Heat Calcs
I Rimledge Ranch Rev 2 - Permit HVAC Load Calculations for Carbondale, CO,81623 d Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCA Manual J 8th Edition, Version 2, and ACCA Manual D Rhvac Online Alius Design Corps Carbondale, CO * Elite Software Development, lnc Rimledge Ranch Rev 2 Pe Page2 Load Calculation Project Report General Project lnformation Project Title: Project Date: Designed By: Project Comment: Client City: Rimledge Ranch Rev 2 - Permit612712024 Greg Wentzell BLDG Permit Carbondale, CO,81623 Design Data Reference City: Building Orientation: Daily Temperature Range: Latitude: Elevation: Altitude Factor: Carbondale, Co, Colorado, United States Front door faces NW High 39 Degrees 6200 feet 0.795 Outdoor Outdoor Outdoor Rel.Hum 100o/o 41o/o lndoor Rel.Hum nla 50% lndoor Grains Difference nla 18 Dry Bulb Wet Bulb Dry Bulb Winter Summer -5 87 -5 68 70 75 Check ures Supply CFM: Square ft. of Room Area: Volume (ft') of Cond. Space Volume (ft3) (Total): 3,090 3,415 47,325 47,325 CFM per Square ft. Square ft. per ton: 0.905 519 Build Loads Total Heating Required lncluding Ventilation Air: Total Sensible Gain Total Latent Gain: Total Cooling Required lncluding Ventilation Air 82 59 6 65 250 Btuh 202 Btuh 333 Btuh 536 Btuh 82.250 MBH 90 o/o 10 o/o 5.46 Tons (Based 6.58 Tons (Based Capacity) On Sensible + Latent) On75% Sensible Notes Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use And weather may vary. Be sure to select a unit that meets both sensible And latent loads according to the manufacturer's performance data at your design conditions. Miscellaneous System 1 Great Room SSHP lnput Data Outdoor Dry Bulb Outdoor Wet Bulb Outdoor Rel.Hum lndoor Rel.Hum lndoor Dry Bulb Grains Difference Winter: Summer: 70 75 nla-5 87 _4 68 100o/o 41o/o 50o/o nla 17.56 System 2 Master Wing SSHP lnput Data Outdoor Dry Bulb Outdoor Wet Bulb Outdoor Rel.Hum lndoor Rel.Hum lndoor Dry Bulb Grains Difference Winter: Summer: 70 75 nla 87 -5 68 100o/o 410h 50o/o nla 17.56 Rhvac Online Alius Design Corps Carbondale, CO * Elite Sofiware Development, Rimledge Ranch Rev 2 Page 3 System 3 Guest Wing SSHP lnput Data Outdoor Dry Bulb Outdoor Wet Bulb Outdoor Rel.Hurn lndoor Rel.Hum lndoor Dry Bulb Grains Difference Winter: Summer: -5 87 70 75 nla-5 68 100% 41%500h nla 17.56 Outside Air Data lnfiltration Specified: lnfiltration Actual: Above Grade Volume: Total Building lnfiltration: Total Building Ventilation Winter 0.100 79 0.000 x 47.325 0 x 0.0167 0 235 AC/hr CFM AC/hr ft3 ft"/hr CFM CFM Summer 0.050 39 0.000 x 47.325 0 x 0.0167 0 235 AC/hr CFM AC/hr ft3 ft3/hr CFM CFM --System 1-- lnfil. & Vent. Sensible Gain Multiplie r: 10.50 = (1 .10 X 0.795 X 12.00 Summer Temp. Diff.) lnfil. & Vent. Latent Gain Multiplier: 9.50 = (0.68 X 0.795 X 17.56 Grains Difference) lnfil. & Vent. Sensible Loss Multiplier: 6 5.62 = (1 .10 X 0.795 X 75.00 Winter Temp. Difference) Winter lnfiltration Specified: 0.100 AC/hr (50 CFM), Construction: Tight Summer lnfiltration Specified: 0.050 AC/hr (25 CFM), Construction: Tight --System 2-- lnfil. & Vent. Sensible Gain Multiplier 10.50 = (1.10 X 0.795 X 12.00 Summer Temp. Diff.) lnfil. & Vent. Latent Gain Multiplier: 9.50 = (0.68 X 0.795 X 17.56 Grains Difference) lnfil. & Vent. Sensible Loss Multiplier: 65.62 = (1.10 X 0.795 X 75.00 Winter Temp. Difference) Winter lnfiltration Specified: 0.100 AC/hr (13 CFM), Construction: Tight Summer lnfiltration Specified: 0.050 AC/hr (7 CFM), Construction: Tight --System 3-- lnfil. & Vent. Sensible Gain Multiplie r: 10.50 = (1 .10 X 0.795 X 12.00 Summer Temp. Diff.) lnfil. & Vent. Latent Gain Multiplier: 9.50 = (0.68 X 0.795 X 17.56 Grains Difference) lnfil. & Vent. Sensible Loss Multiplier: 6 5.62 = (1 .10 X 0.795 X 75.00 Winter Temp. Difference) WinterlnfiltrationSpecified: 0.100AC/hr(15CFM),Construction:Tight Summer lnfiltration Specified: 0.050 AC/hr (8 CFM), Construction: Tight l I I i I l. I i I I I i ir I ll,]ri ji ir',,/:;l ral I I I r.lirll(:l l.;l f') 11iil.l nl i, I ii.! i1 1 1 ir;r; [o1r I |] d:.1rr]!l irt i.iir,r.v f'l II ll'liitrli'r 4 i.llltirtlrt ir ;lll Ii rilr r I'l ;l), lil, ir rr /r,lll,r ) r', r,,rr t,l..ll '. rr ;r ) ii ;: : )r ir r:ll, ;l', ; ,,rr:;; rr:;;.11iir r i r'1 r ; i\,':.liii rl r ) ,. J . : ' ...\ i.:, I, , ii) | iir l,l,: I i i, ll,i i(,ii liirl tr,t i lrir| l r i i'r.iL.)r i:L !fl' li ii i:, l 1 1 Supply Return Aftic Attic 168 168 0.12 0.24 6 6 502.2 186 No No 1 1 Supply Return Attic Attic 168 168 0.12 o.24 6 6 191.7 71 No No 1 1 Supply Return Attic Attic 168 168 0.12 0.24 6 6 228.1 84,5 No No ,,,\.