bldg. Use 1 - Warehouse] (c)
BasementWall 1: Solid Concrete:8" Thickness, Normal Densl$,
Funing: None, Wall Ht 9.0, Depth B.G. 8.5, lBldg. Use'l - Warehousel
EAST
Exterior Wall 4: Other Metat Building Wall, [Bldg. Use 1 -
Warehousel (b)
Window 3; VinyllFiberglass Frame:Operablo, Perf. Specs.: Product lD
pella, SHGC 0.30, [Bldg. Use 1 - Warehouse] (c)
SOUTH
Extedor Wall 1: Other Metal Building Wall, [Bldg. Use 1 -
Warehousel (b)
Wndow'l: VinyUFiberglass Frame:Operable, Perf. Specs.: Product lD
pella, SHGC 0.30, lBldg. Use I - Warehousel (c]
Door 1: lnsulated Metal, Swinging, [Bldg. Use 1 - Warohouse]
Door 2: lnsulated Metal, Garage door 14Yo glazing, lBldg. Use 1 '
Warehousel
WEST
ExtsriorWall 2r O{her Metal Building Wall, [Bldg. Use 1 -
Warehousel(b)
6000 30.0 I 1.0
1 100
18
900 10.0
1350
72
2000
18
21
456
1 350
0.030
0,066
0.300
0.088
0.066
0.300
0.066
0.300
0.360
0.100
0.066
0.035
0.052
0.450
0.119
0.052
0.450
0.052
0.450
0.370
0.310
0.052
Project Title:
Data filename: . C:\Users\Robert Parrington\Documents\COMcheck\Eroadhurst.cck
Report date: l2ll8l24
Page 1 of 14
Assembly Grosa Area Gavltyor R-Value
Perlmeter
Gont.
R-Value
Propored
U.Factor
Budget U.
Factorr.l
OoorS: lnsulated Metal, €arage door 14alo gladng, [Bldg. Use t -
Warehoussl
Door6: lnsulated Metal, Swlnging, [Bldg. Use 1 - Warehousel
196
21
0.100
0.360
0.310
0.370
(a) Budget U-factorc arc used for sofrrar€ basellno calculallone ONLY, and are not coda requlrements.
(b) 'Olhe/ components requiro aupporting documentalion for propoaed U-fac,tors.
(c) Feneslratlon product performance muat be ceilfled ln accordancs with NFRC and reguiles supporting documentation.
Envelope Gompliance Statement
Compllance staternenti The proposed envelope deslgn represented ln this document ls conslstent wlth the buildlng plans,
speclflcations, and other calculations submltted wlth thls permit applicatlon. The proposed envelope systems have been
deslgned to meet the 2018 IECC requirements ln CoMcheck Verslon 4.1.5.5 and to comply with any applicable mandatory
requirements llsted ln the lnspection Checklist.
Name - Tl$e Slgnature uare
f nvelope PASSI S: Design 17% better tlrarr code
Project Title:
Data filename; C:\Users\Robert Parrington\Documents\COMcheck\Broadhurst.cck
Report date: 12118/24
Page 2 ot 14
COMch eck Software Version 4. L.5.5
lnspection Checklist
Energy Code: 2018 IECC
Requirements: 0,0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Additional Comments/Assumptions:
I High lmpact (Tier 1)2 Medium lmpact (Tier 2)3 Low lmpact (Tjer 3)
Section
#
& Req.lD
Plan Review Complies?Comments/Assumptions
Plans and/or specifications provide all
information with which compliance
can be determined for the building
envelope and document where
exceptions to the standard are
claimed.
nComplies
lDoes Not
INot Observable
nNot npplicable
c103.2
lPR1l1
The vertical fenestration area <= 30
percent of the gross above-grade wall
area.
nComplies
!Does Not
nNot observable
flNot npplicable
c402.4.r
lPRloll
The skylight area <= 3 percent of the
gross roof area.
