Project lnformation
Project #: Sweetwater ADU - Vickerman
Name: Sweetwater ADU - Vickerman
Location:TBID c.Dhuw 2.D I5o
ManualJ Load Summary
Total Heating: 45,591 Btu/hr
Outdoor Conditions
Location:
Elevation:
Latitude:
Dry Bulb:
Daily Range:
Wet Bulb:
Heating
-16.0'F
Infiltration
Method:
Stories:
Construction:
Exposure Category:
Num Fircplaces:
Net Air Changes (HeaVOool):
Net Flow (HeaUcool):
2924
Notes:
TotalSensible: 15,554 Btu/hr Total Latent: 200 Btu/hr
lndoor Conditions
(User Specified) Sweetwater
ADU,Colorado
7350',
. 39.8
Cooling
90.0'F
High
59"0 "F
Simple
2
Semi-Tight
Three or Four Exposures
1 (risht)
0.30 / 0.16
127 dm I 68 dm
Room Temp:
Design Temp Diff:
Humidity:
Moisture Diff (Grains)
Ventilation
Num Occupants:
Type:
ACH:
Outside Air:
Sensible Eff:
Heating
55-70"F
86.0 "F
1
Heating
Heat Recovery
0.19
81 cfm
50 o/o
Cooling
75 "F
15.0'F
45
-28.0
Type:
ACH:
Outside Air:
Sensible Eff:
Load Report
Manual J8 Load Calculation
P@ect #:Sweetwater ADU - Vickerman
February 07, 2025
Cooling
Heat Recovery
0.1 I
81 cfm
50 7o
Created Using LoopCAO 2024 (A7EO25')
Version:24.0.0280 R
Floorplan/Levels
Ground Floor
Main Floor
(1 ) AT: Differene between supply air and Eturn air
Length=ft Area=ff TempeEture='F Flowrate=
Head Loss = ft water RH = Radiant Floor Heating
Total Heated Area:
Total Cooled Area:
(2) Estimated
USGPM Air Flow = cfm
air flow based on specified supply air AT
Heat Loss = Btr/hr Unit Heat Loss = Btr/(hr.ftr)
BB = Baseboard FA = Fored Air OTH = Other Heating SM = Snowmelt
Rv = hr'ft"F/lrtu
N = Not Heated
,337
,337
2,674
2,674
ftz
fl2
ft2
ft2
See end of report for important Notes and Disclaimers
,6,nrH,n7 fi/u
Page 1 of8
Name:Sweetwater ADL - Vickerman
Project #:Sweetwater ADU - Vickerman
Constructions
Walls
Doors
Load Report
February 07, 2025
Cooling
1 ,515
0
Heating
11,626
202
Area
2,298
420
U-Value
0.064
0.064
Description
Frame Wall or Partition; Wood Framing; R-13 lnsulation in 2 x 4 Stud Cavity; R-5
Board lnsulation; Stucco or Wood Siding; Plus lnterior Finish
Frame Wall or Partition; Wood Framing; R-13 lnsulation in 2 x 4 Stud Cavity; R-5
Board lnsulation; Stucco orWood Siding; Plus lnterior Finish
Code
12C-5sw
1 2C-5sw
Coolinq
1,814
Heating
6,1 34
Area
144
U-Value
0.600
Code I Description
11J lMetal Door with Fiberglass Core
Floors
Coolinq
0
Heating
3,699
Area
147',-
4'(P)
U-Value
0.1 00
Description
22D - Vertical Board lnsulation Covers Slab Edge, Turns Under the Slab and
Extends Four Feet Horizontally, any Floor Cover
Code
22D-1Op
Coolinq
1,203
Heating
2,300
Area
1,337
U-Value
0.020
Description
FHA vented attic; No radiant banier over ceiling or same type of air space
behind an attic knee wall; R-50 lnsulation; Materials: Asphalt Shingles(a),
Metal(m), Tar / Gravel(x), Membrane(z); Colors: Dark(d);
Code
1 6B-50ad
Ceilings
Glazing
Windows
(1 ) AT: Difference tetween supply air and return air (2) Estimated air f ow based on specified supply air ATLength=ftArea=ff T€mpeEture='F Flowrate=USGPM AirFlow=6-fm HeatLoss=BtL/hr UnitHeatLoss=Btu/(hrff3)
HeadLoss=fiwater RH=RadiantFloorHeating BB=Bassboard FA=ForedAir OTH=OtherHeating Sw=Snowmelt
See end of report for important Notes and Disclaimers.