| l] ,-iir:llii.rtl i'iLtil i I irJ.,t i..:.ir iI r l;;lLii ,. \t i 1r,L l't ') t: lir ) ili ';7 r1r ;Jr.tr)(,lt ', , lii,:,',,1,1,.,lrjr'.i' .l iltr'ilil;iillr,): 11, ;1.i'r1 ;1r'r;;',.'i : rr lr;,.ittiL,)irl t:1t,., '1'ri;,i I11,,11 ,1 )1.y'1; 1,,;'1,r :.1(jl,(lt :..i(:j ,\irt:,lrliit.. ir't ,ir,:l:iiiriltl li,r ii'I:'lr' r'.r :ll l' ' i.,r1ri 1111 I ,liitllr: r 1:;;'ilr,:1r 1,.' I rli f i':,i( I ,t'lt' jrji ifl(: , tti iil Il r r I i; lliir'lr r Total Building Summary Loads Rhvac Online Alius Design Corps Carbondale, CO s Elite Software Development, Rimledge Ranch Rev 2 Pe Page 5 Component Description Area Quan Sen Loss Lat Sen Gain Total GainGain IECC: Glazing-2018_IECC_glass, U-value 0.3, SHGC 0.3 doors: Glazing-glass_doors, U-value 0.5, SHGC 0.35 IECC: Wall-Frame, Custom, 2018_iecc_flr, U-value 0.054 IECC: Roof/Ceiling-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, 2018_iecc-rf, U-value 0.02 IECC: Floor-Over enclosed crawl space, Custom, 201 8_iecc_cs_flr, U-value 0. 03 Subtotals for structure: People: 14 Equipment: Lighting: 4.2 Ductwork: lnfiltration: Winter CFM: 0, Summer CFM: 0 Ventilation: Winter CFM: 235, Summer CFM: 235 AED Excursion: Total Building Load Totals: 772.5 319 3275.5 3635 3415 17,381 11,964 13,264 5,453 4,803 52,865 23,988 0 5,397 0 82,250 17,220 9,056 3,274 946 17,220 9,056 3,274 946 769 0 0 0 0 0 0 2,800 0 1,301 0 2,232 0 6,333 769 31,265 3,220 5,266 14 12,127 0 864 6,447 59,202 31,265 6,020 5,266 14 13,428 0 3,096 6,447 65,536 Check Figures Supply Square Volume Volume 3,090 3,415 47,325 47,325 0.905 519 CFM: ft. of Room Area: CFM per Square ft. Square ft. perton: of Cond. Space Total Heating Required lncluding Ventilation Air: Total Sensible Gain Total Latent Gain: Total Cooling Required lncluding Ventilation Air 250 Btu 202 Btu 333 Btu 536 Btu 82 59 6 65 h h h h 82.250 MBH 90 o/o 10 o/o 5.46 Tons (Based On Sensible + Latent) 6.58 Tons (Based On75% Sensible Capacity) Notes Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use And weather may vary. Be sure to select a unit that meets both sensible And latent loads according to the manufacturer's performance data at your design conditions. Building Loads 1 Great Room SSHP Summary Loads Rhvac Online Alius Design Corps Carbondale, CO Elite Software Development, I3Rimledge Ranch Rev 2 Pe Page 6 Component Area Quan Sen Loss Lat Gain Sen Gain Total Gainn IECC: Glazing-2018-IECC-glass, U-value 0.3, SHGC 0.3 doors: Glazing-glass_doors, U-value 0.5, SHGC 0.35 IECC: Wall-Frame, Custom, 201 8-iecc-flr, U-value 0.054 IECC: Roof/Ceiling-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, 2018-iecc-rf, U-value 0.02 IECC: Floor-Over enclosed crawl space, Custom, 20'l 8_iecc_cs_fl r, U-value 0.03 Subtotals for structure: People: 6 Equipment: Lighting: 1.8 Ductwork: lnfiltration: Winter CFM: 0, Summer CFM: 0 Ventilation:Winter CFM: 115, Summer CFM: 115 AED Excursion: 536 197 1118 2080 1 860 12,060 7,388 4,527 3,120 11,394 5,286 1,117 541 419 11,394 5,286 1,117 541 419 0 0 0 0 2,616 29,711 13,072 0 2,641 0 45,425 0 1,200 0 0 707 0 1,092 0 3,000 18,757 1,380 4,333 6 6,628 0 423 6,'180 37,706 18,757 2,580 4,333 6 7,336 0 1,515 6,180 40,7061 Great Room SSHP Load Totals: Supply CFM: Square ft. of Room Area: Volume (ft3) of Cond. Space: Volume (ft')(Total): 1,997 1,860 30,220 30,220 CFM per Square ft Square ft. per ton: 1.074 444 Check Figures System Loads Total Heating Required lncluding Ventilation Air: Total Sensible Gain Total Latent Gain: Total Cooling Required lncluding Ventilation Air 45.425 MBH 93 o/o 7% 3.39 Tons (Based On Sensible + Latent) 4.19 Tons (Based On75% Sensible Capacity) 45,425 Btuh 37,706 Btuh 3,000 Btuh 40,706 Btuh Notes Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use And weather may vary. Be sure to select a unit that meets both sensible And latent loads according to the manufacturer's performance data at your design conditions. Rhvac Online Alius Design Corps Carbondale, CO s Elite Software Development, Rimledge Ranch Rev 2 7 System 2 Master Wing SSHP Summary Loads Component Description Area Quan Sen Loss Lat Gain Sen Total GainGain IECC: Glazing-2018_IECC_glass, U-value 0.3, SHGC 0.3 doors: Glazing-glass_doors, U-value 0.5, SHGC 0.35 IECC: Wall-Frame, Custom, 201 8_iecc_flr, U-value 0.054 IECC: Roof/Ceiling-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, 2018_iecc_rf, U-value 0.02 IECC: Floor-Over enclosed crawl space, Custom, 20 1 8_iecc_cs_flr, U-value 0.03 Subtotals for structure: People: Equipment: Lighting: Ductwork: lnfiltration: Winter CFM: 0, Summer CFM: 0 Ventilation: Winter CFM: 40, Summer CFM: 40 System 2 Master Wing SSHP Load Totals: 152.5 80 1062.5 710 3,431 3,000 4,303 'r,065 0 0 0 0 4,064 2,667 1,062 185 4,064 2,667 1,062 185 710 998 12,797 0 160 160 2 0 400 0 8,138 460 933 2 2,518 0 147 12,198 8,138 860 933 2 2,788 0 527 13,248 0.6 5,011 