nComplies
[Does Not
ENot Observable
!Not Applicable
c402,4.r
IPR 1 111
ln enclosed spaces > 2,50A ft2
directly under a roof with ceiling
heights >15 ft, and used as an office,
lobby, atrium, concourse, corridor,
storage, gymnasium/exercise center,
convention center, automotive
service, manufacturing, non-
refrigerated warehouse, retail store,
distribution/sorting area,
transportation, or workshop, the
following requirements apply: (a) the
daylight zone under skylights is >=
half the floor area; (b) the skylight
area to daylight zone is >: 3 percent
with a skylight W >= 0.40; or a
minimum skylight effective aperture
>= 1 percent.
nc402.4.2
lPR1411
flNot observable
nNot npplicable
Complies
Does Not
Project Title: Broadhurst shop
Data filename: C:\Users\Robert Parrington\Documents\COMcheck\Broadhurst,cck
Report date: IO/29124
Page 3 of 9
*Fooung 1 Foundatlon lnspecuon Complles?Commen$/Assumptions
Exterior insulation protected
damage, sunlight, moisture,
landscaping and equipment
maintenance activities.
EDoes Not
INot Observable
Etrtot icable
pliesc303.2.1
lFo6l1
against
wind,
Additional Comments/Assumptions:
21h1)Medium I (Tier 2)3 Low lmpact (Tier 3)
Project Title:
Data filename
Broadhurst shop
C:\Users\Robert Parri n gton\Documents\COMcheck\Broadhurst.cck
Report date: LO/29124
Page 4 of 9
Section
#
& Req.lD
Framlng / Rough-ln lnspectlon Complles?Comments/Assumptions
c303.1.3
lFRt 212
Fenestration products rated in
accordance with NFRC.
nComplies
nDoes Not
!Not observable
nruot Applicable
c303.1.3
lFRl3lr
Fenestration products are certified as
to performance labels or certificates
provided.
IComplies
nDoes Not
INot Observable
!Not Applicable
C402.4,3 Vertical fenestration SHGC value
lFR10l1
DComplies See the Envelope Assemblies table for values.
lDoes Not
nNot Observable
nruot
c402.4.3,
c402.4.3.
4
lFR8l1
lnstalled vertical fenestration U-factor
and SHGC consistent with label
specifications and as reported in plans
and COMcheck reports.
plies See the Envelope Assemblies table for values.
tr Does Not
DNot Observable
!Not Applicable
c402.5.1
2.r
lFR19l1
The building envelope contains a
continuous air barrier that is sealed in
an approved manner and material
permeability <= 0.004 dtm6t2. Air
barrier penetrations are sealed in an
approved manner.
nComplies
lDoes Not
nNot Observable
Eruot npplicable
c402.5.2,
c402.5.4
lFR18l3
Factory-built fenestration and doors
are labeled as meeting air leakage
requirements.
!Complies
lDoes Not
nNot Observable
!Not Applicable
c402.5.7
lFR17l3
Vestibules are installed on all building
entrances. Doors have self-closing
devices.
nComplies
lDoes Not
INot Observable
lNot Applicable
Additional Comments/Assumptions:
1 Hi lm act (Tier 1)2 Medium lm ct (Tier 2)3 (Tier 3)Low
Project Title:
Data filename
Broadhurst shop
C :\Users\Robert Parri n gton\Documents\COMcheck\Broadhurst.cck
Report date
Page
LOl29l24
5of 9
Section
#
& Req.lD
Mechanlcal Rough-ln lnspectlon Complies?Comments/Assumptlons
c402,5.s,
c403.2.4.
3
lME313
Stair and elevator shaft vents have nComplies
motorized dampers that automatically nooes Not
close. Refernece section C403.7,7 for [Not observableoperational details' [Not Appricabre
c403.7.7
lMEsS j3
Outdoor air and exhaust systems have nComplies
motorized dampers that automatically DDoes Not
shut when not in use and meet
maximum leakage rates. Cneii. LJNot observable
gravitydamperiwhereallowed. LlNotApplicable
Reference section language for
operational details.
