HomeMy WebLinkAboutDuct Test ReportTesting Company: Name:C5 Energy Inspections Address:2215 Rosewood Ln Grand Junction, COLORADO 81505 Phone: 970-250-1352 C5EnergyInspections.com Technician: Name:Brian Chesney Credentials:BPI Certified ID #5068969 Email:c5energygj@gmail.com Building Information: Project ID:county rd 325 Address: Geo-Tag Data:Latitude: 39.481252 Longitude: -107.861732 Timestamp: 2025-02-20 10:51:43 Customer Information: Name: Address: Measured Leakage:0.82 CFM25/100 ft² Leakage Target:3.00 CFM25/100 ft² Compliance with Leakage Target:Pass Test ID:Duct test Purpose of Test:Duct Total (IECC) Measured CFM25:19.6 Conditioned Floor Area:2,396.0 ft²AH Flow: 0.0 cfm Coefficient (C):2.8 Exponent (n): 0.600 (assumed) Test Standard:RESNET 380 Total Duct Leakage Test Mode: Pressurize Test Characteristics:Time Average Period: 10 seconds Test Date and Time:2025-02-20 10:52:48 Duct Leakage Test Test Readings: Target (Pa)Duct (Pa)Fan (Pa)Flow (cfm)Config 25.0 25.5 -10.8 19.9 Ring 3 Test Equipment: Flow Device:Duct Blaster B Fan Pressure Gauge:DG1000 Serial #: 13229 Calibration Date: 2024-08-27 Deviations from Standard: None Comments: None Duct Leakage Test Page 2 of 2Report by TEC Auto Test 1.10.1 (4), © 2024 The Energy Conservatory, Inc.