0 919 18,727 270 0 380 1,050 Check Figures Supply CFM: Square ft. of Room Area: Volume (ft") of Cond. Space Volume (ft") (Total): 638 CFM per Square ft. Square ft. per ton: 0.899 5247 7,8 7,8 10 10 10 System Loads Total Heating Required lncluding Ventilation Air: Total Sensible Gain Total Latent Gain: Total Cooling Required lncluding Ventilation Air 1 1 8,727 Btuh 2,198 Btuh 1,050 Btuh 3,248 Btuh 18.727 MBH 92 o/o 8 o/o 1 .10 Tons (Based On Sensible + Latent) 1 .36 Tons (Based On 75% Sensible Capacity) 1 Notes Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use And weather may vary. Be sure to select a unit that meets both sensible And latent loads according to the manufacturer's performance data at your design conditions. System 3 Guest Wing SSHP Summary Loads Rhvac Online Alius Design Corps Carbondale, CO * Elite Softrare Development, Rimledge Ranch Rev 2 8 Component Area Quan Sen Lat Gain Sen Gain Total GainLoss IECC: Glazing-2018_IECC_glass, U-value 0.3, SHGC 0.3 doors: Glazing-glass_doors, U-value 0.5, SHGC 0.35 IECC: Wall-Frame, Custom, 20'l 8_iecc_flr, U-value 0,054 IECC: Roof/Ceiling-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, 2018_iecc_rf, U-value 0.02 IECC: Floor-Over enclosed crawl space, Custom, 201 8_iecc_cs_flr, U-value 0.03 Subtotals for structure: People: 6 Equipment: Lighting: 1.8 Ductwork: lnfiltration: Winter CFM: 0, Summer CFM: 0 Ventilation: Winter CFM: 80, Summer CFM: 80 AED Excursion: System 3 Guest Wing SSHP Load Totals: 84 42 1 095 845 1,762 1,103 1,095 220 1,762 1,103 1,095 220 845 1,890 1,576 4,434 1,268 1,189 10,357 5,904 0 1,837 0 18,098 0 0 0 0 324 0 760 0 2,284 0 190 4,370 1,380 0 6 2,980 0 294 267 9,297 190 4,370 2,580 0 6 3,304 0 1,054 267 11 ,581 0 1,200 0 Check Figures Supply CFM: Square ft. of Room Area: Volume (ft') of Cond. Space: Volume (ft3)(Total): 455 845 295 295 CFM per Square ft. Square ft. per ton: 0.538 8'18 9I System Loads Total Heating Required lncluding Ventilation Air: Total Sensible Gain Total Latent Gain: Total Cooling Required lncluding Ventilation Air 18.098 MBH 80% 20 o/o 0.97 Tons (Based On Sensible + Latent) 1.03 Tons (Based On 75o/o Sensible Capacity) 18,098 Btuh 9,297 Btuh 2,284 Bluh 11 ,581 Btuh Notes Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use And weather may vary. Be sure to select a unit that meets both sensible And latent loads according to the manufacturer's performance data at your design conditions. Rhvac Online Alius Design Corps Carbondale, CO s Elite Software Development, I Rimledge Ranch Rev 2 Pe Page 9 System 1, Zone 1 Summary Loads (Peak Load Procedure for Rooms Component Description Area Quan Sen Loss Lat Gain Sen Gain Total Gain IECC: Glazing-2018_IECC_glass, U-value 0.3, SHGC 0.3 IECC: Wall-Frame, Custom, 201 8_iecc-flr, U-value 0.054 IECC: Roof/Ceiling-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, 2018_iecc-rf, U-value 0.02 IECC: Floor-Over enclosed crawl space, Custom, 201 8_iecc_cs_fll U-value 0. 03 Subtotals for structure: People: 2 Equipment: Lighting: 0.6 Ductwork: lnfiltration: Winter CFM: 0, Summer CFM: 0 System 1, Zone 1 Load Totals: 36 68 80 80 810 275 120 0 0 0 828 68 21 18 828 68 21 113 1 ,318 0 0 400 0 0 0 400 18 1 443 0 761 935 460 1,733 2 442 0 4,207 935 860 1,733 2 442 0 4,607 Check Figures Supply CFM: Square ft. of Room Area: Volume (ft") of Cond. Space: Volume (ft")(Total): 240 80 1,040 1,040 CFM per Square ft. Square ft. per ton: 3.005 156 Zone Loads Total Heating Required Total Sensible Gain Total Latent Gain: Total Cooling Required 1 4 4 ,761 ,207 400 ,607 Btu Btu Btu Btu h h h h 1.761 MBH 91 o/o I o/o 0.38 Tons (Based On Sensible + Latent) 0.51 Tons (Based On 75o/o Sensible Capacity) Notes Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use And weather may vary. Be sure to select a unit that meets both sensible And latent loads according to the manufacturer's performance data at your design conditions. 1, Zone 4 Loads (Peak Load Procedure for Rooms IECC: Floor-Over enclosed crawl space, Custom, 201 8_iecc_cs_fl r, U-value 0.03 180 253 Subtotals for structure: People: Equipment: Lighting: Ductwork: lnfiltration: Winter CFM: 0, Summer CFM: 0 253 0 0 0 41 41 0 0 2 6 0 58 0 0 0 2 b 0 0.6 85 0 0 0 0 m 1, Zone 4 Load Totals Supply Square Volume Volume CFM: ft. of Room Area: 3 180 ,980 ,980 CFM per Square ft. Square ft. per ton: 0.018 37,330 ofCond. Space 1 1 Total Heating Required: Total Sensible Gain 338 Btuh 58 Btuh 0 Btuh 58 Btuh 0.338 MBH 100 % 0 o/o 0.00 Tons (Based On Sensible + Latent) 0.00 Tons (Based On75% Sensible Capacity) Total Latent Gain: TotalCooling Required Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCAManualJ 8th Edition, Version 2, andACCAManualD. All computed results