HomeMy WebLinkAboutConditions of PermitCONDITIONS OF PERMIT
BLRE- 11-24-8996
KBBS HOLDINGS LLC
NEW SINGLE-FAMILY RESIDENCE _ TINY HOME
TBD COUNTY ROAD 120, GWS
LOOKOUT MOUNTAIN RANCHES
1) THE APPROVED PLANS ARE TO BE ON-SlrE FOR INSPECTIONS.
2) SANTTARY FACILTTTES ARE REOUIRED TO BE PROVIDED FOR WORKERS.
3) A LIST OF REOUIRED INSPECTIONS WILL BE ATTACHED TO THE PLANS. THE STATE
IS TO PERMIT AND APPROVE THE ELECTRICAL WORK.
RMITS
4) UNDERGROUND UTTL|TY LOCATES rS THE RESPONSTBTLTry OF THE OWNER OR
CONTRACTOR. 811 IS THE COLORADO UTILITY LOCATE HOT LINE.
5) DRAINAGE ACROSS PROPERry LINES SHALL NOT EXCEED THAT WHICH EXISTED
PRIOR TO GRADING. EXCESS OR CONCENTRATED DRAINAGE SHALL BE
CONTAINED ON SITE OR DIRECTED TO AN APPROVED DRAINAGE FACILIry.
EROSION OF THE GROUND IN THE AREA OF DISCHARGE SHALL BE PREVENTED BY
INSTALLATION OF NON-EROSIVE DOWN DRAINS OR OTHER DEVICES.
6) ALL BACKFLOW PREVENTERS ARE REQUIRED TO BE TESTED AND CERTIFIED BY A
LICENSED BACKFLOW SPECIALIST AFTER INSTALLATION AND PRIOR TO ISSUANCE
OF THE CERTIFICATE OF OCCUPANCY.
7) ELECTRTCAL CODE COMPLIANCE WILL BE DETERMINED BASED ON FIELD
INSPECTIONS PERFORMED BY THE STATE ELECTRICAL INSPECTOR, (303) 869-3458.
PLEASE HAVE THE INSPECTOR SIGN THE BUILDING CARD OR PROVIDE WRITTEN
DOCUMENTATION OF THE INSPECTIONS.
B) THE ELECTRICAL CODE REOUIRES A SEPARATE ELECTRICAL PERMIT FOR LOW
VOLTAGE FIRE ALARMS THAT HAS AN ALARM PANEL AND SEND A NOTIFICATION
TO THE FIRE DISTRICT WHEN UNDER ALARM. A ROUGH-IN INSPECTION WITH THE
STATE ELECTRICAL INSPECTOR IS REOUIRED (303) 869-3458. PLEASE HAVE THE
INSPECTOR SIGN THE BUILDING CARD OR PROVIDE WRITTEN DOCUMENTATION
OF THE INSPECTION.
9) GEOTECHNTCAL OBSERVATION lS REOUIRED WHEN THE EXCAVATION lS
COMPLETE AND WRITTEN VERIFICATION BE SUPPLIED AT FOOTING INSPECTION,
1600 PSF. SEE THE ATTACHED ENGINEER'S LETTER REVISING THE BEARING
CAPACITY OF THE STRUCTURAL DESIGN
10)ALL EXTERTOR LIGHTING lS TO BE DOWNCAST AND SHIELDED.
1 1)A PASSTNG BLOWER DOOR TEST rS REOUTRED TO BE SUBMTTTED pRrOR TO
ISSUING THE CERTIFICATE OF OCCUPANCY. SMALLER HOMES HAVE DIFFICULry
TIME COMPLYING WITH 3 AIR CHANGES AN HOUR AT 50 PASCELS. THE
EXCEPTION ALLOWED IN THE 2021 IECC STATED BELOW IS ACCEPTIBLE.
Exception: When testing individual dwelling
units, an air leakage rate not exceeding
0.30 cubic feet per minute per square foot
[0.008 m3/(s x m2)] of the dwelling unit
enclosure area, tested in accordance with
ANSI/RESNET/lCC 380, ASTM E779 or
ASTM E1827 and reported at a pressure of
0.2 inch w.g. (50 Pa), shali be an accepted
alternative permitted in all climate zones
for:
1. Attached single and multiple family
building dwelling units.
2. Buildings or dwelling units that are
1 ,500 square feet (1 39.4 m2) or smaller.
12)SEE THE ATTACHED APPENDIX V FOR ADOPTED TINY HOME CRITERIA
13)THE CRAWLSPACE ACCESS IS PICTORIALLY SHOWN TO SMALL BUT LABELED
24"X18". THE ACCESS IS TO BE LARGE ENOUGH TO REMOVE THE WATER HEATER
SHOWN IN THE CRAWLSPACE AND NOT BE LESS THAN 24"X18''.
14)ANY EXPOSED FOAM tS TO BE COVERED W|TH AN tcNtTtON BARRTER OR A
THERMAL BARRTER BASED ON LOCAT|ON. (tRC R316)
1 5)THE HOME IS TO BE SUPPLIED WITH MECHANICAL VENTILATION OF OUTDOOR
AlR. THE MINIMUM VENTTLATTON RATE tS TO BE CFM = (0.01X TOTAL SOUARE
FOOTAGE OF THE HOUSE) + 7.5 X (NUMBER OF BEDROOMS +1)GENERAL NOTES
ON THE PLANS INDICATE WHOLE HOUSE VENTILATION,
16)MINIMULLY THE ICE SHIELD IS TO BE INSTALLED AT THE EAVES TO A MINIMUM 24"
UP FROM THE INSULATED WALLS.
17)THE DRYER lN A CLOSET WILL REQUTRE 100 SOUARE TNCHES OF MAKE-UP AtR. (tRC
G2439.4)
18)ENGINEER STAMPED TRUSS DRAWINGS ARE REOUIRED TO BE PROVIDED TO THE
INSPECTOR AT I-RAMING INSPTCTION.
19)ALL SHOWER DOORS ARE REOUTRED TO MAtNTA|N 22" tN THE CLEAR AND ARE
REOUIRED TO SWING OUT.
20)ANY MECHANICAL EQUIPMENT IN THE CRAWLSPACE IS TO BE WITHIN 20'OF THE
CRAWLSPACE ACCESS.
21)THE LOFT WTNDOW tS OVER 72" ABOVE GRADE AND ARE LESS THAN 24" ABOVE
THE FINISHED FLOOR. IT WILL BE REOUIRED TO HAVE WINDOW OPENING
LIMITING DEVICE SO THE WINDOW CANNOT OPEN MORE THAN 4".