Created Using LoopCAD 2024 Qn 12025')
Version:24.0.0280 R
Cooling
904
24e
1,082
396
1,827
594
235
1,218
Heating
639
774
2,477
639
1,742
1,161
774
1.161
Area
20
20
107
30
68
45
30
45
SHGC
0.56
0,56
o.21
0.3
0.3
0.3
0.3
0.3
lJ-Value
0.45
0.45
0.27
0.30
0.30
0.30
0.30
0.30
Exposure
E
N
S
S
W
S
N
E
Description
Operable window or sliding glass door, with Emissivity of
Low-e coating = 0.40 - lnsulated Fiberglass Framing,
BlindsMedium45 (50%)
Operable window or sliding glass door, with Emissivity of
Low-e mating = 0.40 - lnsulated Fiberglass Framing,
BlindsMedium45 (50%)
, BlindsMedium45 (50%)
Sweetwater ADU Windows, BlindsMedium45 (50o/o)
SweetwaterADU Wndows, BlindsMedium45 (50%)
S\,veetwater ADU Wi ndows, Bli ndsMediu m45 (500/o)
Sweetwater ADU Wi ndows, Bli ndsMediu m45 (500/o)
Srveetwater ADU Windows, Bli ndsMediu m45 (500/o)
Code
3Af
3Af
Custom
SweetwaterADu Wndows
SweetwaterADU Wndows
SweetwaterADU Wndows
SweetwaterADU Wndows
Sweetwa(erADU Wndows
Rv = hr.ft'?,'Flbtu
N = Not Heatod
Page 2 of 8
Name:Sweetwater ADU - Vickerman
Project #:Sweetwater ADU - Vickerman
lnternal Loads
Description
Default (1,200 Btuh)
1 Occupants:
Total
Latent
Other Loads
Blower Load 1,706 Btu/hrSensible
1,200
230
1,430
200
200
(1 ) AT: Difieren€ between supply air and return air (2) Estimated air flow based on specified supply air AT
Length=ft Area=ff TempeEture='F Flowrate=USGPM AirFlow=cfm HeatLoss=Btu/hr UnitHeatLoss=Btu/(hr'ft')
Head Loss = ft water RH = Radiant Floor Heating BB = Baseboard FA = For@d Air OTH = Other Heating SU = Snowmelt
See end of report for important Notes and Disclaimers.
Load Report
February 07, 2025
Created Using LoopCAD 2O2a (21712025\
Version:24.0.0280 R
Page 3 of 8
Rv = hr'ff 'F/btu
N = Not Heated
Name:Sweetwater ADU - Vickerman
Project #:Sweetwater ADU - Vickerman
Load Breakdown
"Avemoe Load Procedure
Heatino AT1: 70.0
Coolino ATl: 18.0
Est. Heatinq CFM2: 765
Est. Coolinq CFM2: 1015
JSHR: 0.99
MJ8 Tons: 1.31
SqFt/Ton: 2037
CFM/SoFI: 0.38
Load Report
February 07, 2025
Created Using LoopCAD 2024 (2n PO25\
Version:24.0.0280 R
(1 ) AT: Difference between supply air and €turn air (2) Estimated air flow based on specified supply air ATLength=ftArea=ff Temperature='F Flowrate=USGPM AirFlow=cfm HeatLoss=Btu/hr UnitHeatLoss=Btu/(hr'fF)HeadLoss=ftwater RH=RadiantFloorHeating BB=Baseboard FA=ForcedAir OTH=OtherHeating SM=Snowmelt
See end of report for important Notes and Disclaimers.
Latent
200
0
0
200
Sensible
6,504
U
1,814
1 ,515
1,203
866
1,430
U
516
1,706
0
1 5,554
2,674 ft2
Heatinq
9,366
0
6,134
11,828
0
2,300
3,699
9,308
U
0
2,956
0
0
45,591
2,674 t(
Name
Windows*
Skylightst
Doors
Walls
Below Grade Walls
Ceilings
Floors
lnfiltration
lnternal
Other
Duct Loads
Ventilation
Humidification
Piping Load
Radiant Back Loss
Blower Heat
AED-
Total
Total Area
Rv = hr'ft'?.'F/btu
N = Not Heated
Page 4 of 8
Name:Sweetwater ADU - Vickerman
Project #:Sweetwater ADU - Vickerman
AED
Load Report
February 07,2025
Created Using LoopCAD 2Q24 (21712025)
Version:24.0.0280 R
121r
FeE*rdd ldd w Hour d Day - Blek Ldd {lunns)
Average Load: 8,696 Btu/hr
Excursion Limit: 11,304 Btu/hr
Peak Load: 1 1,036 Btu/hr
AED Load: 0 Btu/hr
(1 ) AT: Difierence between supply air and return air (2) Estimated air flow based on specified supply air ATLength=ftArea=ff Temperature='F Flowrate=USGPM AirFlow=cfm HeatLoss=Btr/hr UnitHeatLoss=Btu/(hrfl3)
Head Loss = ft water RH = Radiant Floor Heating BB = Baseboard FA = Forced Air OTH = Other Heating SU = Snowmelt
See end of report for important Notes and Disclaimers.
Rv = hr'ft' "F/btu
N = Not Heated
Page 5 of 8
Name:Sweetwater ADU - Vickerman
Project #:Sweetwater ADU - Vickerman
Heating Zones
Heating Rooms
* The sum of room loads may not be equal to the project total due to additional system loads.