are estimates as building use And weather may vary. Be sure to select a unit that meets both sensible And latent loads according to the manufacturer's performance data at your design conditions. Rhvac Online Alius Design Corps Carbondale, CO ffi Elite Software Development, Rimledge Ranch Rev 2 Page 11 System 1, Zone 5 Summary Loads (Peak Load Procedure for Rooms) Gomponent Description Area Quan Sen Lat Sen Gain Total GainLossGain IECC: Glazing-20'18_IECC_glass, U-value 0.3, SHGC 0.3 doors: Glazing-glass_doors, U-value 0.5, SHGC 0.35 IECC: Wall-Frame, Custom, 201 8_iecc_flr, U-value 0.054 IECC: Roof/Ceiling-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, 201 8_iecc_rf, U-value 0.02 IECC: Floor-Over enclosed crawl space, Custom, 20 1 8_iecc_cs_flr, U-value 0.03 Subtotals for structure: People: 4 Equipment: Lighting: 0.6 Ductwork: lnfiltration: Winter CFM: 0, Summer CFM: 0 System 1, Zone 5 Load Totals: 500 197 1 050 2000 11,250 7,388 4,252 3,000 0 0 0 0 14,695 7,118 1,049 520 14,695 7,118 1,049 520 1 600 2,250 28,140 0 360 360 0 800 0 23,742 920 2,600 2 3,849 0 36,649 23,742 1,720 2,600 2 3,849 0 37,449 9,455 0 37,595 0 0 800 Check ures Supply CFM: Square ft. of Room Area: Volume (ft") of Cond. Space: Volume (ft3) (Total): 2, 1, 27, 27, 094 600 200 200 CFM per Square ft Square ft. per ton: '1.309 474 Zone Loads Total Heating Required Total Sensible Gain Total Latent Gain: Total Cooling Required 37,595 Btuh 36,649 Btuh 800 Btuh 37,449 Btuh 37.595 MBH 98% 2 o/o 3.12 Tons (Based On Sensible + Latent) 3.38 Tons (Based On 75o/o Sensible Capacity) Notes Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use And weather may vary. Be sure to select a unit that meets both sensible And latent loads according to the manufacturer's performance data at your design conditions. Rhvac Online Alius Design Corps Carbondale, CO * Elite Software Development, Rimledge Ranch Rev 2 Pe e12 System 2, Zone 1 Loads (Average Load Procedure for Rooms) Component Description Area Quan Sen Loss Lat Sen Gain Total GainGain IECC: Glazing-2018_IECC_glass, U-value 0.3, SHGC 0.3 doors: Glazing-glass_doors, U-value 0.5, SHGC 0.35 IECC: Wall-Frame, Custom, 201 8_iecc-flr, U-value 0.054 IECC: Roof/Ceiling-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, 2018-iecc-rf, U-value 0.02 IECC: Floor-Over enclosed crawl space, Custom, 201 8_iecc_cs_flr, U-value 0.03 Subtotals for structure: People: 2 Equipment: Lighting: 0.6 Ductwork: lnfiltration: Winter CFM: 0, Summer CFM: 0 System 2, Zone 1 Load Totals: 152.5 80 1062.5 710 3,431 3,000 4,303 1,065 0 0 0 0 4,064 2,667 1,062 185 4,064 2,667 1,062 185 710 998 12,797 0 160 160 0 400 0 8,138 460 933 2 1,633 0 11,166 8,138 860 933 2 1,633 0 11 ,566 3,826 0 16,623 0 0 400 Check Supply CFM: Square ft. of Room Area: Volume (ft") of Cond. Space: Volume (ft") (Total): 638 CFM per Square ft. Square ft. per ton: 0.899 6707 7,8 7,8 '10 '10 10 Zone Loads Total Heating Required TotalSensible Gain Total Latent Gain: Total Cooling Required 16,623 Btuh 11 ,166 Btuh 400 Btuh 11 ,566 Btuh 16.623 MBH 97 o/o 3% 0.96 Tons (Based On Sensible + Latent) 1.06 Tons (Based On 75o/o Sensible Capacity) Notes Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use And weather may vary. Be sure to select a unit that meets both sensible And latent loads according to the manufacturer's performance data at your design conditions. Rhvac Online Alius Design Corps Carbondale, CO * Elite Softrare Development, Rimledge Ranch Rev 2 13 System 3, Zone 1 Summary Loads (Average Load Procedure for Rooms) Component Description Area Quan Sen Loss Lat Gain Sen Gain Total Gain IECC: Glazing-2018_IECC_glass, U-value 0.3, SHGC 0.3 doors: Glazing-glass_doors, U-value 0.5, SHGC 0.35 IECC: Wall-Frame, Custom, 2018_iecc_flr, U-value 0.054 IECC: Roof/Ceiling-Roof Joists Between Roof Deck and Ceiling or Foam Encapsulated Roof Joists, Custom, 2018_iecc_rf, U-value 0.02 IECC: Floor-Over enclosed crawl space, Custom, 201 8_iecc_cs_flr, U-value 0. 03 Subtotals for structure: People: 6 Equipment: Lighting: 1.8 Ductwork: lnfiltration: Winter CFM: 0, Summer CFM: 0 System 3, Zone 1 Load Totals: 84 42 1 095 845 1,890 1,576 4,434 1,268 0 0 0 0 1,762 1,103 1,095 220 1,762 1,103 1,095 220 845 1,189 '10,357 0 190 190 4,370 2,580 0 1,200 0 4,370 1,380 0 6 1,934 0 7,958 0 6 1,934 0 9,1 58 4,510 0 14,867 0 0 1,200 Check Figures Supply CFM: Square ft. of Room Area: Volume (ft3) of Cond. Space Volume (ft") (Total): 455 845 9,295 9,295 CFM per Square ft. Square ft. per ton: 0.538 1,058 Zone Loads Total Heating Required; Total Sensible Gain 14, 7, I, 867 Btuh 958 Btuh 200 Btuh 14.867 MBH 87 o/o 13 Vo 0.76 Tons (Based On Sensible + Latent) 0.80 Tons (Based On 75o/o Sensible Capacity) Total