HomeMy WebLinkAboutBlower Door TestResidential Air Infiltration Test Report
Test date:2/24/2025
Project name:Puma Paw
Address:1771 CR 219
Garfield
Code:2018 IECC
Conditioned volume:26,640 Cubic Feet
Attic:vented/ unconditioned
Crawlspace:NA
Garage:excluded
Measured airflow:1,037 CFM50 Cubic Feet per Minute at 50 Pascal
Temperature; Inside:74
Temperature; Outside:42
Elevation:6,352
Corrected airflow:1,021 CFM50*Cubic Feet per Minute at 50 Pascal
2018 IECC maximum allowed leakage rate:3.0 ACH50 Air Changes Per Hour at 50 Pascal
Tested air leakage rate:2.3 ACH50 Air Changes Per Hour at 50 Pascal
Test code compliance:PASS
Test notes:
Tests were performed by Chris Taylor; Rated Field Inspector, RFIIN #CY5MPL
* Test results have been corrected for elevation and air density temperature differential.
Passes the 2018 IECC infiltration requirments.