Cooling Zones
Load Report
February 07,2025
Total Load
20,075
2,812
885
21,819
Room Temp
55
70
cA
70
Area
1,186
u
68
1,337
Zone
Zone 101
Zone 102
Zone 103
Zone 201
Total Load*
20,075
2,812
885
1.176
769
4,019
3,533
3,335
2,155
1,210
105
3,321
2,195
Room Temp
55
70
70
70
70
70
70
70
70
70
70
Area
1 ,186
84
68
93
71
221
175
on
138
130
38
314
65
Room
GARAGE
LOWER STAIR
MECH ROOM
BATH 1
BATH 2
BEDROOM 1
BEDROOM 2
DINING
ENTRY
KITCHEN
LAUNDRY
LIVING ROOM
UPPER STAIRS
Sensible Load
13,333
AED
YES
Room Temp
7E
Area
2,674
Zone
Entire Building
(Averaqe Load Procedure)
Cooling Rooms
(1 ) AT: Difference between supply air and return air (2) Estimated air flow based on specified supply air AT
Length=ftArea=ff Temperature='F Flowrate-USGPM AirFlow=cfm HeatLoss=Btr/hr UnitHeatLoss=Btu(hrfr,)
HeadLoss=ftwater RH=RadiantFloorHeating BB=Baseboard FA=ForcedAir OTH=OtherHeating SU=Snwmelt
See end of report for important Notes and Disclaimers.
Created Using LoopCAD 2024 (21712025')
Version:24.0.0280 R
Sensible Load*
5,025
251
112
588
164
2,072
AED
NO
YES
YES
NO
YES
NO
Room Temp
75
75
75
75
Area
1 .186
84
68
93
71
221
Room
GARAGE
LOWER STAIR
MECH ROOM
BATH 1
BATH 2
BEDROOM 1
Rv = hr'ff'F/btu
N = Not Heated
Page 6 of 8
2.045
1,750
554
279
54
1.956
947
NO
NO
YES
YES
YES
NO
NO
75
75
75
75
75
75
75
175
92
138
130
38
314
65
BEDROOM 2
DINING
ENTRY
KITCHEN
LAUNDRY
LIVING ROOM
UPPER STAIRS
Name:Sweetwater ADU - Vickerman
Project #:Sweetwater ADU - Vickerman
* (Average Load Procedure) The sum of room loads may not equal the prcject total due to variations in solar gain and system loads.
( 1) AT: Difieene betwen supply air and return air (2) Estimated air flow based on spsified supply air ATLength=ftArea=ft' TempeEture='F Flowrate=USGPM AirFlow=cfm HeatLoss=Btu/hr UnitHeatLoss=Btu/(hrft,)
HeadLoss=frwater RH=RadiantFloorHeating BB=Baseboard FA=ForedAir OTH=OtherHeating Strrt=Snowmelt
See end of repod for important Notes and Disclaimers.
Load Report
February 07,2025
Created Using LoopCAO 2024 (21712025)
Versiont24,0.0280 RRv=hrff'F/btu
N = Not Heated
Page 7 of I
Warnings
Name:Sweetwater ADU - Vickerman
Project #:Sweetwater ADU - Vickerman
Design Locaton
Location:
Province/State:
Country:
Outdoor Heating Design Temp:
Outdoor Cooling Design Temp:
MJSCustom
SweetwaterADU
Colorado
United States
-16.0 "F
90.0 "F
Load Report
February 07, 2025
Created Using LoopCAD 2024 (21712025\
Version:24.0.0280 R
Page I of I
Altitude:
Latitude:
Wet Bulb Temperature:
Daily Range:
7350' ft
39.8
59.0 'F
High
Disclaimers
ACCA, Manual J and Powered by ACCA Manual J are registered trademarks ofthe Air Conditioning Contractors ofAmerica. All rights reserved.
caretully, and to have the calculated results reviewed by an experienced heating professional to ensure reasonableness and suitability for your application.
IN NO EVENT WLL AVENIR SOFTWARE INC. (.AVENIR) OR ITS AFFILIATES BE LIABLE UNDER ANY CONTRACT, NEGLIGENCE, STRICT LIABILITY OR OTHER LEGAL OR EQUITABLE THEORY FOR ANY
OF BUSINESS INFORMATION OR DATA AND THE LIKE), EVEN IF SUCH PARTY HAS BEEN ADVISED OF THE POSSIBILIry OF SUCH DAMAGES. AVENIR'S CUMULATIVE LIABILIry FROM ANY CAUSE RELATED TO OR
ARISING FROM THE USE THIS REPORT, AND REGARDLESS OF THE FORM OF THE ACTION, SHALL BE LIMITED TO NO GREATER THAN THE AMOUNT OF FEES PAID TO AVENIR UNDER THE SOFTWARE LICENSE
AGREEMENT.
(1 ) AT: Differen€ between supply air and return air (2) Estimated air flow based on specified supply air ATLength=ftArea=ff Temperature='F Flowrate=USGPM AirFlow=cfm HeatLoss=Btr/hr UnitHeatLoss=Btu/(hrft,)
Head Loss = ft water RH = Radiant Floor Heating BB = Baseboard FA = Forced Air OTH = Other Heating Stvt = Snowmelt
See end of report for important Notes and Disclaimers.
Rv = hr'ff "F/btu
N = Not Heated