Inspection Report
Permit #:1014458 Date Inspected:12-MAR-25
Permit
Holder:JESSICA FAZZI
4361 GRASS MESA ROAD ANTLERS 81650
Phone: 9706251696 Fax:
Email: jessicawest926@yahoo.com
Site:4361 Grass Mesa Road Rifle County: Garfield
Owner:JESSICA FAZZI
JESSICA FAZZI Phone:9706251696
Status:PARTIAL
Inspection Type: Rough In Trim Permit:N
Constuction Type: NEW Building Type: RESIDENTIAL
Inspector:Lucas Newman 303-869-3474
Corrections:1. the shower fixture drain is S-trapped see cod section 909.1 and 909.2 909.1 Distance of trap from vent. Each
fixture trap shall have a protecting vent located so that the slope and the developed length in the fixture drain from
the trap weir to the vent fitting are within the requirements set forth in Table 909.1. Exception: The developed length
of the fixture drain from the trap weir to the vent fitting for self-siphoning fixtures, such as water closets, shall not be
limited. 909.2 Venting of fixture drains. The total fall in a fixture drain due to pipe slope shall not exceed the
diameter of the fixture drain, nor shall the vent connection to a fixture drain, except for water closets, be below the
weir of the trap.
Comments:1. corrections to the shower have been made and are OK 2. the corrections for the DWV in the crawl space have been
made and are approved excluding the shower fixture drain connection at the the point where it connects to the wet
vented fixture branch ( AKA lavatory drain ) 3. a pressure test or a flood test is required for the DWV in the crawl
space 4. all in wall DWV and domestic water with in the first floor remodel is approved for rough in
COLORADO STATE PLUMBING BOARD
1560 Broadway, Suite 1350
Denver, CO 80202
Inspection Report
Date Inspected: 02/27/2025
Permit #: 1014458
Permit Holder: JESSICA FAZZI JESSICA FAZZI 4361 GRASS MESA ROAD ANTLERS 81650 Phone: 9706251696 Fax: Email: jessicawest926@yahoo.com
Site: 4361 Grass Mesa Road Rifle, Garfield County,
Owner: JESSICA FAZZI
Status: Partial Inspection Type: Rough In NEW RESIDENTIAL
Inspector: Lucas Newman 303-869-3474
Corrections:
1. replace all sanitary tees installed on the horizontal drains with wyes also replace the pressure PVC
90 on the 1-1/2 fixture drains serving the lavatory's with approved drainage fittings see code section
706.7
706.3 Installation of fittings. Fittings shall be installed to guide sewage and waste in the direction of
flow. Change in direction shall be made by fittings installed in accordance with Table 706.3. Change
in direction by combination fittings, side inlets or increasers shall be installed in accordance
with Table 706.3 based on the pattern of flow created by the fitting. Double sanitary tee patterns shall
not receive the discharge of back-to-back water closets and fixtures or appliances with pumping
action discharge.
2. only 1 fixture drain is aloud to discharge upstream of the wet vented fixture drain see code section
912.1
912.1 Horizontal wet vent permitted. Any combination of fixtures within two bathroom groups located
on the same floor level is permitted to be vented by a horizontal wet vent. The wet vent shall be
considered to be the vent for the fixtures and shall extend from the connection of the dry vent along
the direction of the flow in the drain pipe to the most downstream fixture drain connection to the
horizontal branch drain. Each wet-vented fixture drain shall connect
independently to the horizontal wet vent. Only the fixtures within the bathroom groups shall connect to
the wet-vented horizontal branch drain. Any additional fixtures shall discharge downstream of the
horizontal wet vent.
The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.
3. install a diverter for the 2 shower valves
Comments:
1. see corrections
2. the domestic water is on test and OK
3. the domestic water is on working pressure
COLORADO STATE PLUMBING BOARD
1560 Broadway, Suite 1350
Denver, CO 80202
Inspection Report
Date Inspected: 03/04/2025
Permit #: 1014458
Permit Holder: JESSICA FAZZI JESSICA FAZZI 4361 GRASS MESA ROAD ANTLERS 81650 Phone: 9706251696 Fax: Email: jessicawest926@yahoo.com
Site: 4361 Grass Mesa Road Rifle, Garfield County,
Owner: JESSICA FAZZI
Status: Partial Inspection Type: Rough In NEW RESIDENTIAL
Inspector: Lucas Newman 303-869-3474
Corrections:
Comments:
1. The 1-1/2 pressure 90's on the lavatory sinks have been replaced with 1-1/2 long turn 90's
2. the in wall DWV is approved for rough in
3. the corrections for the DWV system in the crawl space will be inspected at a later date
4. the diverter valves for the 2 shower heads has not been installed. DO NOT COVER THE
SHOWER VALVE
5. it is OK to cover all in wall DWV ( drain waste and vent )
The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.
COLORADO STATE PLUMBING BOARD
1560 Broadway, Suite 1350
Denver, CO 80202
Inspection Report
Date Inspected: 03/12/2025
Permit #: 1014458
Permit Holder: JESSICA FAZZI JESSICA FAZZI 4361 GRASS MESA ROAD ANTLERS 81650 Phone: 9706251696 Fax: Email: jessicawest926@yahoo.com
Site: 4361 Grass Mesa Road Rifle, Garfield County,
Owner: JESSICA FAZZI
Status: Partial Inspection Type: Rough In NEW RESIDENTIAL
Inspector: Lucas Newman 303-869-3474
Corrections:
1. the shower fixture drain is S-trapped see cod section 909.1 and 909.2
909.1 Distance of trap from vent. Each fixture trap shall have a protecting vent located so that the
slope and the developed length in the fixture drain from the trap weir to the vent fitting are within the
requirements set forth in Table 909.1. Exception: The developed length of the fixture drain from the
trap weir to the vent fitting for self-siphoning fixtures, such as water closets, shall not be limited.
909.2 Venting of fixture drains. The total fall in a fixture drain due to pipe slope shall not exceed the
diameter of the fixture drain, nor shall the vent connection to a fixture drain, except for water closets,
be below the weir of the trap.
Comments:
1. corrections to the shower have been made and are OK
2. the corrections for the DWV in the crawl space have been made and are approved excluding the
shower fixture drain connection at the the point where it connects to the wet vented fixture branch
( AKA lavatory drain )
3. a pressure test or a flood test is required for the DWV in the crawl space
4. all in wall DWV and domestic water with in the first floor remodel is approved for rough in
The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.