Loading...
HomeMy WebLinkAboutBlower Door TestResidential Air Infiltration Test Report Test date:2/24/2025 Project name:Puma Paw Address:1771 CR 219 Garfield Code:2018 IECC Conditioned volume:26,640 Cubic Feet Attic:vented/ unconditioned Crawlspace:NA Garage:excluded Measured airflow:1,037 CFM50 Cubic Feet per Minute at 50 Pascal Temperature; Inside:74 Temperature; Outside:42 Elevation:6,352 Corrected airflow:1,021 CFM50*Cubic Feet per Minute at 50 Pascal 2018 IECC maximum allowed leakage rate:3.0 ACH50 Air Changes Per Hour at 50 Pascal Tested air leakage rate:2.3 ACH50 Air Changes Per Hour at 50 Pascal Test code compliance:PASS Test notes: Tests were performed by Chris Taylor; Rated Field Inspector, RFIIN #CY5MPL * Test results have been corrected for elevation and air density temperature differential. Passes the 2018 IECC infiltration requirments.