West Slope Testing & Inspection LtC
3177 Glendam Dr.
Grand Junction, CO 81504
Phone: 970-434'6988
Cell: 970-26A-2844
Ins ection R
Report #1
Page 1 of I
/o/ Z
rt
^7-5
Project: Metal Building 111 W. Main LLC
Address; 111 W. Main St. Silt, CO
Building Permit No.: BLCO-08-24-887 i
General Contractor: Rocky Mountain Steel Structures
lnspection of shop fabrication or field work nt iob site ; Field
Report;Inspected high strength A325 bolting at the pre-engineered metal
building main frame & portal fi'ame connections . Mezzanine framing was not yet
completed.
The high strength A325 bolting inspected, as noted above appeared to be in
substantial conformance with the plans & the AISC/RCSC Specification for high
strength bolting.
Further inspections should be performed on theMezzanine framing.
.a
e
-\
.\
.NInspector/Technician: Douglas E Young fi;IW
ffo*glao lE. Vrrung
I{;{J {,1*r{'ii'ieaiion #5 X 02 t?,4
S{:nal.t;f urar} Wci,Jin g Spcci*ll Xmspecton
$truqrfilr,nl $fi:ei Sr xlolfing i$pecial Hnspector
Sp,ray.n6piiecil i! ix,;rfl.CI{rtirre [ipeeietr Iuaspeefon
,i:it'i.:..,,,.i ..' :-: I i' !
|l,fl"Af? {] 5 .ffi?5
*
Eta -ag2/-887/
/,1/ er?m7+l-Bolf
West Slope Testing & trnspection I-l-C
3177 Glendam Dr.
Grand Junclion, CO 81504
Phone: 970-434-6988
Cell: 970-260-2844
Report #2
Page 1 of I
Zof Z
Final Insp ection Report
Date: l-21-25
Project: Metal Building I 1i W. Main LLC
Address: I i I W. Main St. Silt, C0
Buitding Permit Nn.: BLCO-08-24-887 i
General Contrnctor: Rocky Mountain Steel Structures
Inspection of shop fnbrication or fie ld work at iob site: Itiekl
Report: Inspected high strength 4325 bclting at the mezzanine fram ing for the
pre-engineered nretal building, and inspected field welded steel beatr connection
plates at the coiumns North side of mezzanine framing. Welder quaiifications &
w.p.s.ns were aiso verified.
The high strength A325 boiting & onsite welding itrspected, as noted above
appeared to be in su.bstantial confonraflce with the plans, and the quality
requirements of the AWS Dl.1 Structural Welding Code & the AISCLRCSC
Specification for high strength bolting.
To the best of my knowledge this completes the special inspections of the high
strength A3ZS boiting & structurai steel onsite welding on the prcrject, as outlinecl
in reports #l 8L#2.
N
't\
\\
a\
N
$Inspector/Teehnician: Douglas H Young fixtW
,i}i:'ylt i, fl' lil;telg
.'i-'i-' r. lr: Lii !ic:p iiqm #$ tr t:t'222 4
iitrr.ur.f l tsl r,V*f i i:i{{ Iipr:cial Ins pe*tor
i$f :i.il;:.j * ; r.: i $ti: rl e.li iil ti t i * fi ii p r:ainl f, n speeto r
$p;ny-a J:pilt:ii i;ir':r,ir^tx.rf i*1 fipeei*l Inspeelor
-.4^
.r".i'.,-, p P:l,lt!* t: \huns
'!:('i'd"ilg \.!vl lrrit,70
'''|
l''\,g- {..'li:' F.;j., iitlt1:t(}
$d,Al? ij .h ril?5