Latent Gain: Total Cooling Required 9,158 Btuh Notes Rhvac Online ls an ACCA approved Manual J, D And S computer program. Calculations are performed perACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use And weather may vary. Be sure to select a unit that meets both sensible And latent loads according to the manufacturer's performance data at your design conditions. Rhvac Online Alius Design Corps Carbondale, CO * Elite Software Development, Rimledge Ranch Rev 2 Page 14 Detaited Room Loads - Room 6 - Office (Peak Fenestration Gain Procedure) General Room is in zone 1, which peaks at 9 am Calculation Mode: Room Length: Room Width: Area: Ceiling Height: Volume: Actual Winter lnfil.: Actual Summer lnfil.: Htg. & clg. nla nla 80.0 sq.ft. 13.0 ft. 1,040 cu.ft. O CFM O CFM Occurrences: System Number: Zone Number: Supply Air: Supply Air Changes: Actual Winter Vent.: Percent of Supply.: Actual Summer Vent. Percent of Supply: 1 1 1 240 13.9 5 2 12 5 CFM AC/hr CFM o/o CFM Yo NE-Wa||-IECC 8 X 13 NE-Gls-IECC shgc-O.3 0%S UP-Roof-IECC 80 X 1 Floor-IECC 1 X 80180 Subtotals for Structure: lnfil.:Win.: 0.0, Sum.: 0.0 Ductwork: AED Excursion: People: 200 laUper, 230 sen/per: Equipment: Lighting: Room Totals: 68 36 80 80 104 0.054 0.300 0.020 0.030 4.1 22.5 1.5 1.4 275 810 120 113 1 ,318 0 443 1.0 23.0 0.3 0.2 0 0 0 0 0 0 68 828 21 '18 935 0 442 635 460 1,733 2 4,207 0.000 0.000 2 400 0 1 1,761 400 Computer and monitor Laser printer Color television Total 1,536 512 683 0 0 0 35 100 100 100 100 100 538 512 683 1,733 0 0 0 0 Item Area -u-Htg HTM Sen clg HTM Lat Sen GainonValueLossGain Equipment Cooling Loads Item Name Cont. Output Sensible Btuh Cont. Output Latent Btuh Average ln-Use Output Percent Used per Hour Sensible Load Btuh Latent Load Btuh Detailed Room Loads - Room 1 - Mudroom (Peak Fenestration Gain Procedure) Room is in zone 4, which peaks at 7 pm Calculation Mode: Room Length: Room Width: Area: Ceiling Height: Volume: Actual Winter lnfil.: Actual Summer lnfil.: Htg. & clg. nla nla 180.0 11.0 1,980 0 0 sq.ft. ft. cu.ft. CFM CFM Occurrences: System Number: Zone Number: SupplyAir: SupplyAir Changes: Actual WinterVent.: Percent of Supply.: Actual SummerVent.: Percent of Supply: 1 1 4 3 CFM 0.1 AC/hr 1 CFM 30 o/o O CFM 5 o/o Floor-IECC 1X 1801180 Subtotals for Structure: lnfil.: Win.: 0.0, Sum.: 0.0 Ductwork: AED Excursion: Lighting: Room Totals: 180 0.030 253 253 0 85 0.2 0 0 0 41 41 0 6 9 2 58 0 0.000 0.000 338 0 Rhvac Online Alius Design Corps Carbondale, CO s Elite Software Development, Rimledge Ranch Rev 2 16 Detailed Room Loads - Room 5 - Kitchen-Living (Peak Fenestration Ga i n Proced u re General Room is in zone 5, which peaks at 5 pm Calculation Mode; Room Length: ' Room Width: Area: Ceiling Height: Volume: Actual Winter lnfil.: Actual Summer lnfil.: Htg. & clg. nla nla 1,600.0 17.0 27,200 0 0 sq.ft. ft. cu.ft. CFM CFM Occurrences: System Number: Zone Number: Supply Air: Supply Air Changes: Actual Winter Vent.: Percent of Supply.: Actual Summer Vent Percent of Supply: 1 I 5 2,094 4.6 109 5 103 5 CFM AC/hr CFM o/o CFM o/o NW-Wa||-IECC 65 X 13 SE-Wa||-IECC 50 X 13 NW-Wa||-IECC 36 X 7 NW-Gls-IECC shgc-0.3 0%S SE-Gls-IECC shgc-0.3 0%S SE-Gls-doors shgc-0.35 0%S NW-Gls-IECC shgc-0.3 0%S NW-Gls-doors shgc-0.35 0%S UP-Roof-IECC 2000 X 1 Floor-IECC 1 X 160011600 Subtotals for Structure: lnfil.:Win.: 0.0, Sum.: 0.0 Ductwork; AED Excursion: People: 200 laVper, 230 sen/per: Equipment: Lighting: Room Totals: 329 559 162 90 70 21 340 176 2000 1 600 0.054 0.054 0.054 0.300 0.300 0.500 0.300 0.500 0.020 0.030 4.1 4.1 4.1 22.5 22.5 37.5 22.5 37.5 1.5 1.4 1,332 2,264 656 2,025 1,575 788 7,650 6,600 3,000 2,250 28,140 0 9,455 '1.0 1.0 1.0 30.6 21.7 26.9 30.6 37.2 0.3 0.2 0 0 0 0 0 0 0 0 0 0 0 0 329 558 162 2,757 1,522 564 10,416 6,554 520 360 23,742 0 3,849 5,536 920 2,600 2 36,649 1,747 0.000 0.000 4 800 0 1 37,595 800 Whole House DefaultAppliance Load, Refrigerator and range with vented hood. Note: 1200 Btuh applied to the kitchen. Whole House Scenario Adjustment Option D, Large family using TVs, stereos, computers and laundry room during the late afternoon in midsummer. Note: This is an additional 410 watt allowance forAA/ or computer equipment. Total 1,200 0 100 100 1,200 0 1,400 0 100 100 1,400 0 0 Item Area Quantity -u- Value Htg HTM Sen Loss clg HTM Lat Sen GainGain Equipment Cooling Loads Item Name Cont. Output Sensible Btuh Cont. Output Latent Btuh Average ln-Use Output Percent Used per Hour Sensible Load Btuh Latent Load Btuh 2,600 Rhvac Online Alius Design Corps Carbondale, CO s Elite Software Development, I Rimledge Ranch Rev 2 Page 17 Detailed Room Loads - Room 7 - Master_Bed (Average Load Procedure General Calculation Mode: Room Length: Room Width: Area: Ceiling Height: Volume: ActualWinter lnfil.: Actual Summer lnfil.: Htg. & clg. nla nla 710.0 11 .0 7,810 0 0 sq.ft. ft. cu.ft. CFM CFM Occurrences: System Number: Zone Number: SupplyAir: Supply Air Changes: Actual Winter Vent.: Percent of Supply.: Actual Summer Vent. Percent of Supply: 1 2 1 638 4.9 40 6 40 6 CFM AC/hr CFM o/o CFM oa NW-Wa||-IECC 35 X 13 SE-Wa||-IECC 30 X 13 SW-Wa||-IECC 30 X 15 NW-Gls-IECC shgc-0.3 0%S SE-Gls-doors shgc-0. 