2O15 lnternational Residential Gode
APPENDIX V TINY HOUSES
CHAPTER PART AVl Ol.GENERAL
AV101.1 Scope. This appendix shall be applicable to tiny houses used as single dwelling units. Tiny
houses shall comply with this code except as otherwise stated in this appendix.
CHAPTER PART AVl02- DEFINITIONS
AV102.1 General. The following words and terms shall, for the purposes of this appendix, have the
meanings shown herein. Refer to Chapter 2 of this code for general definitions.
EGRESS ROOF ACCESS WINDOW. A skylight or roof window designed and installed to satisfy the
emergency escape and rescue opening requirements in Section R310 .2.
LANDING PLATFORM. A landing provided as the top step of a stairway accessing a loft.
LOFT. A floor level located more than 30 inches (762 mm) above the main floor and open to it on at least
one side with a ceiling height of less than 6 feet 8 inches (2032 mm), used as a living or sleeping space.
TINY HOUSE. A dwelling that is 400 square feet (37 m) or less in floor area excluding lofts.
CHAPTER PART AVl03- CEILINGHEIGHT
AVl03.1 Minimum ceiling height. Habitable space and hallways in tiny houses shall have a ceiling
height of not less than 6 feet 8 inches (2032 mm). Bathrooms, toilet rooms, and kitchens shall have a
ceiling height of not less than 6 feet 4 inches (1930 mm). Obstructions shall not extend below these
minimum ceiling heights including beams, girders, ducts, lighting and other obstructions.
Exception: Ceiling heights in lofts are permitted to be less than 6 feet 8 inches (2032 mm).
CHAPTER PART AV104. LOFTS
AV|04.1 Minimum loft area and dimensions. Lofts used as a sleeping or living space shall meet the
minimum area and dimension requirements of Sections AV104.1 .1 through AV1 04.1 .3.
AVl04.1.1 Minimum area. Lofts shall have a floor area of not less than 35 square feet (3.25 m).
AV104.1.2 Minimum dimensions. Lofts shall be not less than 5 feet (1524 mm) in any horizontal
dimension.
AV104.1.3 Height effect on loft area. Portions of a loft with a sloping ceiling measuring less than 3 feet
(g14 mm) from the finished floor to the finished ceiling shall not be considered as contributing to the
minimum required area for the loft.
Exception: Under gable roofs with a minimum slope of 6:12, portions of a loft with a sloping ceiling
measuring less than 16 inches (406 mm) from the finished floor to the finished ceiling shall not be
considered as contributing to the minimum required area for the loft.
AVl O4.2 Loft access. The access to and primary egress from lofts shall be any type described in
Sections AV 1O4.2.1 through AV1 04.2.4.
AV104.2.1 Stairways. Stainruays accessing lofts shall comply with this code or with Sections AV104.2.1 .1
through AV104.2.1.5.
AV104.2.1.1 Width. Stairways accessing a loft shall not be less than 17 inches (432 mm) in clear width at
or above the handrail. The minimum width below the handrail shall be not less than 20 inches (508 mm).
-\' *,*uit''; ;l-..j f $r',ri:ffi;i
4V104.2.1.2 Headroom. The headroom in stairuvays accessing a loft shall be not less than 6 feet 2
inches (1880 mm), as measured vertically, from a sloped line connecting the tread or landing platform
nosings in the middle of their width.
4V104.2.1.3 Treads and risers. Risers for stairs aoccssing a loft shall bc not lcss than 7 inchcs (178
mm) and not more than 12 inches (305 mm) in height. Tread depth and riser height shall be calculated in
accurdarrce witlr urre u[ tlte fulluwilrg funrrulas:
1. The tread depth shall be 20 inches (508 mm) minus 4/3 of the riser height, or
2. The riser height shall be 15 inches (381 mm) minus 3/4 of the tread depth.
4V104.2.1-4 Landing platforms. The top tread and riser of stairways accessing lofts shall be constructed
as a landing platform where the loft ceiling height is less than 6 feet 2 inches (1880 mm) where the
stairway meets the loft. The landing platform shall be 18 inches to 22 inches (4571o 559 mm) in depth
measured from the nosing of the landing platform to the edge of the loft, and 10 to 18 inches (400 to 457
mm) in height measured from the landing platform to the loft floor.
AV104.2.1.5 Handrails. Handrails shall comply with Section R31 1 .7.8.
4V104.2.1.6 Stairway guards. Guards at open sides of stairways shall comply with Section R312.1 .
AV',04.2.2 Ladders. Ladders accessing lofts shallcomply with Sections AV104.2.1 and AY1O4.2.2.
4V104.2.2.1 Size and capacity. Ladders accessing lofts shall have a rung width of not less than 12
inches (305mm) and 10 inches (254 mm) to 14 inches (356 mm) spacing between rungs. Ladders shall
be capable of supporting a 200 pound (75 kg) load on any rung. Rung spacing shall be uniform within 3/8-
inch (9.5 mm).
AV1O4-2.2.2lncline. Ladders shall be installed at 70 to 80 degrees from horizontal.
4V104.2.3 Alternating trcad dcvices. Alternating tread devices accessing lofts shall comply with
Sections R31 1 .7.1 1 .1 and R311 .7 .11 .2. The clear width at and below the handrails shall be not less than
20 inches (508 mm).
4V1O4.2.4 Ships ladders. Ships ladders accessing lofts shall comply with Sections R31 1 .7.12.1 and
R311.7.12.2. The clear width at and below handrails shall be not less than 20 inches (508 mm).
AV104.2.5 Loft Guards. Loft guards shall be located along the open side of lofts. Loft guards shall not be
less than 36 inches (914 mm) in height or one-half of the clear height to the ceiling, whichever is less.
CHAPTER PART AV105- EMERGENGY ESCAPE AND RESCUE OPENINGS
AV105.1 General. Tiny houses shall meet the requirements of Section R310 for emergency escape and
rescue openings.
Exception: Egress roof access windows in lofts used as sleeping rooms shall be deemed to meet the
requirements of Section R310 where installed such that the bottom of the opening ls not more than 44
inohes (1118 mm) abovc thc loft floor, provided the egress roof access window complies with the
minimum opening area requirements of Section R310 .2.1.