Additional Comments/Assumptions:
l-h tmpact er 1)2 Medium lmpact (Tier 2)3 Low lm ct (Tier 3)
Project Title:
Data filename
Broadhurst shop
C:\Users\Robert Parrington\Documents\COMcheck\Broadhurst.cck
Report date
Page
rol29l24
6of 9
Sectaon
#
& Req.lD
lnsulation lnspection Complies?Comments/Assumptions
Roof insulation installed per
manufacturer's instructions. Blown or
poured loose-fill insulation is installed
only where the roof slope is <:3 in
L2,
!Complies
nDoes Not
nNot Observable
!ruot Applicable
c303.1
ltN3ll
lnsulation installed on a suspended nComplies
ceiling having ceiling tiles is not being lDoes Not
specified for roor/ceiling assemblies.
continuous insutation oo.iJinri.lr"6 LlNot observable
in 2 or more layers with edge joints LJNot Applicable
offset between layers.
c402.2.L
ilN2011
Building envelope insulation is labeled ncomplies
with R-value or insulation certificate nDoes Not
providing R_value and other relevant !Not Observabledata nNot Appticabte
c303.1
ltN 1012
Above-grade wall insulation installed
per manufacturer's instructions.
nComplies
nDoes Not
!Not Observable
nNot Applicable
c303.2
ltN7l1
Exterior insulation is protected from
damage with a protective material.
Verification for exposed foundation
insulation may need to occur during
Foundation lnspection.
!Complies
lDoes Not
ENot Observable
nruot npplicable
c303.2.1
ltN 14 j2
lnstalled above-grade wall insulation
type and R-value consistent with
insulation specifications reported in
plans and COMcheck reports,
nComplies See the Envelope Assemblies table for values
lDoes Not
nNot Observable
nNot Applicable
Radiant panels and associated ncomplies
components, designed for heat lDoes Not
transfer from the panel surfaces to the
occupants or indoor tpt." .i.-- -- - - !f ot Observable
insulated with a minimum of R-3.5. UNot Applicable
c105
ltN6ll
c402.2.6
ltN18l3
lnstalled roof insulation type and R-
value consistent with insulation
specifications reported in plans and
COMcheck reports. For some ceiling
systems, verification may need to
All sources of air leakage in the
building thermal envelope are sealed
caulked, gasketed, weather stripped
or wrapped with moisture vapor-
permeable wrapping material to
[Complies See the Envelope Assemblies table for values.
lDoes Not
INot observable
lNot npplicable
occur durin Fram ln
minimize air leaka
iespl
no Notoes
n
c105
ltN2li
c402.5.r
I
lt N 111 nNot Observable
nNot Applicable
Additional Comments/Assumptions:
1 ct (Tier 1)Hi h 2 Medium I t (Tier 2)3 Low lmpact (Tier 3)
Project Title:
Data filename
Broadhurst shop
C :\Users\Robert Pa rrington\Docu ments\COMcheck\B roadhurst.cck
Report date
Page
L0129/24
7of 9
Section
#
& Req.lD
Flnal lnspection Complles?Comments/Assumptlons
Weatherseals installed on all loading nComplies
dock cargo door openings and provide EDoes Notdirect contact along the top and sides
of vehicles parked in tne oSoiwit:--- lNot observable- LJNot Applicable
c402.5.6
lFt37I1
Recessed luminaires in thermal
envelope to limit infiltration and be lC
rated and labeled, Seal between
interior finish and luminaire housing.
Does Not
resc402.5,8
lFI26l3
nNot Observable
flNot Applicable
Add itional Comments/Assu mptions :
1 High lmpact (Tier 1)2 Medium lmpact (Tier 2)3 Low lmpact (Tier 3)
Project Title:
Data filename
Broadhurst shop
C :\Users\Robert Parrin gton\Documents\COMcheck\Broadh urst.cck
Report date
Page
IOl29l24
8of 9