35 0%S SE-Gls-IECC shgc-0.3 0%S SW-Gls-IECC shgc-O.3 0%S UP-Roof-IECC 710 X 1 Floor-IECC 1X7101710 Subtotals for Structure: lnfil.:Win.: 0:0, Sum.: 0.0 Ductwork: People: 200 lat/per, 230 sen/per: Equipment: Lighting: Room Totals: 442.5 220 400 0,054 0.054 0.054 0.300 0.500 0.300 0.300 0.020 0.030 4.1 4.1 4.1 22.5 37.5 22.5 22.5 1.5 1.4 1,792 891 1,620 281 3,000 2,025 1,125 1,065 998 12,797 0 3,826 1.0 1.0 1.0 22.3 33.3 27.0 27.0 0.3 0.2 0 0 0 0 0 0 0 0 0 0 0 442 220 400 279 2,667 2,433 1,352 185 160 8,138 0 1,633 460 933 2 11,166 12.5 80 90 50 710 710 1,295 0.000 0.000 2 400 0 400 1 16,623 Ceiling fan Color television Total 250 683 0 0 100 100 100 100 250 683 933 0 0 0 Item Description Area Quantity -u- Value Htg HTM Sen Loss clg HTM Lat Gain Sen Gain Equipment Cooling Loads Item Name Cont. Gont.Output Output AverageSensible Latent ln-UseBtuh Btuh Output Percent Used per Hour Sensible Load Btuh Latent Load Btuh Detailed Room Loads - Room 2 - ADU-GYM verage Load Procedure) Calculation Mode: Room Length: Room Width: Area: Ceiling Height: Volume: Actual Winter lnfil.: ActualSummer lnfil Htg. & clg. nla nla 285.0 sq.ft. 11.0 ft. 3,135 cu.ft. O CFM O CFM Occurrences: System Number: Zone Number: SupplyAir: SupplyAir Changes: Actual WinterVent.: Percent of Supply.: Actual Summer Vent. Percent of Supply: 1 3 1 80 CFM 1.5 AC/hr 19 CFM 24 o/o 14 CFM 18 %o N-Wall-IECC 13X11 NE-Wa||-IECC 18 X 11 SE-Wa||-IECC 6 X 11 UP-Roof-IECC 285 X 1 Floor-IECC 1X2851285 143 198 66 285 285 0.054 0.054 0.054 0.020 0.030 4.1 4.1 4.1 1.5 1.4 579 802 267 428 401 1.0 1.0 1.0 0.3 0.2 0 0 0 0 0 o 0 143 198 66 74 64 sqs 0 338 47 460 2 1,392 Subtotals for Structure: lnfil.: Win.: 0.0, Sum.: 0.0 Ductwork: AED Excursion: People: 200 laUper, 230 sen/per: Lighting: Room Totals: 407 0.000 2,477 0 1,079 0.000 2 1 400 4003,556 Detailed Room Loads - Room 3 - Guest 2 (Average Load Procedure) Calculation Mode: Room Length: Room Width: Area: Ceiling Height: Volume: Actual Winter lnfil.: Actual Summer lnfil. Htg. & clg. nla nla 280.0 sq.ft. 11.0 ft. 3,080 cu.ft. O CFM O CFM Occurrences: System Number: Zone Number: Supply Air: Supply Air Changes: Actual WinterVent.: Percent of Supply.: Actual SummerVent. Percent of Supply: 1 3 1 156 CFM 3.0 AC/hr 30 CFM 20% 27 CFM 18 o/o NE-Wall-IECC 20 X 11 SE-Wall-IECC 17 X 11 SE-Gls-IECC shgc-O.3 68%S SE-Gls-doors shgc-0.35 68%S UP-Roof-IECC 280 X 1 Floor-IECC 1X2801280 Subtotals for Structure: lnfil.:Win.: 0.0, Sum.: 0.0 Ductwork: AED Excursion: People:200 laUper, 230 sen/per: Llohtins: Room Totals: 220 124 42 21 280 280 0.054 0.054 0.300 0.500 0.020 0.030 4.1 4.1 22.5 37.5 1.5 1.4 891 502 945 788 420 394 1.0 1.0 14.9 19.2 0.3 0.2 0 0 0 0 0 0 0 0 220 124 627 403 73 63 1,510 0 663 92 460 2 2,726 407 0.000 3,940 0 1,716 0.000 2 1 400 4005,656 lii'..1 i r.v,rcr (rt rli I r rlr., .,1,\ ii1r1;r I )i.):ligllirt li))o)rlcl:l i( ;i:,lii irlo)ir[q iiit k ), r.( )()) I ,ll :lliht l-:lcl[\',V;111r:, ii)].]lrl [0.]|) nlld (llii,,, ll li litrri,r I i rlj 11 p]i lrli Io1r:t i-l:, 1 r,lL;1 it I ;i irt:Lv/ 12 i Jr )l l rr'' Detailed Room Loads - Room 4 - Guest 1 (Average Load Procedure) Calculation Mode: Room Length: Room Width: Area: Ceiling Height: Volume: ActualWinter lnfil.: Actual Summer lnfil. Htg. & clg. nla nla 280.0 11.0 3,080 0 0 sq.ft. ft. cu.ft. CFM CFM Occurrences: System Number: Zone Number: SupplyAir: SupplyAir Changes: Actual Winter Vent.: Percent of Supply.: Actual Summer Vent. Percent of Supply: 1 3 1 219 CFM 4.3 AC/hr 30 CFM 14 o/o 39 CFM 18 Yo NE-Wall-IECC 20X11 SE-WaI|-IEGC 17 X 11 SE-Gls-IECC shgc-0.3 0%S SE-Gls-doors shgc-0.35 0%S UP-Roof-IECC 280 X 1 220 124 42 21 280 280 0.054 0.054 0.300 0.500 0.020 0.030 4.1 4.1 22,5 37.5 1,5 1.4 891 502 945 788 420 394 1.0 1.0 27.0 33.3 0.3 0.2 0 0 0 0 0 0 220 124 1 ,135 700 73 63Floor-IECC 1 X Subtotals for Structure: lnfil.:Win.: 0.0, Sum.: 0.0 Ductwork: AED Excursion: People: 200 laUper, 230 sen/per: Lighting: 3,940 0 1,716 0 2,315 0 933 129 460 2 407 0.000 0.000 0 2 400 1 Room Totals:5,656 400 3,839 .li11l::11 I ii r) L [;:ir I i] li::i ,rrj \il, I ,i i, r i lil' il I ir\r r. l,lr rr ):J: l ,i ; ir;l liritriil I i:ri if i: I r:t il.ir:l i li.i,, ,r l ' ji ir.irltl'rllli{rl I I Manual S Performance Data - System I - Great Room SSHP Cooling: Outdoor Dry Bulb: Outdoor Wet Bulb lndoor Dry Bulb: lndoor RH: Supply Airflow: 0 68 75 50 0 Sensible Gain: Latent Gain: Total Gain: Load SHR: Entering Dry Bulb: Entering Wet Bulb 37.706 3.000 40.706 0.93 0 0 Heating: Outdoor Dry Bulb lndoor Dry Bulb: lndoor RH: -5 70 30 Sensible Loss: Entering Dry Bulb SupplyAirflow: 45.425 60.9 648 This system's equipment was selected in accordance with ACCA Manual S. Cooling: Model Type:Air Source Heat Pump, Outdoor Model: NTXMSH48A182AA,,lndoor Model: TPEFYP054MA144A AHRI Reterence Number: 207517167, NominalCapacity: 54.000, Manufacturer: Mitsubishi Interpolation Results: Percent Load 37.706 3.000 40.706 of Load Sensible Capacity: Latent Capacity: TotalCapacity: 0.000 0.000 0.000 OVo 0To 0o/o Heating: Model Type:Air Source Heat Pump, Model: NTXMSH48A182AA, Nominal Capacity: 54.000, Manufacturer: Mitsubishi Results: PercentLoad of Load Heating Capacity: 54.000 45.425 119o/o Manual S Performance Data - System 2 - Master Wing SSHP Cooling: Outdoor Dry Bulb: Outdoor Wet Bulb: lndoor Dry Bulb: lndoor RH: SupplyAirflow: 0 68 75 50 0 Sensible Gain: Latent Gain: Total Gain: Load SHR: Entering Dry Bulb: Entering Wet Bulb: 12.198 1.050 13.248 0.92 0 0 Heating: Outdoor Dry Bulb: lndoor Dry Bulb: lndoor RH: -5 70 30 Sensible Loss: Entering Dry Bulb: SupplyAirflow: 18.727 61.9 271 This system's equipment was selected in accordance with ACCA Manual S. Cooling: Model Type:Air Source Heat Pump, Outdoor Model: NTXMSH36A142AA,lndoor Model: TPEADAO241AA80A, NTXDKS12A112AA AHRI Reference Number: 207517163, NominalCapacity: 36.000, Manufacturer: Mitsubishi Interpolation Results: Percent Load 12.198 1.050 13.248 of Load Sensible Capacity: Latent Capacity: TotalCapacity: 0.000 0.000 0.000 0% 0% 0o/o Heating: Model Type: Air Source Heat Pump, Model: NTXMSH36A142AA, Nominal Capacity: 45.000, Manufacturer: Mitsubishi Results: Heating Capacity:45.000 Load 18.727 Percent of Load 240o/o Manual S Performance Data - System 3 - Guest Wing SSHP Cooling: Outdoor Dry Bulb: Outdoor Wet Bulb: lndoor Dry Bulb: lndoor RH: SupplyAirflow: 0 68 75 50 0 Sensible Gain: Latent Gain: Total Gain: Load SHR: Entering Dry Bulb: Entering Wet Bulb 9.297 2.284 11.581 0.80 0 0 Heating: Outdoor Dry Bulb: lndoor Dry Bulb: lndoor RH: -5 70 30 Sensible Loss: Entering Dry Bulb: Supply Airflow: 18.098 56.9 243 This system's equipment was selected in accordance with ACCA Manual S. Cooling: Model Type:Air Source Heat Pump, Outdoor Model: NTXMSH36A142AA,lndoor Model: NTXDKSO9A112AA AHRI Reference Number: 207517163, NominalCapacity: 36.000, Manufacturer: Mitsubishi lnterpolation Results: Percent Load 9.297 2.284 11 .581 of Load Sensible Capacity: Latent Capacity: TotalCapacity: 0.000 0.000 0.000 0o/o 0o/o 0% Heating: Model Type:Air Source Heat Pump, Model: NTXMSH36A142AA, Nominal Capacity: 45.000, Manufacturer: Mitsubishi Results: Heating Capacity:45.000 Load 18.098 Percent of Load 249o/o Rhvac Online Alius Design Corps Carbondale, CO * Elite Software Development, Rimledge Ranch Rev 2 Page24 System 1 Room Load Summary 6 Office - Zone 1 subtotal --Zone 4-- 1 Mudroom - Zone 4 subtotal --Zone 5-- 5 Kitchen-Living - Zone 5 subtotal - Ventilation - Duct Latent - Return Duct - System 1 total 80 80 1,761 1,761 29 29 0-0 0 4,207 4,207 400 400 240 240 240 240 180 180 338 338 6 6 0-0 0 0 58 58 0 0 3 3 3 3 1,600 '1,600 37,595 37,595 2,641 614 614 0-0 36,649 36,649 423 2,332 37,706 800 800 1,092 359 348 3,000 2,094 2,094_ 1,gg; 2,094 2,094_ 1,gg; - 3,090 1,860 45,425 648 Note: Since the system is multizone, the Peak Fenestration Gain Procedure was used to determine glass sensible gains at the room and zone levels, 5o the sums of the zone sensible gains and airflows for cooling shown above are not intended to equal the totals at the system levei. Room and zone sensible gains and cooling CFM values are for the hour in which the glass sensible gain for the zone is at its peak. Sensible gains at the system level are based on the "Average Load Procedure + Excursion" method. Net Required: Recommended: 3.39 4.19 93o/o I 7o/o 75o/o I 25o/o 37,706 37,706 3,000 12,569 40,706 50,275 Room No Name Htg Sens Btuh Htg CFM Run Duct Size Run Duct Vel clg Sens Btuh clg Lat clg CFM Act sys CFM Min Min Btuh Area SF Cooling System Summary Cooling Tons Sensible/Latent SPlit Sensible Btuh Latent Btuh Total Btuh l/N irrrr.; 1 r rlllt1q1lrr (!,)rq)1ip;::, l(a;:tlil i,Io) rIj f r,ll li,), i( lI(.') l l'j l [i,) ii]ilj [\'^Tr.l (r).l Dh vrd k ] lt n n t r.l 11 (, ;.{1 npj[qd1111:t.1i,;i;;11ir.1iil ] i.1{1;17.71 |L ill hlorql.; (':,, ri I t n tcr li' Ia t: (tl :::'il',)'t System 2 Room Load Summary 7 Master_Bed 710 16,623 271 0-0 0 11,166 400 638 638 - Ventilation - Duct Latent - Return Duct 919 147 380 137 1331,185 885 - System 2 total 710 18,727 271 12,198 1,050 638 638 Net Required: Recommended: 1.10 1.36 92o/o I 9Vo 75o/o 125% 12,'t98 12,198 1,050 4,066 13,248 16,265 '!r:lr l{ i ri.i1 ir ,.1,:ry:, i'\ iii j:r l ll,;.tt i i:;11 il .j ii 1ti ilt r i ll .i . i\,' ...11, i) ir)i ill,;,',ti r r ,.li ,;ljl! ir 'ili ,i ,; i117 ] r\il t, r( ii0lL tl rr,Ir. llii'l i i, ; lr.j', tii.}r tli li. /,:rlri. ir li :.ji,iil ri,ir:li t: tl irtl. I irliirr il i;;ltrr: lirll, ltililLri l rliiliri l lr(..i .lrl, J j lf]( i :i i,v,4i.l i.::jij,l li:ii{r ir,r I iriflrlllli Rhvac Online Alius Design Corps Carbondale, CO * Elite Softntare Development, Rimledge Ranch Rev 2 Page26 3 Room Load Summary e 2 ADU-GYM 3 Guest 2 4 Guest I - Ventilation - Duct Latent - Return Duct - System 3 total 285 280 280 3,556 5,656 5,656 1,837 58 92 92 ,oi 0-0 0-0 0-0 0 0 0 1,392 2,726 3,839 294 400 400 400 760 166 158 2,284 80 156 219 80 156 219 845 1,394 18,098 1,046 9,297 455 455 Net Required: Recommended Actual: 0.97 1.03 3.00 80o/o I 20o/o 75% I 25% 670/o I 33o/o 9,297 9,297 24,000 2,284 3,099 12,000 11 ,581 12,397 36,000 Equipment Data Type: Model: lndoor Model: Brand: Efficiency: Sound: Capacity: Adjusted Capacity: Sensible Capacity: Latent Capacity: AHRI Reference No Heating System Air Source Heat Pump NTXMSH364142AA Cooling System Air Source Heat Pump NTXMSH36A142AA NTXDKSO9All2AA 0 45,000 Btuh nla nla nla nla O SEER 0 36,000 Btuh 33,200 Btuh 24,000 Btuh 12,000 Btuh 207517163 This system's equipment was selected in accordance with ACCA Manual S. Manual S equiprhent sizing data: SODB: 87F, SOWB: 68F, WODB: -!f, SIDB: 75F, SIRH: 50%9, \t!l-Dp17_0F, Sen. gain: Q,291 Btul1,_ Lat. gain: 2,2843tuh, Sen.loss: 18,098 Btuh, EnterinS c]S.ggilDB:78.3F, Enterin-g clg. coilWB:63.1F, Entering htg. coilDB:56.9F, Clg. boil TD: 20F, Htg. coil TD: 70F, Req. clg. airflow: 455 CFM, Req. htg. airflow: 243 CFM Room No Name Htg Sens Btuh Htg CFM Run Duct Size Run Duct Vel clg Sens Btuh clg Lat clg CFM Act sys CFM Min Min Btuh Area SF Cooling System Summary Cooling Tons Sensible/Latent SPlit Sensible Btuh Latent Btuh Total Btuh Rhvac Online Alius Design Corps Carbondale, CO s Elite Software Development, Inc Rimledge Ranch Rev 2 Per Page27 Equipment Data - System 1 - Great Room SSHP Cooling System Type: Outdoor Model: lndoor Model: Outdoor Manufacturer: AHRI Reference No.: Nominal Capacity: Adjusted Capacity: Efficiency: Air Source Heat Pump NTXMSH48A182AA TPEFYPO54M 41444 Mitsubishi 207517167 54000 27600 O SEER Heating System Type: Model: Manufacturer: Capacity: Efficiency: Air Source Heat Pump NTXMSH48A182AA Mitsubishi 54000 This system's equipment was selected in accordance with ACCA Manual S. Manual S equipment sizing data: SODB: 87F, SOWB: 68F, WODB: -5F, SIDB: 75F, SIRH: 50%, WIDB: 70F, Sen. gain: 37,706 Btuh, Lat. gain:3,000 Btuh, Sen. loss: 45,425 Btuh, Entering clg. coilDB:76.6F, Entering clg. coilWB:62.3F, Entering htg. coil DB:60.9F, Clg. coilTD: 20F, Htg. coilTD: 70F, Req. clg. airflow: 1997 CFM, Req. htg. airflow: 648 CFM Equipment Data - System 2 - Master Wing SSHP Cooling System Type: Outdoor Model: lndoor Model: Outdoor Manufacturer: AHRI Reference No.: Nominal Capacity: Adjusted Capacity: Efficiency: Air Source Heat Pump NTXMSH36A142AA TPEADAO24 1 AA8OA, NTXDKS 1 2A1 1 2PA, Mitsubishi 207517163 36000 32800 O SEER Heating System Type: Air Source Heat PumP Model: NTXMSH36A142FA, Manufacturer: Mitsubishi Capacity: 45000 Efficiency: This system's equipment was selected in accordance with ACCA Manual S. Manual S equipment sizing data: SODB: 87F, SOWB: 68F, WODB: -5F, SIDB: 75E SIRH: 507o, WIDB: 70F, Sen. gain: 12,198 Btuh, Lat. gain: 1,050 Btuh, Sen. loss: 18,727 Btuh, Entering clg, qollDB:76.8F, Entering clg_. coilWB:62.4F, Entering htg. coilDB:61.9F, Clg. coilTD:20F, Htg. coilTD: 70F, Req. clg. airflow:638 CFM, Req. htg. airflow: 271CFM Equipment Data - System 3 - Guest Wing SSHP Cooling System Type: Outdoor Model: lndoor Model: Outdoor Manufacturer: AHRI Reference No.: Nominal Capacity: Adjusted Capacity: Efficiency: Air Source Heat Pump NTXMSH36A142PA, NTXDKSOgAll2AA Mitsubishi 207517163 36000 33200 O SEER Heating System Type: Model: Manufacturer: Capacity: Efficiency: Air Source Heat Pump NTXMSH36A142AA Mitsubishi 45000 This system's equipment was selected in accordance with ACCA Manual S. Manual S equipment sizing data: SODB: 87F, SOWB: 68F, WODB: -5F, SIDB: 75F, SIRH: 50%, WIDB: 70F, Sen. gain: 9,297 Btuh, Lat. gain: 2,284Brhuh, Sen. loss: 18,098 Btuh, Entering clg. coilDB: 78.3F, Entering clg. coilWB:63.1F, Entering htg. coilDB:56.9F, Clg. coil TD:20F, Htg. coil TD: 70F, Req. clg. airflow: 455 CFM, Req. htg. airflow: 243 CFM